UPS5000-H-(1200 kVA-1600 kVA) Quick Guide (100 kVA Power Modules, Three-Phase Three-Wire)
03
Installing Power Cables Between the UPS and the Inductor Cabinet
Installing Power Cables between the UPS and the Inductor Cabinet (1200 kVA)
Cables have been preinstalled and bound in the inductor cabinet.
The cables from the inductor cabinet to the UPS are configured based on the longest cable
length before delivery. If short cables are needed in the actual installation scenario, you can
cut the excess cables and crimp terminals.
Cables must be bound to the nearest beam or cable bridge according to the route shown in
the figure.
Do not bind signal cables and power cables together.
The number and colors of cables in the figures are for reference only.
Copper bars are heavy. Two persons are required.
Power cable hole
Signal cable hole
Single Power Source
Different Power Sources
5
Side view of the UPS
Signal cable hole
Power
cable
hole
Side view
of the UPS
Signal cable hole Power
cable
hole