Series Preface Thank you for choosing SAJ solar inverter. We are pleased to provide you first-class products and exceptional service. This manual includes information for installation, operation, maintenance, trouble shooting and safety. Please follow the instructions of this manual so that we can ensure delivery of our professional guidance and wholehearted service.
Series Chapter 1 Safety Precautions 1.1 Scope of Application This User Manual describes instructions and detailed procedures for installing, operating, maintaining, and troubleshooting of the following SAJ on-grid inverters: R5-0.7K-S1;R5-1K-S1;R5-1.5K-S1;R5-2K-S1;R5-2.5K-S1;R5-3K-S1; R5-3K-S2;R5-3.6K-S2;R5-4K-S2;R5-5K-S2;R5-6K-S2;R5-7K-S2;R5- 8K-S2 Please keep this manual all time available in case of emergency.
· Do not stay close to the inverter while there are severe weather conditions including storm, lighting, etc. · Before opening the housing, the SAJ inverter must be disconnected from the grid and PV generator; you must wait for at least five minutes to let the energy storage capacitors completely discharged after disconnecting from power source.
Page 7
Series · Risk of damage due to improper modifications. NOTICE · Public utility only. · The solar inverter is designed to feed AC power directly to the public utility power grid; do not connect AC output of the inverter to any private AC equipment. - 6 -...
The inverter complies with the safety instructions from China's Quality Center. No unauthorized operations or modifications Any unauthorized operations or modifications are strictly forbidden, if any defect or damage (device/person) occurs, SAJ shall not take any responsibility for it. - 7 -...
Series Chapter 3 Product Information 3.1 Application Scope of Products R5-XK-SX products are on-grid single phase inverters without transformers, and the inverters are important components of on-grid solar power systems. The R5 inverter converts the DC generated by solar panels into AC which is in accordance with the requirements of public grid and send the AC into the grid, Figure 3.1 shows the structural diagram of the typical application system of R5 inverter.
Series 3.2 Specification for Product Model R5 – XK – S2 ① ② ③ ① R5 represents for product name. ② XK represents rated power XkW of inverter, for example 3K means 3kW. ③ S means single phase; 1 or 2 represents that the inverter has the function of one or double MPPT.
Page 11
Series Figure 3.4 Dimensions of R5-7K/8K-S2 - 10 -...
Series 3.4 Datasheet R5-0.7K/1K/1.5K-S1 R5-0.7K-S1 R5-1K-S1 R5-1.5K-S1 Type Input (DC) Max. PV Array Power [Wp]@STC 1050 1500 2250 Max. DC Voltage [V] MPPT Voltage Range [V] 40-425 Nominal DC Voltage [V] Start Voltage [V] Min. DC Voltage [V] Max. DC Input Current [A] 12.5...
Page 13
Series GFCI Monitoring Integrated Grid Monitoring Integrated AC Short Circuit Current Protection Integrated AC grounding detection Integrated DC Surge Protection Integrated AC Surge Protection Integrated Thermal Protection Integrated Anti-island protection monitoring Interface AC Connection Plug-in connector DC Connection Human Machine Interface LED+(Bluetooth/Wi-Fi+APP) Communication Port RS232(USB)+RS485(RJ45)
Page 14
Series R5-2K/2.5K/3K-S1 R5-2K-S1 R5-2.5K-S1 R5-3K-S1 Type Input (DC) Max. PV Array Power [Wp]@STC 3000 3750 3900 0Max. DC Voltage [V] MPPT Voltage Range [V] 50-450 Nominal DC Voltage [V] Start Voltage [V] Min. DC Voltage [V] Max. DC Input Current [A] 12.5 Max.
Page 15
Series Grid Monitoring Integrated AC Short Circuit Current Protection Integrated AC grounding detection Integrated DC Surge Protection Integrated AC Surge Protection Integrated Thermal Protection Integrated Anti-island protection monitoring Interface AC Connection Plug-in connector DC Connection Human Machine Interface LED+(Bluetooth/Wi-Fi+APP) Communication Port RS232(USB)+RS485(RJ45) Communication Mode Wi-Fi/GPRS/4G(Optional)
Page 16
Series R5-3K/3.6K/4K/5K/6K-S2 R5-3K-S2 R5-3.6K-S2 R5-4K-S2 R5-5K-S2 R5-6K-S2 Type Input (DC) Max. PV Array Power [Wp]@STC 4500 5520 6000 7500 9000 Max. DC Voltage [V] MPPT Voltage Range [V] 90-550 Nominal DC Voltage [V] Start Voltage [V] Min. DC Voltage [V] Max.
Page 17
Series DCI Monitoring Integrated GFCI Monitoring Integrated Grid Monitoring Integrated AC Short Circuit Current Protection Integrated AC grounding detection Integrated DC Surge Protection Integrated AC Surge Protection Integrated Thermal Protection Integrated Anti-island protection monitoring Interface AC Connection Plug-in connector DC Connection Human Machine Interface LED+(Bluetooth/Wi-Fi+APP) Communication Port...
Page 18
Series R5-7K/8K-S2 R5-7K-S2 R5-8K-S2 Type Input (DC) Max. PV Array Power [Wp]@STC 10500 12000 Max. DC Voltage [V] MPPT Voltage Range [V] 90-550 Nominal DC Voltage[V] Start Voltage [V] Min. DC Voltage [V] Max. DC Input Current [A] 25/12.5 Max. DC Short Current [A] 30/15 Number of DC Connection Sets per MPPT Number of MPPT...
Page 19
Series Grid Monitoring Integrated AC Short Circuit Current Protection Integrated AC grounding detection Integrated DC Surge Protection Integrated AC Surge Protection Integrated Thermal Protection Integrated Anti-island Protection Monitoring Interface AC Connection Terminal Block DC Connection Human Machine Interface LED+(Bluetooth/Wi-Fi+APP) Communication Port RS232(USB)+RS485(RJ45) Communication Mode Wi-Fi/GPRS/4G(Optional)
4.2 Pre-installation Check 4.2.1 Check the Package Although SAJ’s inverters have surpassed stringent testing and are checked before leaving factory, it is still possible that the inverters may suffer damages during transportation. Please check the package for any obvious signs of damage, and if such evidence is present, do not open the package and contact your dealer as soon as possible.
Series 4.3 The Determination of the Installation Method and Position 4.3.1 Mounting Method Figure 4.1 Mounting method ① The equipment employs natural convection cooling method, and it can be installed indoor or outdoor. ② Please install the equipment under the guidance of Figure 4.1. Vertical installation on floor level is recommended.
Series To make sure the installation spot is suitably ventilated, if multiple SAJ on-grid olar inverters are installed in the same area, the following safety clearance in Figure 4.2 shall be followed for proper ventilation conditions. 4.2 Installation position 4.4 Mounting Procedure 4.4.1 Mark the Positions of the Drill Holes of the Rear Panel...
Page 23
Series Figure 4.4 Dimensions of rear panel of R5-3K/3.6K/4K/5K/6K-S2 Figure 4.5 Dimensions of rear panel of R5-7K/8K-S2 4.4.2 Drill Holes and Place the Expansion Tubes According to the guides, drill 3 holes in the wall (in conformity with position marked in Figure 4.6&Figure 4.7), and then place expansion tubes in the holes using a rubber mallet.
Page 24
Series Figure 4.7 Drill holes’ dimensions of R5-3K/3.6K/4K/5K/6K/7K/8K-S2 4.4.3 Mount the Screws and the Rear Panel The panels should be mounted in the mounting position by screws as shown in Figure 4.8. Figure 4.8 Mount the rear panel of R5-0.7K-3K-S1 & R5-3K-8K-S2 4.4.4 Mount the Inverter Carefully mount the inverter to the rear panel as shown in Figure 4.9 and 4.10, Make sure that the rear part of the equipment is closely mounted to the rear panel.
Page 25
Series Figure 4.9 Mount R5-0.7K-3K-S1 & R5-3K-8K-S2 inverter Fig. 4.10 Fasten the inverter and hanging panel with screws 4.4.5 Install Anti-theft Lock As shown in figure 4.11, anti-theft lock could be added to the inverter and hanging panel. Diameter of the lock hole is φ6.0mm and anti-theft lock with a φ5.0mm diameter of lock hook shall be recommended.
Series Chapter 5 Electrical Connection 5.1 Safety Instruction for Hot-line Job Electrical connection must only be operated by professional technicians. Please keep in mind that the inverter is a bi-power supply equipment. Before connection, necessary protective equipment must be employed by technicians, including insulating gloves, insulating shoes and safety helmet.
Series 5.2 Specifications for Electrical Interface Figure 5.1 Electrical interface of R5-0.7K/1K/1.5K/2K/2.5K/3K-S1 Code Name DC Switch DC Input Decompression Valves RS232 Communication(GPRS/Wi-Fi/4G) Ground Connection RS485 Communication AC Output DRM( Optional) Table 5.1 Specifications for interface - 27 -...
Page 29
Series Figure 5.2 Electrical interface of R5-3K/3.6K/4K/5K/6K-S2 Code Name DC Switch DC Input RS485 Communication RS232 Communication(GPRS/Wi-Fi/4G) Ground Connection AC Output Decompression Valves Table 5.2 Specifications for interface - 28 -...
Page 30
Series Figure 5.3 Electrical interface of R5-7K/8K-S2 Code Name DC Switch Decompression Valves DC Input RS232 Communication(GPRS/Wi-Fi/4G) RS485 Communication Ground Connection AC Output Table 5.3 Specifications for interface - 29 -...
Series 5.3 AC Connection Wire cross sectional area Type External diameter(mm) recommended value/max. value(mm² ) R5-3K/3.6K/4K/5K/6K-S2 4.0 /6.0 4.2~5.3 R5-7K/8K-S2 3*8.37/3*10 15~22 Table 5.3 Recommended power grid connecting cable specification If the grid-connection distance is too far, please select AC cable with larger diameter as per the actual condition.
Page 32
Series Figure 5.6 Connect cable ③ Screw all parts of the AC connector. Figure 5.7 Screw the connector ④ Connect the AC connector to the equipment securely, ensuring the pins are connected directly. Then the connection of AC cable is completed. Figure 5.8 Connect the inverter 5.3.3 R5-7K/8K-S2AC Side Electrical Connection ①...
Page 33
Series Fig. 5.9 Connecting the cable ② After fixing the cover at the AC output wire terminal with screws, tighten up the AC waterproof nut. Fig. 5.10 Tighten up AC interface protective cover and the locker - 32 -...
Series 5.4 DC Side Connection Cross-sectional area of cables(mm² ) Outside diameter of the cables (mm) Scope Recommended value 4.0-6.0 4.2~5.3 Table5.4 Recommended specifications of DC cables DC connector is made up of the positive connector and the cathode connector Figure 5.11 Positive connector 1.
Page 35
Series Connecting Procedures: 1. Tighten the lock screws on positive and cathode connector. 2. Use specified strip tool to strip the insulated enclosure of the positive and cathode cables with appropriate length. 1.Positive cable 2. Cathode cable Figure 5.13 Connecting cables 3.
Page 36
Series 1. Connection port Figure 5.14 Connect the inverter NOTICE · Before inserting the connector into DC input terminal of the inverter, please make sure that the DC switch of the inverter is OFF. · Please use the original H4 terminal to install. - 35 -...
Series 5.5 Communication Connection R5 inverter is standardly equipped with a RS485 interface and a RS232 interface. Figure5.15 RS485 pin Pin Number Description Effect GND_W Ground wire +7V_W Power supply RS485-A Transmission RS485 differential signal RS485-B Table 5.6 RS485 pin port definition - 36 -...
Page 38
Series Figure5.16 RS232 pin Pin Number Description Effect Power supply RS-232 TX Send data RS-232 RX Receive data Ground wire Table 5.7 USB pin port definition 1. USB interface could be externally connected with eSolar GPRS/4G module, for operation in details please refer to eSolar GPRS/4G module quick installation guide. 2.
Series Chapter 6 Debugging Instructions 6.1 Introduction of Human-computer Interface Figure 6.1 Human-computer interface A/B/C are double-color LED lamps which could show green light or red light at the same time Description LED lamps state Flicker: 3 s/time The inverter is just on power. Green Flicker:0.5 s/time The inverter is in second countdown on-grid state.
Account---Please use the installer account to login. Note: For the end user, please download and install the “eSolar Air” APP and log in to the APP or SAJ eSolar O&M Portal to register your account. 6.2.2 Nearby Monitoring Connecting way 1 — Bluetooth connection After installing the eSolar GPRS/4G module(with built-in Bluetooh) the mobile phone could be directly connected with the inverter via Bluetooth.
Page 41
Series Connection setting iOS system operation steps 1. Choose “setting” →choose “Bluetooth””→ open 2.Log in APP → choose “My” interface → choose “Bluetooth” “Remote control” → choose connection way as “Bluetooth ” Connection Please choose a connection method Bluetooth WiFi Cloud Note (1)Bluetooth is a kind local connection,...
Page 42
Series Connection setting Android system operation steps 1.Choose “setting” →choose “Bluetooth””→ open 2.Log in APP → choose “My” interface → choose “Bluetooth” “Remote control” → choose connection way as “Bluetooth ” Connection Please choose a connection method Bluetooth WiFi Cloud Note (1)Bluetooth is a kind local connection,...
Page 43
Series Equipment information Communication information of the inverter such as connection way, running state, basic information, running information, power information and events information could be checked. 1. Click “Basic info” Inverter model, Module SN code, Module firmware version, Communication board firmware version, Main board firmware version, Slave board firmware version could be checked.
Page 44
Series Device info Bluetooth:R5-5K-S2:00001 R5S2502G1815E00001 Basic info Event info Running info Power info PV information Grid power information XXHz N/Hz N/Hz Battery information Fig. 6.4 Running information 3. Click “Power info” Current power, today energy, monthly energy, yearly energy and total energy could be checked.
Page 45
Series 4. Click “Event info” Time of the events, events sequence number (referring to fault codes details in Chapter 7 Fault Codes and Common Troubleshooting) and events content of the faults of the inverter could be checked. Fig. 6.6 Events information Connecting way 2 —...
Page 46
Series Connection setting Please refer to the eSolar WiFi module operating manual for more details in operation. Equipment information Connection way, running state, basic information, running information, power information and events information of the communication of the inverter could be checked.
Page 47
Series 6.2.3 Remote Monitoring 1. Connect the internet via the eSolar GPRS/4G module, and upload the inverter data onto the server and customers could monitor running information of the inverter remotely via the eSolar Web Portal or their mobile customer terminals. 2.
Series Chapter 7 Fault Code and Troubleshooting Error Code Explanation Relay Error Master Storer Error Master High Temperature Master Low Temperature Master Interior Communication Error Master GFCI Devices Error Master DCI Devices Error Master Current Sensor Error Master Grid Over Voltage Master Grid Low Voltage Master High average voltage of 10 minutes Master Over Frequency Master...
Page 49
Check whether the radiator is blocked, whether the inverter is High Temperature in too high or too low temperature. If the above mentioned are Error in normal, please contact your distributor or call SAJ technical support. If this error occurs frequently, please contact your distributor GFCI Device Error or call SAJ technical support.
Page 50
Overcurrent above mentioned are in normal, please contact your distributor or call SAJ technical support. Check the settings of the solar panel. SAJ designer can help Over Bus Voltage you. If the above mentioned are in normal, please contact your distributor or call SAJ technical support.
Series Fault Information Troubleshooting control board and display board. If the above mentioned are in normal, please contact your distributor or call SAJ technical support. Check if connection of the AC output grounding terminal is Null line-to-earth stable and reliable. If the condition as above is normal, voltage fault please contact your distributor or call SAJ technical support.
Series Chapter 9 Contact SAJ Guangzhou Sanjing Electric Co., Ltd. SAJ Innovation Park, No.9, Lizhishan Road, Guangzhou Science City, Guangdong, P.R.China. Web: http: //www.saj-electric.com Technical Support & Service Tel:+86 20 6660 8588 Fax:+86 20 6660 8589 E-mail: service@saj-electric.com International Sales...
Series SAJ Warranty Policy 1.1 Standard Warranty Period Starting from the date of shipment from SAJ factory or 60 months (5 years) starting from the date of purchased invoice marked (whichever is longer). 1.2 Extension of Warranty The purchaser of SAJ inverters should extend the warranty period in 18 months from the date of settlement or 30 months from the date of shipment from SAJ by providing the serial number of the unit and purchased receipt (whichever is shorter).
Page 54
You will not receive a new certificate, as your entitlement is documented at SAJ. If the inverter needs to be replaced in emergency, SAJ will send a replacement unit immediately. The defective inverter should be sent back to the closest SAJ Service Center by packing in its original package if possible.
Page 55
(hardware or software) and debugging the faulty product. ■ Logistic fee: Cost of delivery, tariff and other derived expense when defective products are sent from user to SAJ or/and repaired products are sent from SAJ to user. 1.6 Exclusion of Liability Any defect caused by the following circumstances will not be covered by the manufacturer’s warranty (the Dealers or Distributors are responsible and authorized...
Series Warranty Card The installer should fill in the second form while installing the inverter. For warranty claim, please complete the below forms and send this page to SAJ, attached with the Customer’s invoice. For customer to fill in Name:...
Page 57
Series For installer to fill in Modules used: Modules per string: No. of string: Installation company: Contractor license number: Company: City: Country: Zip: Tel: Fax: E-mail: Signature: Date: - 56 -...
Need help?