5.1. Functional test
BEKOMAT
8/9
®
Check normal function
To check the solenoid valve, press the TEST button briefly (approx. 2 sec.).
Red LED "Alarm" flashes, yellow LED "Valve" lights up
Valve opens for condensate discharge
Test fault signal
To test the solenoid valve, shut off the condensate inlet and press the TEST button for
approx. 1 minute.
Alarm relay switches
Release the TEST button
BEKOMAT
returns to normal function
®
•
Open condensate inlet again!
•
Minimum operating pressure 0.5 bar!
Installation and operation manual