4.3

Check and clear of the faults history

The operation panel stores the fault indications which appears when a protective function is activated to display the fault
record for the past eight faults. (Faults history)
Check for the faults history
Monitor mode
Faults history mode
[Operation for displaying faults history]
Eight past faults can be displayed with the setting dial.
(The latest fault is ended by ".".)
Faults history1
Faults history2
Faults history8
When there is no faults
history, "E0" is displayed.

When an overcurrent trip occurs by an instantaneous overcurrent, the monitored current value saved in the faults history may be lower than the
actual current that has flowed.

The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from
0.
Parameter setting mode
Function mode
Press the
setting dial.
Faults history number
Latest fault
Faults history number
First fault in past
Press the
setting dial.
Faults history number
Seventh fault in past
Press the
setting dial.
Check and clear of the faults history
Output frequency
Flickering
Time
Flickering
Day
Flickering
Month
Flickering
PROTECTIVE FUNCTIONS
Output current ∗1
Flickering
Output voltage
Flickering
Cumulative
energization time ∗2
Flickering
Year
Flickering
79