Piping Limitations - Mitsubishi Electric BDT CITY MULTI Installation And Pre-Commissioning Booklet

Table of Contents

Advertisement

S SERIES PIPING LIMITATIONS
PUMY-P-V(Y)KM-A(-BS)
10
REFRIGERANT PIPING TASKS
10-1. REFRIGERANT PIPING SYSTEM
Line-Branch Method
Connection Examples
(Connecting to 4 Indoor Units)
Total Piping Length
Permissible
Farthest Piping Length
Length
Farthest Piping Length After First Branch
Permissible High/
High/Low Difference in Indoor/Outdoor Section
Low Difference
High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d)
(3) Section From Branch to
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
Refrigerant for the extended piping is not included in the
outdoor unit when the unit is shipped from the factory.
Therefore, charge each refrigerant piping system with
additional refrigerant at the installation site. In addition, in
order to carry out service, enter the size and length of each
liquid pipe and additional refrigerant charge amounts in
the spaces provided on the "Refrigerant amount" plate on
the outdoor unit.
Calculation of additional refrigerant charge
• Calculate the additional charge using the liquid pipe size
and length of the extended piping and total capacity of
connected indoor units.
• Calculate the additional refrigerant charge using the
procedure shown to the right, and charge with the
additional refrigerant.
• For amounts less than 0.1 kg, round up the calculated
additional refrigerant charge.
(For example, if the calculated charge is 6.01 kg, round up
the charge to 6.1 kg.)
A
B
C
A+B+C+a+b+c+d [ 300 m
(L)
A+B+C+d [ 150 m
(R)
B+C+d [ 30 m
(H)
50 meters or less (If the outdoor unit is lower, 40 meters or less)
(h)
15 meters or less
Use an optional branch piping kit (CMY-Y62-G-E).
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch
(Outdoor Unit Piping Diameter)
Model
Each
PUMY-P112
Section of
PUMY-P125
Piping
PUMY-P140
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
Liquid Line (mm)
{9.52
<Additional Charge>
Calculation of refrigerant charge
Pipe size
Liquid pipe
ø6.35
(m) × 19.0 (g/m)
Included refrigerant amount when shipped from the factory
Included refrigerant amount: 4.8 kg
<Example>
Outdoor model : P125
Indoor 1 : P63 (7.1 kW) A : ø9.52 30 m a : ø9.52 15 m
2 : P40 (4.5 kW)
3 : P25 (2.8 kW)
4 : P20 (2.2 kW)
The total length of each liquid line is as follows:
ø9.52 : A + a = 30 + 15 = 45 m
ø6.35 : b + c + d = 10 + 10 + 20 = 40 m
The total capacity of connected indoor unit is as follows:
7.1 + 4.5 + 2.8 + 2.2 = 16.6
<Calculation example>
Additional refrigerant charge
19.0
+ 45 ×
40 ×
A
L
R
B
C
a
b
c
C
C
(2) Refrigerant Piping Diameter In Section
(Indoor Unit Piping Diameter)
Piping Diameter (mm)
Model number
Liquid Line
{9.52
50 or lower
Gas Line
{15.88
Note:
When connecting the CONNECTION KIT
(PAC-LV11M-J) and an M-series indoor
unit, refer to the installation manual for the
Gas Line (mm)
CONNECTION KIT when selecting the
{15.88
pipe size and piping length.
Total capacity of
Pipe size
connected indoor units
Liquid pipe
+
+
~ 8.0 kW
ø9.52
8.1 ~ 16.0 kW
(m) × 50.0 (g/m)
16.1 kW ~
b : ø6.35 10 m
c : ø6.35 10 m
d : ø6.35 20 m
50.0
+ 3.0 = 6.1 kg (rounded up)
d
C
Outdoor unit
A
Outdoor Unit
First branch
B
First Branch
Indoor unit
C
Indoor unit
From Branch to Indoor Unit
Piping Diameter (mm)
Liquid Line
{6.35
Gas Line
{12.7
Liquid Line
{9.52
63 to 140
Gas Line
{15.88
Amount for the
indoor units
1.5 kg
2.5 kg
3.0 kg
At the conditions
below:
21