Panasonic CU-FZ25WKE Series Installation Instruction

Panasonic CU-FZ25WKE Series Installation Instruction

Hide thumbs Also See for CU-FZ25WKE Series:
Table of Contents

Advertisement

Air conditioner
MODEL NO. :-
Installation Instruction
CS/CU-FZ25, FZ35, FZ50, FZ60WKE Series.
CS/CU-UZ25, UZ35, UZ50WKE Series.
CS/CU-PZ25, PZ35, PZ50WKE Series.
CAUTION
Required tools for Installation Works
R32
1 Phillips screw driver
2 Level gauge
REFRIGERANT
3 Electric drill, hole core drill (ø70 mm)
4 Hexagonal wrench (4 mm)
5 Spanner
This Air Conditioner contains and
operates with refrigerant R32.
6 Pipe cutter
7 Reamer
THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED
8 Knife
BY QUALIFIED PERSONNEL.
9 Gas leak detector
Refer to National, State, Territory and local legislation,
10 Measuring tape
regulations, codes, installation & operation manuals, before
the installation, maintenance and/or service of this product.
11 Thermometer
SAFETY PRECAUTIONS
Read the following "SAFETY PRECAUTIONS" carefully before installation.
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classifi ed by the symbols:
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the
customer to keep the operating instructions for future reference.
WARNING
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. Any unfi t method or using incompatible material may cause product damage, burst
and serious injury.
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over the handrail causing an accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current will
cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc mix into refrigeration cycle (piping).
Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, fl ame, sparks, or other sources of ignition.
Else, it may explode and cause injury or death.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
For R32/R410A model, use piping, fl are nut and tools which is specifi ed for R32/R410A refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally high pressure in the refrigerant
cycle (piping), and possibly result in explosion and injury.
For R32 and R410A, the same fl are nut on the outdoor unit side and pipe can be used.
Since the working pressure for R32/R410A is higher than that of refrigerant R22 model, replacing conventional piping and fl are nuts on the outdoor unit side are recommended.
If reuse piping is unavoidable, refer to instruction "IN CASE OF REUSING EXISTING REFRIGERANT PIPING"
Thickness for copper pipes used with R32/R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm.
It is desirable that the amount of residual oil less than 40 mg/10 m.
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
For refrigeration system work, Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For electrical work, follow the national regulation, legistration and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found
in the electrical work, it will cause electrical shock or fi re.
Do not use joint cable for indoor / outdoor connection cable. Use the specifi ed indoor/outdoor connection cable, refer to instruction 5 CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for
indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fi xing is not perfect, it will cause heat up or fi re at the connection.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD), with sensitivity of 30mA at 0.1sec or less. Otherwise, it may cause
electrical shock and fi re in case of equipment breakdown or insulation breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at opened position will cause suck-in of air, abnormal
high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are opened will cause suck-in of air,
abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fi re.
Be aware that refrigerants may not contain an odour.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone.
Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit in a place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Prevent liquid or vapor from entering sumps or sewers since vapor is heavier than air and may form suffocating atmospheres.
Do not release refrigerant during piping work for installation, re-installation and during repairing refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
Power supply connection to the room air conditioner.
Use power supply cord 3 x 1.5 mm² (1.0 ~ 1.5HP), 3 x 2.5 mm² (2.0 ~ 2.25HP) type designation 60245 IEC 57 or heavier cord.
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
1) Power supply connection to the receptacle using power plug.
Use an approved 15/16A (1.0 ~ 1.5HP), 16A (2.0 ~ 2.25HP), power plug with earth pin for the connection to the socket.
2) Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A (1.0 ~ 2.25HP), circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap.
Installation work.
It may need two people to carry out the installation work.
Keep any required ventilation openings clear of obstruction.
PRECAUTION FOR USING R32 REFRIGERANT
Pay careful attention to the following precaution points and the installation work procedures.
WARNING
When connecting fl are at indoor side, make sure that the fl are connection is used only once, if torqued up and released, the fl are must be remade. Once the fl are connection was torqued up correctly and leak test was
made, thoroughly clean and dry the surface to remove oil, dirt and grease by following instructions of silicone sealant. Apply neutral cure (Alkoxy type) & ammonia-free silicone sealant that is non-corrosive to copper &
brass to the external of the fl ared connection to prevent the ingress of moisture on both the gas & liquid sides. (Moisture may cause freezing and premature failure of the connection)
The appliance shall be stored, installed and operated in a well ventilated room with indoor fl oor area larger than A
(m²) [refer Table A] and without any continuously operating ignition source. Keep away from open
min
fl ames, any operating gas appliances or any operating electric heater. Else, it may explode and cause injury or death.
The mixing of different refrigerants within a system is prohibited. Models that use refrigerant R32 and R410A have a different charging port thread diameter to prevent erroneous charging with refrigerant R22 and for safety.
Therefore, check beforehand. [The charging port thread diameter for R32 and R410A is 12.7 mm (1/2 inch).]
Ensure that foreign matter (oil, water, etc.) does not enter the piping.
Also, when storing the piping, securely seal the opening by pinching, taping, etc. (Handling of R32 is similar to R410A.)
Operation, maintenance, repairing and refrigerant recovery should be carried out by trained and certifi ed personnel in the use of fl ammable refrigerants and as recommended by the manufacturer. Any personnel
conducting an operation, servicing or maintenance on a system or associated parts of the equipment should be trained and certifi ed.
Any part of refrigerating circuit (evaporators, air coolers, AHU, condensers or liquid receivers) or piping should not be located in the proximity of heat sources, open fl ames, operating gas appliance or an operating
electric heater.
The user/owner or their authorized representative shall regularly check the alarms, mechanical ventilation and detectors, at least once a year, where as required by national regulations, to ensure their correct
functioning.
A logbook shall be maintained. The results of these checks shall be recorded in the logbook.
In case of ventilations in occupied spaces shall be checked to confi rm no obstruction.
Before a new refrigerating system is put into service, the person responsible for placing the system in operation should ensure that trained and certifi ed operating personnel are instructed on the basis of the instruction
manual about the construction, supervision, operation and maintenance of the refrigerating system, as well as the safety measures to be observed, and the properties and handling of the refrigerant used.
The general requirement of trained and certifi ed personnel are indicated as below:
a) Knowledge of legislation, regulations and standards relating to fl ammable refrigerants; and,
b)  D etailed knowledge of and skills in handling fl ammable refrigerants, personal protective equipment, refrigerant leakage prevention, handling of cylinders, charging, leak detection, recovery and disposal; and,
c) Able to understand and to apply in practice the requirements in the national legislation, regulations and Standards; and,
d) Continuously undergo regular and further training to maintain this expertise.
Air-conditioner piping in the occupied space shall be installed in such a way to protect against accidental damage in operation and service.
Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping.
Ensure protection devices, refrigerating piping and fi ttings are well protected against adverse environmental effects (such as the danger of water collecting and freezing in relief pipes or the
accumulation of dirt and debris).
Expansion and contraction of long runs piping in refrigerating systems shall be designed and installed securely (mounted and guarded) to minimize the likelihood hydraulic shock damaging the system.
Protect the refrigerating system from accidental rupture due to moving furniture or reconstruction activities.
To ensure no leaking, fi eld-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least
0,25 times the maximum allowable pressure (>1.04MPa, max 4.15MPa). No leak shall be detected.
1. General
Must ensure the installation of pipe-work shall be kept to a minimum. Avoid use dented pipe and do not allow acute bending.
Must ensure that pipe-work shall be protected from physical damage.
12 Megameter
Must comply with national gas regulations, state municipal rules and legislation. Notify relevant authorities in accordance with all applicable regulations.
13 Multimeter
Must ensure mechanical connections be accessible for maintenance purposes.
In cases that require mechanical ventilation, ventilation openings shall be kept clear of obstruction.
14 Torque wrench
When disposal of the product, do follow to the precautions in #12 and comply with national regulations.
18 N•m (1.8 kgf•m)
In case of fi eld charge, the effect on refrigerant charge caused by the different pipe length has to be quantifi ed, measured and labelled.
42 N•m (4.3 kgf•m)
Always contact to local municipal offi ces for proper handling.
55 N•m (5.6 kgf•m)
Ensure the actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed.
65 N•m (6.6 kgf•m)
Ensure refrigerant charge not to leak.
Wear appropriate protective equipment, including respiratory protection, as conditions warrant.
100 N•m (10.2 kgf•m)
Keep all sources of ignition and hot metal surfaces away.
15 Vacuum pump
2. Servicing
16 Gauge manifold
2-1. Qualifi cation of workers
Any qualifi ed person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certifi cate from an industry-accredited assessment authority, which authorizes
their competence to handle refrigerants safely in accordance with an industry recognized assessment specifi cation.
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the
supervision of the person competent in the use of fl ammable refrigerants.
Servicing shall be performed only as recommended by the manufacturer.
The system is inspected, regularly supervised and maintained by a trained and certifi ed service personnel who is employed by the person user or party responsible.
2-2. Checks to the area
Prior to beginning work on systems containing fl ammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised.
For repair to the refrigerating system, the precautions in #2-3 to #2-7 must be followed before conducting work on the system.
2-3. Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a fl ammable gas or vapour being present while the work is being performed.
2-4. General work area
All maintenance staff and others working in the local area shall be instructed and supervised on the nature of work being carried out.
Avoid working in confi ned spaces. Always ensure away from source, at least 2 meter of safety distance, or zoning of free space area of at least 2 meter in radius.
2-5. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially fl ammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with fl ammable refrigerants, i.e. non sparking, adequately sealed or intrinsically safe.
In case of leakage/spillage happened, immediately ventilate area and stay upwind and away from spill/release.
In case of leakage/spillage happened, do notify persons down wind of the leaking/spill, isolate immediate hazard area and keep unauthorized personnel out.
2-6. Presence of fi re extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fi re extinguishing equipment shall be available at hand.
Have a dry powder or CO
fi re extinguisher adjacent to the charging area.
2
2-7. No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing any pipe work that contains or has contained fl ammable refrigerant shall use any sources of ignition in
such a manner that it may lead to the risk of fi re or explosion. He/She must not be smoking when carrying out such work.
All possible ignition sources, including cigarette smoking, should be kept suffi ciently far away from the site of installation, repairing, removing and disposal, during which fl ammable refrigerant can
possibly be released to the surrounding space.
Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no fl ammable hazards or ignition risks.
"No Smoking" signs shall be displayed.
2-8. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work.
A degree of ventilation shall continue during the period that the work is carried out.
The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
2-9. Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fi t for the purpose and to the correct specifi cation.
At all times the manufacturer's maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer's technical department for assistance.
The following checks shall be applied to installations using fl ammable refrigerants.
- The actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed.
- The ventilation machinery and outlets are operating adequately and are not obstructed.
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
- Refrigerating pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components
are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded.
2-10. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures.
Initial safety checks shall include but not limit to:-
- That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking.
- That there is no live electrical components and wiring are exposed while charging, recovering or purging the system.
- That there is continuity of earth bonding.
At all times the manufacturer's maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer's technical department for assistance.
If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used.
The owner of the equipment must be informed or reported so all parties are advised thereinafter.
3. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc.
If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a
potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include
damage to cables, excessive number of connections, terminals not made to original specifi cation, damage to seals, incorrect fi tting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the
purpose of preventing the ingress of fl ammable atmospheres.
Replacement parts shall be in accordance with the manufacturer's specifi cations.
4. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a fl ammable atmosphere.
The test apparatus shall be at the correct rating.
Replace components only with parts specifi ed by the manufacturer. Unspecifi ed parts by manufacturer may result ignition of refrigerant in the atmosphere from a leak.
5. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
6. Detection of fl ammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching or detection of refrigerant leaks.
A halide torch (or any other detector using a naked fl ame) shall not be used.
The following leak detection methods are deemed acceptable for all refrigerant systems.
- No leaks shall be detected when using detection equipment with a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0,25 times the maximum allowable
pressure (>1.04MPa, max 4.15MPa) for example, a universal sniffer.
- Electronic leak detectors may be used to detect fl ammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free area.)
- Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
- Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum)
is confi rmed.
- Leak detection fl uids are also suitable for use with most refrigerants, for example, bubble method and fl uorescent method agents. The use of detergents containing chlorine shall be avoided as
the chlorine may react with the refrigerant and corrode the copper pipe-work.
- If a leak is suspected, all naked fl ames shall be removed/extinguished.
- If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from
the leak. The precautions in #7 must be followed to remove the refrigerant.
7. Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used.
However, it is important that best practice is followed since fl ammability is a consideration.
The following procedure shall be adhered to:
• remove refrigerant -> • purge the circuit with inert gas -> • evacuate -> • purge with inert gas -> • open the circuit by cutting or brazing
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be purged with OFN to render the appliance safe. (remark: OFN = oxygen free nitrogen, type of inert gas)
This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Purging shall be achieved by breaking the vacuum in the system with OFN and continuing to fi ll until the working pressure is achieved, then venting to atmosphere, and fi nally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system.
When the fi nal OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe work are to take place.
Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available.
8. Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
- Ensure that contamination of different refrigerants does not occur when using charging equipment.
- Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
- Cylinders shall be kept in an appropriate position according to the instructions.
- Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to over fi ll the refrigerating system.
Prior to recharging the system it shall be pressure tested with OFN (refer to #7).
The system shall be leak tested on completion of charging but prior to commissioning.
A follow up leak test shall be carried out prior to leaving the site.
Electrostatic charge may accumulate and create a hazardous condition when charging and discharging the refrigerant.
To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.
9. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.
It is recommended good practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant.
It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
mechanical handling equipment is available, if required, for handling refrigerant cylinders;
all personal protective equipment is available and being used correctly;
the recovery process is supervised at all times by a competent person;
recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of
the system.
Electrostatic charge may accumulate and create a hazardous condition when charging or discharging the refrigerant.
To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.
10. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
The label shall be dated and signed.
Ensure that there are labels on the equipment stating the equipment contains fl ammable refrigerant.
11. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the total system charge are available.
All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.
Recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
CAUTION
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of concerning the equipment that is at hand and shall be suitable for the recovery of
fl ammable refrigerants.
In addition, a set of calibrated weighing scales shall be available and in good working order.
Hoses shall be complete with leak-free disconnect couplings and in good condition.
Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that fl ammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor to the suppliers.
Only electric heating to the compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.
Explanation of symbols displayed on the indoor unit or outdoor unit.
WARNING
CAUTION
CAUTION
CAUTION
Attached accessories
No.
Accessories part
Installation plate
1
CENTER
HOLE
PIPE
HOLE CENTER
115mm TO
Installation plate fi xing
screw
2
Remote Control
3
Applicable piping kit
CZ-3F5, 7BP
CZ-4F5, 7, 10BP
CZ-52F5, 7, 10BP
  Do not install the unit in excessive oil fume area such as kitchen, workshop and etc.
  There should not be any heat source or steam near the unit.
  There should not be any obstacles blocking the air circulation.
  A place where air circulation in the room is good.
  A place where drainage can be easily done.
  A place where noise prevention is taken into consideration.
  Do not install the unit near the door way.
  Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
  Indoor unit of this air conditioner shall be installed in a height of at least 1.8 m.
  If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation
from the condenser is not obstructed.
  There should not be any animal or plant which could be affected by hot air discharged.
  Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
  Do not place any obstacles which may cause a short circuit of the discharged air.
  If piping length is over the [piping length for additional gas], additional refrigerant should be
added as shown in the table.
Table A
NOTE:
- The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment.
- Intrinsically safe components do not have to be isolated prior to working on them.
Capacity
Model
W
(HP)
FZ25***,
UZ25***,
1.0HP
PZ25***
FZ35***,
UZ35***,
1.5HP
PZ35***
FZ50***,
UZ50***,
2.0HP
PZ50***
FZ60***
2.25HP
(*) Systems with total refrigerant charge,
Example: For FZ25***
If the unit is installed at 10 m distance, the quantity of additional refrigerant should be
25 g .... (10-7.5) m x 10 g/m = 25 g.
A
= (
/ (2.5 x (LFL)
m
min
c
A
= Required minimum room area, in m²
min
m
= Refrigerant charge in appliance, in kg
c
LFL = Lower fl ammability limit (0.307 kg/m³)
h
= Installation height of the appliance (1.8 m for wall mounted)
0
SF
= Safety factor with a value of 0.75
** The required minimum room area, A min , shall also be governed by the safety factor margin formula below :
A
=
m
/ (SF x LFL x h
min
c
The higher value shall be taken when determining the room area.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not over fi ll cylinders. (No more than 80 % volume liquid charge).
i)
Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j)
When the cylinders have been fi lled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and
all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigerating system
unless it has been cleaned and checked.
Indoor/Outdoor Unit Installation Diagram
This symbol shows that this equipment uses a fl ammable refrigerant. If the
Piping direction
refrigerant is leaked, together with an external ignition source, there is a
possibility of ignition.
Right
This symbol shows that the Installation Manual should be read carefully.
This symbol shows that a service personnel should be handling this
Right
Rear
equipment with reference to the Installation Manual.
Right
This symbol shows that there is information included in the Operation
bottom
Manual and/or Installation Manual.
Qty. No.
Accessories part
Qty. No.
Accessories part
Qty.
Battery
Drain elbow
1
4
2
7
1
PIPE
HOLE
CENTER
115mm TO
HOLE CENTER
Remote control holder
Air Purifying Filter/
5
1
Dust Collector Filter
5
8
1
Remote control holder
fi xing screw
1
6
2
(only applicable for
"FZ" & "UZ" model)
50 mm
or more
Piping size
Gas
Liquid
9.52 mm (3/8")
6.35 mm (1/4")
12.7 mm (1/2")
6.35 mm (1/4")
15.88 mm (5/8")
6.35 mm (1/4")
SELECT THE BEST LOCATION
Insulation of piping connections
INDOOR UNIT
Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Attaching the remote control holder to the wall
Remote control holder fi xing screws 6
Remote
OUTDOOR UNIT
control 3
Remote control holder 5
Piping
Piping size
Min.
Max.
Max.
Std.
Max.
Additional
Length
Piping
Piping
Refrigerant
Length
Elevation
Refrigerant
for add.
Indoor A min (m²)
It is advisable to
Length
Length
Charge
Gas
Liquid
(m)
(m)
(g/m)
gas
avoid more than 2
(m)
(m)
(kg)
(m)
blockage directions.
For better ventilation
& multiple-outdoor
15
3
15
10
7.5
0.62
Not applicable (*)
installation, please
9.52mm
consult authorized
(3/8")
dealer/specialist.
15
3
15
10
7.5
0.75
Not applicable (*)
6.35mm
5
(1/4")
This illustration is for
explanation purposes only.
15
3
15
15
7.5
1.25
Not applicable (*)
12.7mm
The indoor unit will actually
(1/2")
face a different way.
15
3
30
15
7.5
1.45
Not applicable (*)
( * ) If holder at the rear of chassis
m
, lower than 1.84kg are not subjected to any room area requirements.
c
(Refer column " 4 Indoor Unit
Installation" ) need to be used
to prop up the unit, this distance
shall be 65 mm or more.
(5/4)
x h
)) ²
** not less than safety factor margin
0
)
0
Attention not to bend
up drain hose
(Front side)
Left
Left
Rear
Left bottom
Installation parts you
should purchase ( )
( * )
Installation plate 1
Bushing-Sleeve ( )
Sleeve ( )
Putty ( )
(Gum Type Sealer)
Bend the pipe as closely
(Left and right are identical)
on the wall as possible,
but be careful that it
doesn't break.
Power supply cord ( )
Flare connection
Vinyl tape (wide) ( )
Vinyl tape
• Apply after carrying out
a drainage test.
• To carry out the
drainage test, remove
the air fi lters and pour
water into the heat
exchanger.
Saddle ( )
Connection cable
Liquid side piping ( )
Gas side piping ( )
Additional drain hose ( )
ENGLISH
ACXF60-38660-AA
1/2
PRINTED IN MALAYSIA

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CU-FZ25WKE Series

  • Page 1 10. Labelling Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping. • Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. • The label shall be dated and signed. Ensure protection devices, refrigerating piping and fi ttings are well protected against adverse environmental effects (such as the danger of water collecting and freezing in relief pipes or the •...
  • Page 2 INDOOR UNIT OUTDOOR UNIT SELECT THE BEST LOCATION SELECT THE BEST LOCATION AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM INDOOR UNIT INSTALLATION (Refer to “Select the best location” section) (Refer to “Select the best location” section) AIR TIGHTNESS TEST ON THE REFRIGERATING SYSTEM Pull out the Indoor piping INSTALL THE OUTDOOR UNIT •...
  • Page 3 – This Air Conditioner contains and operates with refrigerant R32. THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL. Refer to National, State, Territory and local legislation, regulations, codes, installation & operation manuals, before the installation, maintenance and/or service of this product. © Panasonic Corporation 2020...
  • Page 4: Table Of Contents

    TABLE OF CONTENTS PAGE PAGE 1. Safety Precautions ..........3 14. Operation Control ..........68 2. Precaution for Using R32 Refrigerant ....6 14.1 Basic Function ..........68 14.2 Indoor Fan Motor Operation .......69 3. Specifications ........... 11 14.3 Outdoor Fan Motor Operation ....70 4.
  • Page 5: Safety Precautions

    1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.  Confirm the type of gas used before installation.  Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
  • Page 6 WARNING  For R32/R410A model, use piping, flare nut and tools which is specified for R32/R410A refrigerant. Using of existing (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury. For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be used.
  • Page 7 CAUTION Select an installation location which is easy for maintenance. Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property. Power supply connection to the room air conditioner. Use power supply cord 3 x 1.5 mm (1.0 ~ 1.5HP), 3 x 2.5 mm (2.0 ~ 2.25HP) type designation 60245 IEC 57 or heavier cord.
  • Page 8: Precaution For Using R32 Refrigerant

    2. Precaution for Using R32 Refrigerant  Pay careful attention to the following precaution points and the installation work procedures: WARNING When connecting flare at indoor side, make sure that the flare connection is used only once, if torqued up and released, the flare must be remade.
  • Page 9 CAUTION General  Must ensure the installation of pipe-work shall be kept to a minimum. Avoid use dented pipe and do not allow acute bending.  Must ensure that pipe-work shall be protected from physical damage.  Must comply with national gas regulations, state municipal rules and legislation. Notify relevant authorities in accordance with all applicable regulations.
  • Page 10 CAUTION 2-9. Checks to the refrigeration equipment  Where electrical components are being changed, they shall be fit for the purpose and to the correct specification.  At all times the manufacturer’s maintenance and service guidelines shall be followed.  If in doubt consult the manufacturer’s technical department for assistance.
  • Page 11 CAUTION Removal and evacuation  When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: •...
  • Page 12 CAUTION Recovery  When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.  When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. ...
  • Page 13: Specifications

    3. Specifications Indoor Model CS-FZ25WKE CS-FZ35WKE Outdoor Model CU-FZ25WKE CU-FZ35WKE Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.85 2.50 3.00 0.85 3.40 3.90 Capacity BTU/h 2900 8530 10200 2900 11600 13300...
  • Page 14 Indoor Model CS-FZ25WKE CS-FZ35WKE Outdoor Model CU-FZ25WKE CU-FZ35WKE Type Hermetic Motor / Rotary Hermetic Motor / Rotary Compressor Motor Type Brushless (6-poles) Brushless (6-poles) Output Power Type Cross-flow Fan Cross-flow Fan Material ASG30 ASG30 Motor Type DC (8-poles) DC (8-poles) Input Power 43.8 43.8...
  • Page 15 Indoor Model CS-FZ25WKE CS-FZ35WKE Outdoor Model CU-FZ25WKE CU-FZ35WKE Height mm (inch) 290 (11-7/16) / 542 (21-11/32) 290 (11-7/16) / 542 (21-11/32) (I/D / O/D) Width Dimension Unit mm (inch) 779 (30-11/16) / 780 (30-23/32) 779 (30-11/16) / 780 (30-23/32) (I/D / O/D) Depth mm (inch) 209 (8-1/4) / 289 (11-13/32)
  • Page 16 Indoor Model CS-FZ50WKE CS-FZ60WKE Outdoor Model CU-FZ50WKE CU-FZ60WKE Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.98 5.00 5.40 0.98 6.00 6.50 Capacity BTU/h 3340 17100 18400 3340 20500 22200 kcal/h 4300...
  • Page 17 Indoor Model CS-FZ50WKE CS-FZ60WKE Outdoor Model CU-FZ50WKE CU-FZ60WKE Type Hermetic Motor / Rotary Hermetic Motor / Rotary Compressor Motor Type Brushless (4-poles) Brushless (4-poles) Output Power Type Cross-flow Fan Cross-flow Fan Material ASG30 ASG30 Motor Type DC (8-poles) DC (8-poles) Input Power 43.8 43.8...
  • Page 18 Indoor Model CS-FZ50WKE CS-FZ60WKE Outdoor Model CU-FZ50WKE CU-FZ60WKE Height mm (inch) 290 (11-7/16) / 619 (24-3/8) 290 (11-7/16) / 695 (27-3/8) (I/D / O/D) Width Dimension Unit mm (inch) 779 (30-11/16) / 824 (32-15/32) 779 (30-11/16) / 875 (34-15/32) (I/D / O/D) Depth mm (inch) 209 (8-1/4) / 299 (11-25/32)
  • Page 19: Features

    4. Features  Inverter Technology Wider output power range Energy saving Quick Cooling Quick Heating More precise temperature control  Environment Protection Non-ozone depletion substances refrigerant (R32)  Long Installation Piping Long piping up to 15 meters (1.0 ~ 2.0HP) and 30 meters (2.25HP) ...
  • Page 20: Location Of Controls And Components

    5. Location of Controls and Components Indoor Unit Air purifying Filter Front panel Auto OFF/ON button • Use when remote control is misplaced or a malfunction occurs. Aluminium fin Air filters INDICATOR POWER (White) Horizontal airflow TIMER (White) direction louver Remote Control •...
  • Page 21: Dimensions

    6. Dimensions Indoor Unit & Remote Control <Top View> <Side View> <Side View> <Front View> Air intake direction Left piping Air outlet Right piping <Bottom View> hole direction hole <Remote Control> 99.5 <Rear View> 41-61 <Remote Control Holder> Liquid side Gas side Relative position between the indoor unit and the installation plate <Front View>...
  • Page 22: Outdoor Unit

    Outdoor Unit 6.2.1 CU-FZ25WKE CU-FZ35WKE <Top View> 67.6 (104.7) 104.9 60.5 Space necessary for installation 100 mm 100 mm 1000 mm Anchor Bolt Pitch 320 × 570 <Side View> <Side View> <Front View> 3-way valve at Gas side Unit : mm (Low Pressure) 2-way valve at Liquid side (High Pressure)
  • Page 23 6.2.3 CU-FZ60WKE <Top View> Space necessary for (131) 34.7 installation 100mm 100mm 1000mm Anchor Bolt Pitch 360.5 × 613 2-way valve at Liquid side (High Pressure) <Side View> 3-way valve at Gas side <Side View> <Front View> (Low Pressure) Unit : mm...
  • Page 24: Refrigeration Cycle Diagram

    7. Refrigeration Cycle Diagram CS-FZ25WKE CU-FZ25WKE CS-FZ35WKE CU-FZ35WKE CS-FZ50WKE CU-FZ50WKE INDOOR OUTDOOR PIPE LIQUID TEMP. EXPANSION SIDE SENSOR VALVE MUFFLER STRAINER 2-WAY VALVE PIPE INTAKE TEMP. SENSOR 1 TEMP. SENSOR HEAT EXCHANGER TEMP. (CONDENSER) SENSOR PIPE TEMP. SENSOR 2 HEAT EXCHANGER (EVAPORATOR) SIDE MUFFLER...
  • Page 25: Cs-Fz60Wke Cu-Fz60Wke

    CS-FZ60WKE CU-FZ60WKE INDOOR OUTDOOR LIQUID EXPANSION SIDE VALVE STRAINER 2-WAY PROCESS VALVE TUBE TEMP. PIPE SENSOR TEMP. CONDENSER INTAKE SENSOR 2 TEMP. SENSOR PIPE TEMP. PIPE SENSOR 1 TEMP. SENSOR HEAT EXCHANGER (EVAPORATOR) SIDE 4-WAYS VALVE 3-WAY RECEIVER VALVE TANK SENSOR COMPRESSOR COOLING...
  • Page 26: Block Diagram

    8. Block Diagram CS-FZ25WKE CU-FZ25WKE CS-FZ35WKE CU-FZ35WKE...
  • Page 27: Cs-Fz50Wke Cu-Fz50Wke Cs-Fz60Wke Cu-Fz60Wke

    CS-FZ50WKE CU-FZ50WKE CS-FZ60WKE CU-FZ60WKE...
  • Page 28: Wiring Connection Diagram

    9. Wiring Connection Diagram Indoor Unit TERMINAL BOARD TEMP. FUSE 102°C REMARKS : RY-PWR AC308 (BLK) RY-PWR2 : BLUE P : PINK BR : BROWN O : ORANGE BL : BLACK Y : YELLOW AC307 (BRW) W : WHITE G : GREEN : RED GR : GRAY FUSE301...
  • Page 29: Outdoor Unit

    Outdoor Unit 9.2.1 CU-FZ25WKE CU-FZ35WKE TO INDOOR UNIT REACTOR TERMINAL BOARD RAT2 RAT1 OUTDOOR AIR TEMP. (GRY) (GRY) SENSOR FUSE105 (THERMISTOR) (15A 250V) DATA t° (RED) CN-TH (WHT) t° NOISE PIPING TEMP. SENSOR FILTER (THERMISTOR) COMMUNICATION AC-BLK CIRCUIT CIRCUIT (BLK) CN-TANK t°...
  • Page 30 9.2.2 CU-FZ50WKE CU-FZ60WKE TO INDOOR UNIT REACTOR TERMINAL BOARD RAT2 RAT1 (GRY) (GRY) FUSE6 (20A 250V) OUTDOOR AIR TEMP. DATA SENSOR (RED) (THERMISTOR) COMMUNICATION CIRCUIT CN-TH1 NOISE (WHT) FILTER AC-BLK CIRCUIT FUSE8 PIPING TEMP. SENSOR (BLK) T3.15A (THERMISTOR) L250V FUSE1 RECTIFICATION CN-TANK (25A 250V)
  • Page 31: Electronic Circuit Diagram

    10. Electronic Circuit Diagram 10.1 Indoor Unit TERMINAL BOARD TEMP. FUSE 102°C RY-PWR AC308 (BLK) RY-PWR2 AC307 (BRW) FUSE301 AC303 (WHT) T3.15A L250V AC304 (RED) G301 (GRN) NOISE FILTER F301 CIRCUIT COMMUNICATION CIRCUIT EVAPORATOR 0.1µ 0.1µ RECTIFICATION CIRCUIT SW01 CN – FM FAN MOTOR (WHT) ELECTRONIC CONTROLLER...
  • Page 32: Outdoor Unit

    10.2 Outdoor Unit 10.2.1 CU-FZ25WKE CU-FZ35WKE TO INDOOR UNIT REACTOR TERMINAL BOARD RAT2 RAT1 (GRY) (GRY) R205 R206 OUTDOOR AIR TEMP. R207 R208 ELECTRONIC SENSOR C204 C205 CONTROLLER (THERMISTOR) t° t° PIPING TEMP. SENSOR (THERMISTOR) FUSE105 (15A 250V) DATA (RED) t°...
  • Page 33 10.2.2 CU-FZ50WKE CU-FZ60WKE TO INDOOR UNIT REACTOR TERMINAL BOARD RAT2 RAT1 (GRY) (GRY) FUSE6 (20A 250V) 15.8k DATA (RED) 470µ COMMUNICATION 1µ OUTDOOR AIR TEMP. 1µ CIRCUIT NOISE SENSOR (15kΩ 3950) FILTER AC-BLK CIRCUIT t° FUSE8 (BLK) T3.15A t° L250V FUSE1 RECTIFICATION CN-TH1...
  • Page 34: Printed Circuit Board

    11. Printed Circuit Board 11.1 Indoor Unit 11.1.1 Main Printed Circuit Board AC303 G301 AC304 RY-PWR CN-FM CN-CNT CN-RMT CN-STM1 CN-TH JP1 (Random Auto Restart enable/disable) CN-DISP...
  • Page 35 11.1.2 Indicator & Receiver Printed Circuit Board LED201 LED202 CN-DISP...
  • Page 36: Outdoor Unit

    11.2 Outdoor Unit 11.2.1 Main Printed Circuit Board 11.2.1.1 CU-FZ25WKE CU-FZ35WKE POWER TRANSISTOR (IPM) CN-MTR2 CN-MTR1 CN-HOT CN-TH CN-TANK CN-STM AC-WHT DATA AC-BLK...
  • Page 37 11.2.1.2 CU-FZ50WKE CU-FZ60WKE POWER TRANSISTOR (IPM) CN-MTR2 CURRENT TRANSFORMER (CT) CN-MTR1 CN-STM1 CN-TH1 CN-HOT DATA CN-TANK AC-WHT AC-BLK...
  • Page 38: Installation Instruction

    12. Installation Instruction 12.1 Select the Best Location ** The required minimum room area, A , shall also 12.1.1 Indoor Unit be governed by the safety factor margin formula below :  Do not install the unit in excessive oil fume area such as kitchen, workshop and etc.
  • Page 39: Indoor Unit

    12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from vibration. Ceiling Wall More than More than Wall More 2 screw Indoor unit than 216 mm 168 mm Measuring Tape Installation PIPE...
  • Page 40 12.2.2 To Drill a Hole in the Wall and Install a Sleeve of Piping Insert the piping sleeve to the hole. Fix the bushing to the sleeve. Wall Cut the sleeve until it extrudes about 15 mm Indoor Outdoor from the wall. 15 mm Approx.
  • Page 41 12.2.3 Indoor Unit Installation Pull out the Indoor piping ● Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage. ● Use shock absorber during pull out the piping to protect the intake grille from damage. Piping Piping Shock absorber...
  • Page 42 Change the drain hose position Rear view for left piping installation PIPE HOLE CENTER 115mm TO HOLE CENTER Connection cable Drain hose Connection cable Piping More than 950 mm Drain hose Drain cap Adjust the piping slightly Sleeve for piping hole downwards.
  • Page 43 Tape Colour of wires (connection cable) Power supply Terminals on the indoor unit cord (Power supply cord) Tape Terminals on the isolating (L) (N) devices (Disconnecting means) Connection cable Recommended WARNING length (mm) This equipment must be refer table below properly earthed.
  • Page 44: Outdoor Unit

    12.3 Outdoor Unit 12.3.1 Install the Outdoor Unit  After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt, screws or nails.
  • Page 45 AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM 12.3.1 Air Tightness Test on the Refrigerating System Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. There is no extra refrigerant in the outdoor unit for air purging. •...
  • Page 46 12.3.2 Connect the Cable to the Outdoor Unit Remove the control board cover from the unit by loosening the screw. Terminal Board Connection cable between indoor unit and Earth wire outdoor unit shall be approved longer than polychloroprene sheathed 4 × 1.5 mm others (1.0 ~ 1.5HP) or 4 ×...
  • Page 47 12.3.5 How to Take Out Front Grille Please follow the steps below to take out front grille if necessary such as when installing or servicing. Front panel Open front panel. Remove the 3 mounting screws on the front grille as shown in the illustration at right. Slide the 3 lock knobs on the upside of front grille to unlock position.
  • Page 48 12.3.8 Disposal of Outdoor Unit Drain Water  If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm.  If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate.
  • Page 49 12.3.12 In case of Reusing Existing Refrigerant Piping  Observe the followings to decide reusing the existing refrigerant piping. Poor refrigerant piping could result in product failure.  In the circumstances listed below, do not reuse any refrigerant piping. Instead, make sure to install a new piping. Heat insulation is not provided for either liquid-side or gas-side piping or both.
  • Page 50: Installation And Servicing Air Conditioner Using R32

    13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
  • Page 51 2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
  • Page 52: Refrigerant Piping Installation • Tools Used In Services

    13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
  • Page 53 3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
  • Page 54 7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
  • Page 55 11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
  • Page 56: New Installation, Relocation, Repairing Of Refrigerant Cycle System The Procedures

    13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
  • Page 57: Piping Installation Of R32

    13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
  • Page 58: Installation, Relocation, And Service

    13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
  • Page 59 13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
  • Page 60 13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
  • Page 61 13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
  • Page 62: Repairing Of Refrigerant Cycle / Brazing Point

    13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
  • Page 63 2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
  • Page 64 13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
  • Page 65 13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
  • Page 66 13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
  • Page 67 (Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
  • Page 68: Reference> Analysis Method For No Error Code, No Cooling / No Warming

    13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
  • Page 69 1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
  • Page 70: Operation Control

    14. Operation Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
  • Page 71: Indoor Fan Motor Operation

    14.1.5 Automatic Operation  This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode and indoor intake air temperature.  During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the indoor intake air temperature.
  • Page 72: Outdoor Fan Motor Operation

    [Heating]  According to indoor pipe temperature, automatic heating fan speed is determined as follows. B. Feedback control  Immediately after the fan motor started, feedback control is performed once every second.  During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error counter increase, fan motor is then stop and restart.
  • Page 73 Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner is stopped using remote control, the vane will shift to close position.
  • Page 74: Timer Control

    Side View (Outer Vane) Closed Position Stopper 115º Reference point Step 1 Step 2 Step 3 Step 4 Step 5 Figure 2 * The horizontal vane angle tolerance is within +/- 5 degree. 14.4.2 Horizontal Airflow  The horizontal airflow direction louver can be adjusted manually by hand. 14.5 Timer Control ...
  • Page 75: Sleep Mode Operation

    14.6 Sleep Mode Operation This operation provide comfortable environment while sleeping. It will automatically adjust the sleep pattern temperature during the activation period. SLEEP (Cancel) This operation is incorporated with the activation timer (0.5, 1, 2, 3, 4, 5, 6, 7, 8 or 9 hours). Start Condition: ...
  • Page 76: Random Auto Restart Control

     Heating mode i t c Set Temp -1°C 1 Hr Max 9 Hrs  Sleep operation will not undergo temperature shift when it collaborate with below operation. However, it will execute the delay timer. Powerful mode operation Auto mode operation Stop Condition: ...
  • Page 77: Quiet Operation (Heating)

    14.10 Quiet Operation (Heating) A. Purpose To provide quiet heating operation compare to normal operation. B. Control condition a. Quiet operation start condition When "FAN SPEED/QUIET" button at remote control is pressed continuously until QUIET will be shown on remote control display. b.
  • Page 78: Protection Control

    15. Protection Control 15.1 Protection Control for All Operations 15.1.1 Restart Control (Time Delay Safety Control)  The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
  • Page 79 15.1.4 Compressor Overheating Prevention Control  Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below.  If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will be blinking.
  • Page 80: Protection Control For Cooling & Soft Dry Operation

    15.2 Protection Control for Cooling & Soft Dry Operation 15.2.1 Outdoor Air Temperature Control  The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.  This control will begin 1 minute after the compressor starts. ...
  • Page 81: Protection Control For Heating Operation

    15.2.5 Dew Prevention Control 1  To prevent dew formation at indoor unit discharge area.  This control will be activated if: Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled. When Cooling or Dry mode is operated more than 20 minutes or more. ...
  • Page 82 15.3.5 Cold Draught Prevention Control  When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced. 15.3.6 Deice Operation  When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor and outdoor fan motor stop and operation LED blinks.
  • Page 83: Servicing Mode

    16. Servicing Mode 16.1 Auto OFF/ON Button AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunction. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds.
  • Page 84: Heat Only Operation

    REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset”...
  • Page 85: Remote Control Button

    16.3 Remote Control Button 16.3.1 SET Button  To check remote control transmission code and store the transmission code to EEPROM. Press “Set” button by using pointer. Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code change. LCD returns to original display if remote control does not operate for 30 seconds.
  • Page 86  To limit set temperature range for COOL & DRY, HEAT, AUTO mode. Press “Set” button by using pointer. Press TEMP increment or decrement button to choose No. 3. Press Timer increment or decrement button to select desired temperature low limit of set temperature for COOL &...
  • Page 87 Press Timer Set button to confirm high limit selection. Press TEMP increment or decrement button to choose No. 5. Press Timer increment or decrement button to select desired temperature low limit of set temperature for HEAT mode. Normal display mode Press SW to enter customer zone &...
  • Page 88 Press TEMP increment or decrement button to choose No. 12. Press Timer increment or decrement button to select desired temperature low limit of set temperature for AUTO mode. Normal display mode Press SW to enter customer zone & Press SW’s to choose function 12 i) Display latest set temp (Low3).
  • Page 89 16.3.2 RESET (RC)  To clear and restore the remote control setting to factory default. Press once to clear the memory. 16.3.3 RESET (AC)  To restore the unit’s setting to factory default. Press once to restore the unit’s setting. 16.3.4 TIMER ▲...
  • Page 90 16.3.6 Customization mode LCD display area: Customization display area (highlighted in color) POWERFUL FAN SPEED/ QUIET TIMER Function Options (If any) Cannot enter this customization mode under the following conditions: 1 Operation ON. 2 Under [Real/ON/OFF] time setting mode. To enter Customer zone: Normal display Customer Zone mode...
  • Page 91 Customization list table: Note: The functions described in the table may not be applicable to the model and may subject to change without further notice. Customization Options Remark Name Remote control number selection A, B, C, D Solar radiation sensitivity level adjustment 1, 2, 3, 4, 5 [iAUTO-X/iAUTO/iCOMF, Cool &...
  • Page 92: Troubleshooting Guide

    17. Troubleshooting Guide 17.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas pressure Outlet air temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
  • Page 93: Relationship Between The Condition Of The Air Conditioner And Pressure And Electric Current

    17.2 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
  • Page 94: Breakdown Self Diagnosis Function

    17.3 Breakdown Self Diagnosis Function 17.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code)  Every press of the button (up or down) will Once abnormality has occurred during operation, increase abnormality numbers and transmit the unit will stop its operation, and Timer LEDs abnormality code signal to the main unit.
  • Page 95: Error Codes Table

    17.4 Error Codes Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only  Indoor/outdoor wire terminal Indoor/outdoor operation can Indoor/outdoor After operation for ...
  • Page 96 Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation  Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality  Expansion valve and lead wire and connector ...
  • Page 97: Self-Diagnosis Method

    17.5 Self-diagnosis Method 17.5.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions  During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused  Faulty indoor unit PCB.
  • Page 98 17.5.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions  During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused  Wrong models interconnected.  Wrong indoor unit or outdoor unit PCBs mounted. ...
  • Page 99 17.5.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 100 17.5.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection.  Faulty sensor.
  • Page 101 17.5.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions  An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused  Lack of gas  Broken CT (current transformer) ...
  • Page 102 17.5.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused ...
  • Page 103 17.5.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 104 17.5.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 105 17.5.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 106 17.5.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 107 17.5.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection.
  • Page 108 17.5.12 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions  The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused  Wrong models interconnected.  Wrong indoor unit and outdoor unit PCBs used.  Indoor unit or outdoor unit PCB defective.
  • Page 109 17.5.13 H34 (Outdoor Heat Sink Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 110 17.5.14 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 111 17.5.15 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 112 17.5.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused  Operation stops due to short circuit inside the fan motor winding. ...
  • Page 113 17.5.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions  Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
  • Page 114 17.5.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions  Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) Malfunction Caused ...
  • Page 115 17.5.19 F11 (4-way valve Abnormality) Malfunction Decision Conditions  When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
  • Page 116 17.5.20 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions  When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor pipe temperature is below -1.0°C. Remark: When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit(s).
  • Page 117 17.5.21 F90 (Power Factor Correction Protection) Malfunction Decision Conditions  To maintain DC voltage level supply to power transistor.  To detect high DC voltage level after rectification. Malfunction Caused  During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
  • Page 118 17.5.22 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions  The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused  Lack of gas.  3-way valve close. Troubleshooting...
  • Page 119 17.5.23 F93 (Compressor Rotation Failure) Malfunction Decision Conditions  A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused  Compressor terminal disconnect  Faulty Outdoor PCB  Faulty compressor Troubleshooting...
  • Page 120 17.5.24 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions  During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
  • Page 121 17.5.25 F96 (IPM Overheating) Malfunction Decision Conditions  During operating of cooling and heating, when IPM temperature data (120°C) is detected by the IPM temperature sensor. Multi Models Only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
  • Page 122 17.5.26 F97 (Compressor Overheating) Malfunction Decision Conditions  During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor. Malfunction Caused  Faulty compressor tank temperature sensor  2/3 way valve closed ...
  • Page 123 17.5.27 F98 (Input Over Current Detection) Malfunction Decision Conditions  During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
  • Page 124 17.5.28 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused  DC current peak due to compressor failure. ...
  • Page 125: Disassembly And Assembly Instructions

    18. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 18.1.1...
  • Page 126 6. Remove the Particular Piece from the 3 hooks. Figure 3 9. Remove the earth wire screw. 11. Detach all connectors as labelled from the Main Electronic Controller. Then pull out the Main Electronic Controller gently. AC303 10. Pull out the Main Electronic Controller halfway.
  • Page 127 18.1.3 To Remove Discharge Grille 13. Pull out and remove the Drain Hose from the Discharge Grille. 12. Remove the 2 screws of the Discharge Grille. 14. Then pull the Discharge Grille downward gently to dismantle it. Figure 6 18.1.4 To Remove Control Board 15.
  • Page 128 18.1.5 To Remove Cross Flow Fan and Indoor Fan Motor 16. Remove the screw that holding the Cross Flow Fan and Fan Motor axis. Figure 8 18. Remove the Bearing by pulling it gently. 17. Remove the screw from the Evaporator. Figure 9...
  • Page 129 Evaporator 19. Push the holdfast to the left and lift up the Evaporator. 21. Fan Motor can be removed after the removal of the Cross Flow Fan. Reminder: To reinstall the Fan Motor, adjust the Fan Motor connector to 60° towards you before fixing Control Board Cross Flow Fan 20.
  • Page 130: Outdoor Electronic Controller Removal Procedure

    18.2 Outdoor Electronic Controller Removal Procedure 18.2.1 CU-FZ25WKE CU-FZ35WKE Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Screws Top Panel Release 3 Terminal Screws Connectors, L, N and Earth Wire Screw.
  • Page 131 18.2.2 CU-FZ50WKE Caution! When handling electronic controller, be careful of electrostatic discharge. 1. Remove the 5 screws of the Top Panel. 5. Remove the Control Board as follows: Fig. 1 Fig. 4 2. Remove the 8 screws of the Front Panel. Fig.
  • Page 132 18.2.3 CU-FZ60WKE Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove 2 screws for the plate of Terminal Board Cover. Top Panel Screw Plate of Terminal Board Cover Screws Screws Screws Fig.
  • Page 133: Technical Data

    19. Technical Data Technical data provided are based on the air conditioner running under free frequency. 19.1 Cool Mode Performance Data Unit setting: Standard piping length, Hi Fan, Cool mode at 16°C Voltage: 230V 19.1.1 CS-FZ25WKE CU-FZ25WKE Indoor (°C) Outdoor DB (°C) 19.0 3005 2367 387 2934 2345 470 2872 2330 506 2665 2240 582 2949 2359 410 2763 2278 534 2500 2206 680 22.0 3201 1798 409 3069 1782 502 3100 1785 454 3050 1767 485 3142 1817 408 2993 1755 540 2723 1660 685 15.7 2793 2371 369 2687 2312 438 2471 2206 492 2462 2218 557 2658 2322 424 2409 2207 541 2182 2090 667...
  • Page 134 19.1.4 CS-FZ60WKE CU-FZ60WKE Indoor (°C) Outdoor DB (°C) 19.0 6694 5378 1604 6211 5006 1613 6674 5332 1569 6813 5433 1505 7218 5639 1300 6751 5367 1605 6000 4629 1980 22.0 7564 4672 1412 7228 4325 1628 7376 4443 1670 7366 4429 1570 7900 4686 1312 7378 4421 1633 6674 4077 2012 15.7 5530 4777 1111 5449 4849 1245 5168 4692 1028 5024 4642 1068 4846 4510 606 5146 4706 1047 5360 4881 1931 18.4 6558 4287 1716 6757 4450 1549 6635 4402 1557 6474 4324 1637 6768 4483 1122 6609 4385 1605 6029 4155 1972 13.3 3883 3805 917 4462 4340 789 3820 3744 838 3984 3905 923 3530 3459 444 3983 3904 762 4078 3997 1236...
  • Page 135: Heat Mode Performance Data

    19.2 Heat Mode Performance Data Unit setting: Standard piping length, Hi Fan, Heat mode at 30°C Voltage: 230V 19.2.1 CS-FZ25WKE CU-FZ25WKE Indoor (°C) Outdoor WB (°C) 1590 2105 2500 2918 3173 1604 2140 2610 3150 3358 1550 2179 2747 3130 3602 19.2.2 CS-FZ35WKE CU-FZ35WKE...
  • Page 136: Service Data

    20. Service Data Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced heating mode. 20.1 Cool Mode Outdoor Air Temperature Characteristic Room Temperature: 27/19°C, Cooling Characteristic Fan: High Pipe Length: 5.0m Freq: Rated Fc 20.1.1 CS-FZ25WKE CU-FZ25WKE...
  • Page 137 20.1.2 CS-FZ35WKE CU-FZ35WKE 18.00 17.00 16.00 15.00 14.00 13.00 12.00 Outdoor Air Temperature (°C) 6.00 5.50 5.00 4.50 4.00 3.50 3.00 2.50 Outdoor Air Temperature (°C) 1.10 1.05 1.00 0.95 0.90 0.85 0.80 Outdoor Air Temperature (°C)
  • Page 138 20.1.3 CS-FZ50WKE CU-FZ50WKE 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 Outdoor Air Temperature (°C) 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 Outdoor Air Temperature (°C) 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 Outdoor Air Temperature (°C)
  • Page 139 20.1.4 CS-FZ60WKE CU-FZ60WKE 18.00 17.00 16.00 15.00 14.00 13.00 12.00 11.00 10.00 9.00 8.00 Outdoor Air Temperature (°C) 10.00 9.50 9.00 8.50 8.00 7.50 7.00 6.50 6.00 5.50 5.00 4.50 4.00 3.50 3.00 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 Outdoor Air Temperature (°C) 1.10 1.05...
  • Page 140: Heat Mode Outdoor Air Temperature Characteristic

    20.2 Heat Mode Outdoor Air Temperature Characteristic Room Temperature: 20°C, Heating Characteristic Fan: High Pipe Length: 5.0m Freq: Rated Fh 20.2.1 CS-FZ25WKE CU-FZ25WKE Outdoor Air Temperature (°C) 4.00 3.75 3.50 3.25 3.00 2.75 2.50 2.25 2.00 Outdoor Air Temperature (°C) 3.50 3.00 2.50...
  • Page 141 20.2.2 CS-FZ35WKE CU-FZ35WKE Outdoor Air Temperature (°C) 5.50 5.00 4.50 4.00 3.50 3.00 2.50 Outdoor Air Temperature (°C) 3.50 3.00 2.50 2.00 1.50 1.00 Outdoor Air Temperature (°C)
  • Page 142 20.2.3 CS-FZ50WKE CU-FZ50WKE Outdoor Air Temperature (°C) 8.00 7.50 7.00 6.50 6.00 5.50 5.00 4.50 4.00 3.50 3.00 Outdoor Air Temperature (°C) 4.00 3.50 3.00 2.50 2.00 1.50 Outdoor Air Temperature (°C)
  • Page 143 20.2.4 CS-FZ60WKE CU-FZ60WKE Outdoor Air Temperature (°C) 12.00 11.00 10.00 9.00 8.00 7.00 6.00 5.00 Outdoor Air Temperature (°C) 4.00 3.50 3.00 2.50 2.00 Outdoor Air Temperature (°C)
  • Page 144: Piping Length Correction Factor

    20.3 Piping Length Correction Factor The characteristic of the unit has to be corrected in accordance with the piping length. 20.3.1 CS-FZ25WKE CU-FZ25WKE CS-FZ35WKE CU-FZ35WKE 1.02 1.00 0.98 0.96 0.94 0.92 Pipe Length (m) 1.04 1.02 1.00 0.98 0.96 0.94 0.92 0.90 0.88...
  • Page 145 20.3.2 CS-FZ50WKE CU-FZ50WKE 1.04 1.00 0.96 0.92 0.88 Pipe Length (m) 1.01 1.01 1.00 1.00 0.99 0.99 0.98 Pipe Length (m) Note: The graphs show the factor after added right amount of additional refrigerant.
  • Page 146 20.3.3 CS-FZ60WKE CU-FZ60WKE 1.03 1.01 0.99 0.97 0.95 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Pipe Length (m) 1.01 1.01 1.00...
  • Page 147: Exploded View And Replacement Parts List

    21. Exploded View and Replacement Parts List 21.1 Indoor Unit CWH55025J CWH55051AJ (FOR FZ25WK ONLY) (FOR FZ50WK ONLY) 47596 85-3487 47598 85-3489 25 W ACXF 50 W ACXF C S- C S- CU-FZ25W CU-FZ50W 47596 25 W ACXF 85-3487 50 W ACXF 47598 85-3489...
  • Page 148 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-FZ25WKE CS-FZ35WKE REMARK CHASSIS COMPLETE ACXD50C03410 ← FAN MOTOR L6CBYYYL0334 ← CROSS-FLOW FAN COMPLETE ACXH02C01190 ← BEARING ASSY CWH64K1006 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C29310 ← FLARE NUT (LIQUID) CWT251048 ←...
  • Page 149 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-FZ50WKE CS-FZ60WKE REMARK CHASSIS COMPLETE ACXD50C03410 ACXD50C03730 FAN MOTOR L6CBYYYL0334 ← CROSS-FLOW FAN COMPLETE ACXH02C01190 ← BEARING ASSY CWH64K1006 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C29360 ACXB30C29320 FLARE NUT (LIQUID) CWT251048 ←...
  • Page 150: Outdoor Unit

    21.2 Outdoor Unit 21.2.1 CU-FZ25WKE CU-FZ35WKE (FOR FZ25WK ONLY) (FOR FZ35WK ONLY) 31700 65860 65861 31710 ACXF85- ACXF85- -F Z2 -F Z3 place. place. a cool, well-ventila other heat sources. a cool, well-ventila other heat sources. tightly welding closed, operations, tightly closed, welding...
  • Page 151 ACXB81-06510 ← BAG - COMPLETE CWG87C900 ← V-COIL COMPLETE (EXP. VALVE) ACXA43C06110 ← STRAINER CWB11094 ← DISCHARGE MUFFLER CWB121021 ← PANASONIC BADGE CWE373439 ← OPERATING INSTRUCTION ACXF55-27061 ← OPERATING INSTRUCTION ACXF55-27071 ← OPERATING INSTRUCTION ACXF55-27081 ← INSTALLATION INSTRUCTION ACXF60-38660 ←...
  • Page 152 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-FZ25WKE CU-FZ35WKE REMARK INSTALLATION INSTRUCTION ACXF60-38710 ← INSTALLATION INSTRUCTION ACXF60-38720 ← INSTALLATION INSTRUCTION ACXF60-38730 ← INSTALLATION INSTRUCTION ACXF60-38740 ← INSTALLATION INSTRUCTION ACXF60-38750 ← INSTALLATION INSTRUCTION ACXF60-38760 ← CWG861078 ← BASE BOARD - COMPLETE CWG62C1223 ←...
  • Page 153 21.2.2 CU-FZ50WKE 65862 31720 ACXF85- -F Z5 place. a cool, well-ventila other heat sources. tightly closed, operations , and : Keep good order, surfaces, welding RECOMME NDATIONS Keep from open flames, STORAGE Keep area dry. 65862 31720 ACXF85- -F Z5 place.
  • Page 154 4-WAYS VALVE ACXB00-01290 V-COIL COMPLETE (4-WAY VALVE) ACXA43C00250 O-RING ACXB81-06510 V-COIL COMPLETE (EXP. VALVE) ACXA43C06110 DISCHARGE MUFFLER CWB121058 STRAINER CWB11094 PANASONIC BADGE CWE373439 BAG - COMPLETE CWG87C900 SOUND PROOF MATERIAL CWG302952 SOUND PROOF MATERIAL CWG302745 OPERATING INSTRUCTION ACXF55-27061 OPERATING INSTRUCTION ACXF55-27071...
  • Page 155 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-FZ50WKE REMARK INSTALLATION INSTRUCTION ACXF60-38690 INSTALLATION INSTRUCTION ACXF60-38700 INSTALLATION INSTRUCTION ACXF60-38710 INSTALLATION INSTRUCTION ACXF60-38720 INSTALLATION INSTRUCTION ACXF60-38730 INSTALLATION INSTRUCTION ACXF60-38740 INSTALLATION INSTRUCTION ACXF60-38750 INSTALLATION INSTRUCTION ACXF60-38760 ACXG86-03760 BASE BOARD COMP. CWG62C1144 SHOCK ABSORBER (L) CWG713416 SHOCK ABSORBER (R) CWG713415...
  • Page 156 21.2.3 CU-FZ60WKE -31730 65863 ACXF85 -F Z ilated sources. place. a cool, well-vent other heat order, tightly welding closed, operation Keep flames, good surfaces, ENDATIO Keep from open STORAG Keep E RECOMM area dry. 65863 ACXF85 -31730 -F Z place. well-vent other ilated...
  • Page 157 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-FZ60WKE REMARK CHASSIS COMPLETE ACXD52K00320 FAN MOTOR BRACKET ACXD54-00140 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR L6CAYYYL0076 SCREW - FAN MOTOR MOUNT CWH551106J PROPELLER FAN ASSY ACXH03K00070 NUT - PROPELLER FAN CWH56053J COMPRESSOR 9RD132XAA21...
  • Page 158 PART NAME & DESCRIPTION QTY. CU-FZ60WKE REMARK INSTALLATION INSTRUCTION ACXF60-38720 INSTALLATION INSTRUCTION ACXF60-38730 INSTALLATION INSTRUCTION ACXF60-38740 INSTALLATION INSTRUCTION ACXF60-38750 PANASONIC BADGE CWE373439 OPERATING INSTRUCTION ACXF55-27081 INSTALLATION INSTRUCTION ACXF60-38760 CWG861461 BASE BOARD - COMPLETE CWG62C1131 SHOCK ABSORBER - LEFT CWG713217 SHOCK ABSORBER - RIGHT CWG713218 C.

Table of Contents