Local Monitor Mode (Locm); Remote Terminal Mode (Remt) - Ansul AUTOPULSE IQ-301 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Terminal Interface Protocol
170
Table 62 below summarizes the functions available with the Local Terminal mode:
Function
Lets you...
Read Status
• Display the status of an individual point (detector, module, panel circuit, or
zone)
• Display a list of all the points in alarm or trouble
• Display a list of all programmed points in the system
• Step through the history buffer event by event
• Display the entire history buffer
Alter Status
• Disable/Enable an individual point
• Change the sensitivity of a detector
• Clear the verification counter of all detectors
• Clear the entire history buffer
• Set the AWACS™ alert and action levels
Control
• Acknowledge
Functions
• Alarm Silence
• System Reset
• Drill
I.2.2 Local Monitor Mode (LocM)
Functions, passwords, and special requirements of Local Monitor Mode (LocM) are:
Functions:
Read Status, Alter Status, and Control Functions.
Passwords:
User-defined password for Alter Status and Control functions.
Requirements:
Password security feature for Control Functions eliminates the need
for mounting the CRT-2 in an enclosure.
Table 63 summarizes the functions available with the Local Monitor mode:
Function
Lets you...
Read Status
• Display the status of an individual point (detector, module, panel circuit, or
zone)
• Display a list of all the points in alarm or trouble.
• Display a list of all programmed points in the system
• Step through the history buffer event by event
• Display the entire history buffer
Alter Status*
• Disable/Enable an individual point
• Change the sensitivity of a detector
• Clear the verification counter of all detectors
• Clear the entire history buffer
• Set the AWACS™ alert and action levels
Control
• Acknowledge
Functions*
• Alarm Silence
• System Reset
• Drill
*Requires the user defined password for access.
I.2.3 Remote Terminal Mode (RemT)
Functions, passwords, and special requirements of Remote Terminal Mode (RemT) are:
Functions:
Read Status only. See Table 64.
Table 62 LocT Functions
Table 63 LocM Functions
Operating Modes
IQ-301 PN 50036:F 10/29/2001