Determination Of The Maximum Cable Length - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Determination of the
maximum cable length
Siemens Building Technologies
HVAC Products
The maximum cable length between transformer and bus users is dependent on the
type of cable (cross-sectional area), the number of actuators and the type of actuator
used (current).
The following graphs can be used to determine the maximum bus cable lengths
between the transformer and group of actuators or the AZL51..., depending on the
relevant influencing factors.
The assumption was made that the actuators within the group are close to one another.
The minimum cross-sectional area for the system examples shown results from the
start of the curve.
The maximum cable lengths for the defined system cables AGG5.640 and AGG5.630
result from the points of intersection in the graph.
50
48
46
44
42
40
38
36
34
32
AGG5.630 / 631
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
AGG5.630 / 631
(cable type 2)
AGG5.640 / 641
(cable type 1)
1 x SQM45
1
5
2 x SQM45
2
6
3 x SQM45
3
7
4 x SQM45
4
8
Bus connection between transformer and actuator group
Example: System cable AGG5.640 (connecting cable to the actuators)
Actuators, 2 x SQM45...
The point of intersection of the vetical line for the AGG5.640 (1.25 mm
(2 x SQM45.xxx) gives a maximum cable length of 33.4 m between the transformer and
the group of actuators.
The minimumcross-sectional area is 0.33 mm
Basic Documentation LMV51...
9 Mounting, electrical installation and service
AGG5.640 / 641
0.5
2 x SQM48
1 x SQM45 + 1 x SQM48
2 x SQM45 + 1 x SQM48
3 x SQM45 + 1 x SQM48
2
.
1.25
Cross-section in mm
2
2
) and curve
139/157
CC1P7550en
29.05.2002