Mitsubishi Electric FR-F802-E Instruction Manual page 55

Inverter for fans and pumps
Table of Contents

Advertisement

Connection of stand-alone option units
2.8.3
Connection of the power regeneration converter
(MT-RC)
When connecting the power regeneration converter (MT-RC), perform wiring securely as shown below. Incorrect connection
will damage the power regeneration converter and the inverter. After making sure that the wiring is correct, set "1" in Pr.30
Regenerative function selection.
MCCB
Three-phase
AC power
supply

For wiring to terminals P/+ and N/- of the FR-F842-08660(400K) or lower inverters, up to two cables can be connected. For wiring to the
terminals of the FR-F842-09620(450K) or higher inverters, up to four cables can be connected. To use more cables, use a bus bar.
NOTE
• When using the inverter with the MT-RC, install a magnetic contactor (MC) at
the input side of the inverter so that power is supplied to the inverter after 1 s or
more has elapsed after powering ON the MT-RC. When power is supplied to
the inverter prior to the MT-RC, the inverter and the MT-RC may be damaged
or the MCCB may trip or be damaged.
• When connecting the power coordination reactor and others, refer to
Instruction Manual of the MT-RC for precautions.
54
INSTALLATION AND WIRING
MC2
MC1
DCL
MT-RCL
R
S
T
Inverter / converter unit
U
R/L1
V
S/L2
W
T/L3
R1/L11
S1/L21
P1
P1
P/+
N/-
P
∗1
P
N
R2
RES
R2
STF
S2
S2
SD
T2
T2
C
B
R
A
S
RDY
T
R1
SE
S1
MT-RC
Inverter input power
M
Reset signal
Alarm signal
Ready signal
supply (MC2)
ON
MT-RC power
supply (MC1)
1s or more
ON