Electronic equipment reception interference ........................Environmental requirements ..............................Technical specifications ................................ Permitted door weight and door width for ASSA ABLOY SW300 ................. Permitted door weight and door width for ASSA ABLOY SW150 ................. How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work ................
Page 4
Coordination unit (only for ASSA ABLOY SW300) ......................LED Cable ......................................Battery backup unit ..................................Cover piece kit ....................................Closing time board kit (only for ASSA ABLOY SW300) ...................... Fire kit (only for ASSA ABLOY SW300) ............................ Mounting plate (for reinforcement of wall) ......................... 9.10 Labels .........................................
Page 5
17.3 Diagrams for Door weight ................................17.3.1 Aluminium frame with glass ............................. Troubleshooting ..................................18.1 Error indication ....................................Service/Maintenance ................................1007913-en-20.0 Issue 2021-02-04...
2 Instructions for safe operation Instructions for safe operation • Failure to observe the information in this manual may result in personal injury or damage to equipment. • To reduce the risk of injury to persons - use this operator with single or double pedestrian swinging or folding doors only.
SW300 is an electromechanical operator approved for fire door applications. The ASSA ABLOY SW300 and ASSA ABLOY SW150 are to be installed indoors where they are suitable for almost all types of external and internal swing doors. This widely-used operators can be found in applications ranging from handicapped-access in private homes to high-traffic retail operations.
3 Important information Environmental requirements ASSA ABLOY Entrance Systems products are equipped with electronics and may also be equipped with batteries containing materials which are hazardous to the environment. Disconnect power before removing electronics and battery and make sure it is disposed of properly according to local regulations (how and where) as was done with the packaging material.
ASSA ABLOY Entrance Systems AB Address: Lodjursgatan 10, SE-261 44 Landskrona, Sweden Type: ASSA ABLOY SW300 and ASSA ABLOY SW150 Mains supply: 100-240 V AC +10/-15%, 50/60 Hz, mains fuse max 10A (building installation) Note! The mains supply shall be installed with protection and an...
4 Technical specifications This product is to be installed internally. Permitted door weight and door width for ASSA ABLOY SW300 PUSH arm PUSH arm PULL arm PULL arm Door width (m) Issue 2021-02-04 1007913-en-20.0...
4 Technical specifications Permitted door weight and door width for ASSA ABLOY SW150 PUSH arm PULL arm Door width (m) 1007913-en-20.0 Issue 2021-02-04...
How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work The swing door operators ASSA ABLOY SW300 and ASSA ABLOY SW150 use a DC motor which is connected to the output shaft by a combination of a worm gear and spur gears. The push- or pull arm system that is connected to the output shaft opens the door in a surface mounted application.
5 How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work Opening When an activation signal is received by the control unit, the door is opened at the installer-adjusted opening speed. Before the door is fully open at back check, it slows automatically to low speed.
5 How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work 5.4.3 Extended closing torque (CLTQ) If the potentiometer CLTQ is set to 0°, the door will close with normal spring power. If the poten- tiometer is turned clockwise, the motor will increase the closing torque. Extended closing torque will be reduced to zero: •...
5 How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work 5.4.10 Double acting Opening inwards and with panic break out outwards see Quick Start 1011548. Functions on the extension unit EXU-SI Also see page 66 for more information. 5.5.1...
5 How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work 5.5.5 OPEN/CLOSE impulse The impulse will open the door and the door will stay open until a new impulse is given. If no impulse is given the door will close after 15 minutes. This can be made infinite by changing group of para- meters, see page 82.
5 How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work 5.5.7 Nurse and bed functionality Solution 1 Connect a bridge between 3 and 7 on the secondary EXU-SI. Use any impulse on primary to open primary door. Use Open/Close impulse on secondary to open both doors.
5 How the ASSA ABLOY SW300 and ASSA ABLOY SW150 work 5.6.2 Presence detection swingpath, door mounted When a sensor that is mounted on the swing side of a door detects an object, it will send a command to the control unit to stall the door. If the control unit has received a short signal from the sensor and there is still hold open time left on the control unit, the door will continue on its way open if the object has cleared.
6 Models Models Three main models of the ASSA ABLOY SW300 and ASSA ABLOY SW150 are available: • Single doors • Double doors (two operators) • Double egress doors (two operators) The operators are non-handed and not dependent on the hinges. The operators suit both pushing and pulling arm systems.
6 Models Double operator, surface mounted The product is delivered complete with back plate, control unit, end plates and cover. Total cover length CL includes end plates. Two operators can be mounted under the same cover (full length or a modular) to open one door each.
8 Arm systems Arm systems The installation process of arm systems is the same for Fire door installations, Basic installations and Inverse installations. Pushing installation with PUSH-arm This arm system is delivered with drive arm, telescopic part and door fitting. It is used if the oper- ator is installed on the wall on the opposite side of the door swing, and approved for fire door ap- plication for A up to 300 mm.
8 Arm systems Pulling installation with PULL-arm This arm system is delivered with drive arm, guide shoe and door fitting. Approved for fire door application for A up to 130 mm. PULL, 1008401BK/SI (A = -20-130 mm, B = 150 mm) PULL-220, 1011998BK/SI (A = -20-65 mm, B = 150 mm), only for LE Performance PULL-600, 1014729BK/SI (A = -20-230 mm, B = 250/420 mm) 20 mm extension...
8 Arm systems Pushing installation with PULL-arm This arm system consists of main arm, slide track, guide shoe and shaft adapter. It can be fitted on combinations of doors and jambs (walls), where the wall thickness does not exceed approx. 114 mm.
8 Arm systems Double acting kits One way automatic opening and opposite way panic opening. Identify the automatic opening, sliding PUSH or PULL. Opposite direction will be the manual break- away. RH/DIN, 1014091BK/SI LH/DIN, 1014090BK/SI Sliding PUSH PULL Automatic Automatic Issue 2021-02-04 1007913-en-20.0...
8 Arm systems Drive shaft extension kits 70 mm 50 mm 20 mm Art. No.: 1008396BK/SI Art. No.: 1008398BK/SI Art. No.: 1008400BK/SI Lower adapter M10, used for 20 mm lower installation height. Art. No.: 1010296BK/SI 1007913-en-20.0 Issue 2021-02-04...
Black Art. No.: 1003583 Coordination unit (only for ASSA ABLOY SW300) To coordinate rebated doors in a double door installation and to make sure the doors are closed in right order. See page for installation and adjustment.
Art. No.: 1007823 Cover piece kit Art. No.: 1009686BK/SI Closing time board kit (only for ASSA ABLOY SW300) To fulfill the DIN 18263-4 standard it is necessary to mount and connect this board to the lock kick. Art. No.: 1010374 1007913-en-20.0...
9 Options Fire kit (only for ASSA ABLOY SW300) For fire door installations. Containing a smoke detector ORS142W with silver cover, a Reset & Indication Device, Closing brake kit and a three pole connection cable harness. Art. No.: 1009899 Mounting plate (for reinforcement of wall) Art.
9 Options 9.10 Labels Label kit- including all below Art. No.: 1005227 Emergency break-out, DIN right door Emergency break-out, DIN left door Activation by disabled people Operator designed for disabled people Supervision of child ASSA ABLOY door sticker 1007913-en-20.0 Issue 2021-02-04...
10 Pre-installation Pre-installation 10.1 General tips/Safety concerns In all instances, where work is being done, the area is to be secured from ped- estrian traffic, and the main power removed to prevent injury. • Make sure that the power is off before installing. •...
Brick wall Expansion-shell bolt, min. M6x85, UPAT PSEA B10/25, min. 50 mm from the underside * ASSA ABLOY Entrance Systems minimum recommended requirements. Building Codes may give different specifications. ** Thinner wall profiles (3-5 mm) must be reinforced with rivet nuts.
11 Mechanical installation Mechanical installation The operator is mounted on either side of the door header depending on type of doors. The door is controlled with a push or pull arm system. If a coordination unit is to be installed on a double door installation, mount the coordinator base with rotor before mounting the transmission unit, see page 56.
Page 38
11 Mechanical installation A = 192 B = 557 Issue 2021-02-04 1007913-en-20.0...
Page 39
11 Mechanical installation A = 192 B = 557 1007913-en-20.0 Issue 2021-02-04...
Page 40
11 Mechanical installation A = 192 B = 557 Issue 2021-02-04 1007913-en-20.0...
11 Mechanical installation 11.1 PUSH arm system Reveal 1007913-en-20.0 Issue 2021-02-04...
Page 42
11 Mechanical installation Operator with PUSH arm system DIN Right (mm) Cable inlet Note! Screw head must be flush with back plate surface. Issue 2021-02-04 1007913-en-20.0...
Page 43
11 Mechanical installation Continuous "Operator with PUSH arm system" DIN Left (mm) Cable inlet Note! Screw head must be flush with back plate surface. 1007913-en-20.0 Issue 2021-02-04...
Page 44
Continuous "Operator with PUSH arm system" DIN Right DIN Left 20° 1. Pre-tension the spring Note! Only ASSA ABLOY SW300, not ASSA ABLOY SW150 2. Secure the pre-tension by the pin Let the stop arm locator and the stop arm be loose.
Page 45
11 Mechanical installation Continuous "Operator with PUSH arm system" MARK Align the marks between arm and adaptor. Align the arm with the operator mark. 15 Nm Loosen the four screws. Fasten the arm system to the door. 1007913-en-20.0 Issue 2021-02-04...
Page 46
11 Mechanical installation 14 Nm Tighten the four screws. The door must be closed. Hold the door a bit open and re- move the start position pin. 50 Nm See the table on page for available extensions. Continue on page Issue 2021-02-04 1007913-en-20.0...
11 Mechanical installation 11.2 PULL arm system Slim slide track Note! Measurement Z must be reduced by 20 mm if lower adapter from kit 1010296BK/SI is used. 1007913-en-20.0 Issue 2021-02-04...
Page 48
11 Mechanical installation Operator with PULL arm system DIN Left (mm) Cable inlet Note! Screw head must be flush with back plate surface. Issue 2021-02-04 1007913-en-20.0...
Page 49
11 Mechanical installation Continuous "Operator with PULL arm system" DIN Right (mm) Cable inlet Note! Screw head must be flush with back plate surface. 1007913-en-20.0 Issue 2021-02-04...
Page 50
11 Mechanical installation Continuous "Operator with PULL arm system" DIN Right DIN Left 20° Note! Only ASSA ABLOY SW300, not ASSA ABLOY SW150 Let the stop arm locator and the stop arm be loose. Do not tighten. Issue 2021-02-04 1007913-en-20.0...
Page 51
11 Mechanical installation Slim slide track Attach the slide track (1) to the door with the guide shoe (2) fitted into the track. Use appropriate screws. Slide track Guide shoe 1007913-en-20.0 Issue 2021-02-04...
Page 52
11 Mechanical installation Continuous. "Operator with PULL arm system" It is important to align the marks correctly. If necessary move one mark at a time. This corresponds to approx. 3° and will give a precision of ±1,5°. Align the marks. 50 Nm Hold the door a bit open and remove the start position pin.
11 Mechanical installation 11.3 Operator with sliding PUSH arm system Slim slide track Max. 114 Reveal See instructions for PULL installation. 1007913-en-20.0 Issue 2021-02-04...
11 Mechanical installation 11.4 ASSA ABLOY SW300 inverse installation with PUSH arm system Remove the microswitch lever (1), but not the micro switch (2). Remove also the stop arm (3). Microswitch lever Micro switch Stop arm Note! Set dip switch INV to ON for Inverse operation, see 12.1.1...
11 Mechanical installation 11.5 ASSA ABLOY SW300 inverse installation with PULL arm system Remove the microswitch lever (1), but not the micro switch (2). Remove also the stop arm (3). Microswitch lever Micro switch Stop arm Note! Set dip switch INV to ON for Inverse operation, see 12.1.1 on page...
11 Mechanical installation 11.6 Installation of coordination unit on Fire Door installations Before installing the transmission unit do step a-e below. Screw in the two steering pins (1) for the coordinator base. Steering pin Mount the rotor (parts 2 to 4 below) before the motor is installed on the back plate. Install the control unit when the installation of the coordination unit is completed.
Page 57
11 Mechanical installation d Mount the rotor (4) on the motor unit (7) with the screw (5) and washer (6) on the primary drive unit = for the door that opens first and closes last. Rotor Screw Washer Motor unit e Release the brake (26) by pushing in the linkage arm (14), so that the brake (26) is opened, push the fork (27) into the the coordinator base (15).
Page 58
11 Mechanical installation Mount the coordinator base (15) with the two screws (8) on the primary drive unit. Remove the screw (9) and throw the washer (24) away when mount the acceptor (11) on the adjuster (10). Mount the screw (9) through the acceptor (11). g Mount the transmission unit.
Page 59
11 Mechanical installation Mount the link rod (12) with its adaptor (13) into the linkage arm (14). Link rod Adaptor Linkage arm Mount on the other side of the link rod (12) to the secondary motor unit with the signal (16). Fasten the stop screw (17).
Page 60
11 Mechanical installation k Adjust the release of the brake by loosening the joint (18) and turning the link rod (12) close to the primary drive unit. Make the angle between the doors near closed position. Link rod Joint Route the cables, see illustrations on page 38. m Put the grease on the rod support.
Page 61
11 Mechanical installation n Mount the follower roller (20) at the leading edge close to the top of the secondary door leaf (21) with the appropriate screws (23). Follower roller Secondary door leaf Primary door leaf Screw 1007913-en-20.0 Issue 2021-02-04...
12 Electrical connection Electrical connection Note! During any work with the electrical connections the mains must be disconnected. • Place the electric switch easily accessible from the operator. If an plug contact is used in the installation the wall socket shall be placed easily accessible from the operator. •...
12 Electrical connection 12.1 Control units 12.1.1 CU-300 Synchronizing of double doors Hold open time Key hold open time DIP-switch Closing torque Symmetric cam (jumper off) Encoder Asymmetric cam (jumper on) Motor Program selector PUSH Motor +24V DC PULL = Lock-out for OPD (–) = Overhead presence detection/mat safety Lock Kick = Inner impulse...
12 Electrical connection 12.1.3 Extension units EXU-SI / EXU-SA Installation Torx T10 EXU-SA 5 mm nut driver Electrical power contact EXU-SI Tag strip long 2 pcs EXU short 1 pc EXU CU-300 1007913-en-20.0 Issue 2021-02-04...
12 Electrical connection 12.1.4 Extension unit EXU-SI This extension unit has inputs for electro-mechanical lock, program selector, batteries, KILL function, OPEN/CLOSE, KEY opening and outer impulse. Functions Battery backup unit (+) 24 VDC Program selector Unlocked signal from lock KILL reset (see jumper below) KILL impulse Key impulse (1.5-30 s) OPEN / CLOSE impulse (latching relay)
12 Electrical connection 12.1.5 Extension unit EXU-SA This extension unit has inputs for door mounted sensors, which can give presence impulse on approach side and/or presence detection on swing path side. Relay output for error indication, KILL output, Lock output or door indication is also integrated.
12 Electrical connection 12.1.6 Installation on double doors If the operators are to be mounted at the same height with pushing and pulling arm systems, the height is determined by the pulling arm system, PULL. The pushing arm system PUSH must always have a shaft extension, minimum 50 mm, maximum 70 mm to match the mounting heights visually.
12 Electrical connection 12.3 Double door installations There are four different types of double door installations: • Rebated Has an overlapping primary door, can be opened synchronously if it is not jamming and must be closed asynchronously to avoid that the doors will jam or close in the wrong order. •...
Start-up 13.1 ASSA ABLOY SW300 spring pre-tension The spring pre-tension is factory set to EN4. The closing torque (spring force) is adjusted by an hexagon nut placed at the end of the spring. Turning the nut clockwise increases the force. One turn equals a torque change of approx.
13 Start-up 13.2 Micro switch (only for ASSA ABLOY SW300) Check and adjust the micro switch, controlling the lock kick at power failure. 13.3 Adjusting the door stop a Close the door. b Open the door to required open position, plus approx. 15 mm. Put a doorbuffer under the door.
Page 75
13 Start-up d When stop arm is on the bottom of the operator, loose the stop arm locator and the stop arm. Mount the stop arm on the splines, as close as possible to the stop block 3). Mount the stop arm locator.
13 Start-up 13.4 Auto-learn-automatically sets back and latch check (recommended) This learning is performed by pushing the LEARN BUTTON (LRN). • Switch on the electrical power (the operator will find its closed position) and make sure the LED is on. •...
13 Start-up 13.4.1 Push the LEARN BUTTON (LRN) The door has no safety during auto-learn cycle. Remain clear of swing path of door, as door may close rapidly. Note! If the learn button is just pushed ones, a learn for reveal 0-100 mm will be carried out. For greater reveal keep the button pressed, and release it when the status LED is blinking for desired reveal, see below table.
When sensors are used in order to avoid contact with the door leaf it is required that the presence detect sensor and the presence impulse sensor fulfills Performance Level = c according to EN ISO 13849-1. These sensors shall also be monitored (tested) by ASSA ABLOY SW300 and ASSA ABLOY SW150 door operators. Configue sensor SP33-M:...
When properly installed and adjusted, attach the product label, which includes the CE mark on the right side of the lower part of the operator cover (see illustration). Apply the ASSA ABLOY logotype to the cover see illustration. Only for SE: Apply the SITAC label next to the product label - see illustration.
Product label: Mandatory Emergency break-out: Mandatory, if approved for escape route. ASSA ABLOY Entrance Systems door sticker: Mandatory, if applicable to highlight the presence of the glass (applied to all glass sections that are moving). Supervision of child (applied to both sides of the door): Mandatory according to national regulations. Recommended, if the risk analysis shows use by children.
16 Advanced settings Advanced settings 16.1 Learn with advanced setting of “back- and latch-check” See the prerequisites for performing a “learn” in section Auto-learn-automatically sets back and latch check (recommended) on page 76. a Push the button once as for auto-setting. The status LED starts to blink.
16 Advanced settings 16.3 Changing group of parameters (Level 2) a Disconnect batteries if any. b Disconnect the mains. c Press the LEARN BUTTON (LRN) and keep it depressed. d Connect the mains. e Watch the ERROR LED. Release the LEARN BUTTON after 2 flashes (LED is out). The ERROR LED flashes a number of short flashes that corresponds to the parameter group number (see table).
16 Advanced settings 16.4 Classification (Level 3) a Disconnect batteries if any. b Disconnect the mains. c Press the LEARN BUTTON (LRN) and keep it depressed. d Connect the mains. e Watch the ERROR LED. Release the LEARN BUTTON after 3 flashes (LED is out). g Identify the current classification The ERROR LED flashes an amount of short flashes that correspond to the classification number.
16 Advanced settings 16.5 Overhead Presence Detection and Interlock (Level 4) a Disconnect batteries if any. b Disconnect the mains. c Press the LEARN BUTTON (LRN) and keep it depressed. d Connect the mains. e Watch the ERROR LED. Release the LEARN BUTTON after 4 flashes (LED is out). g Identify the current monitoring The ERROR LED flashes an amount of short flashes that correspond to the status number.
16 Advanced settings 16.6 Enhanced Lock Kick, Fire Input and Extended Arm Selection (Level 5) a Disconnect batteries if any. b Disconnect the mains. c Press the LEARN BUTTON (LRN) and keep it depressed. d Connect the mains. e Watch the ERROR LED. Release the LEARN BUTTON after 5 flashes (LED is out).
17 Guide for installation and adjustments Guide for installation and adjustments 17.1 Complementary Safety Devices Swing Doors If there is any risk for finger jam, add finger protection strip at the hinge side for internal doors, article No. 833334 or add finger protection roll for external doors, article No. 833333. 17.2 Swing Doors Opening and Closing Time Adjust, as a minimum, the operator's opening and closing time according to the diagram below.
17 Guide for installation and adjustments 17.3 Diagrams for Door weight a Measure the door width (DW) and the door height (DH) in metres for one door leaf only. b Calculate the area DW x DH. c Select diagram for your type of door and the actual glass thickness. Find the weight. Example: Aluminium door with measurement DW = 1.5 m, DH = 2 m and glass thickness 12 mm.
18 Troubleshooting Troubleshooting Fault Possible reasons why Remedies/Explanations The door does not open Control switch is set to OFF Change the setting of the control switch The motor does not start Mains power is missing Check the mains power and fuse in the building Activation unit does not function Strap impulse inputs Presence detection is activated...
18 Troubleshooting 18.1 Error indication • During normal operation the status LED on the control unit is illuminated. • An extinguished LED indicates that there is no electrical power. • A flashing light on the LED indicates that the operator is out of function (see table below). •...
Service/Maintenance Regular inspections shall be made according to national regulations and product documentation by an ASSA ABLOY Entrance Systems-trained and qualified technician. The number of service occa- sions should be in accordance with national requirements and product documentation. This is especially important when the installation concerns a fire-approved door or a door with an emer- gency opening function.