EMC Immunity Type Tests for IEEE 1613
Note
The RUGGEDCOM RX1501 meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Environmental Type Tests
RUGGEDCOM RX1501
Installation Manual, 10/2021, C79000-G8976-1054-21
Description
HV Impulse
Dielectric Strength
Fast Transient
Oscillatory
Radiated RFI
ESD
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
IEC 61373
IEC 60255-21-3
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Description
Cold Temperature
Test Ad
Dry Heat
Test Bd
Humidity (Damp
Test Db
Heat, Cyclic)
Vibration
Shock
Bump
Long Life (Random Vibration)
Shock
Seismic
6.2 EMC and Environmental Type Tests
Test Levels
5 kV (Failsafe Relay Output)
5 kV
2 kV
1.5 kV
2 kV
± 4 kV @ 2.5 kHz
± 4 kV
2.5 kV common mode @1MHz
2.5 kV common
1 kV differential mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
2 g @ 10-150 Hz
30 g @ 11 ms
10 g @ 16 ms
Category 1 Class B
Method A
Certification
Severity
Levels
 
 
 
Class 2
Class 2
Class 1
 
 
Level 2
47