Original instructions
Tina 5A
Bypassing unit
ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden
www.abb.com/lowvoltage

Advertisement

Table of Contents
loading

Summary of Contents for ABB Tina 5A

  • Page 1 Original instructions Tina 5A Bypassing unit ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/lowvoltage...
  • Page 2 DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall responsibility of ABB/JOKAB SAFETY for any act exceed the individual price of the product on which liability asserted.
  • Page 3: Table Of Contents

    Maintenance ..............................11 Testing of the safety functions .......................... 12 Troubleshooting ............................... 12 Operation ............................13 Information output signal attributes ........................13 Technical data ........................... 14 Dimensions ..............................15 EC Declaration of conformity ......................16 2TLC172131M0201, rev. A www.abb.com/lowvoltage 2011-09-20...
  • Page 4: Introduction

    Introduction Scope The purpose of these instructions is to describe the bypassing unit Tina 5A and to provide the necessary information required for installation and operation. Audience This document is intended for authorized installation personnel. Prerequisites It is assumed that the reader of this document has knowledge of the following: Basic knowledge of ABB/Jokab Safety products.
  • Page 5: Overview

    S2 and S3, therefore stopping the bypassing. The dynamic signal to S1 on Tina 5A must be the input signal from the first of the safety devices intended to bypass. The signal can be connected via output contacts from a safety relay, a safety timer or be initiated via a unit providing the dynamic signal as for example an Eden or a Spot.
  • Page 6: Connections

    Warning! The information channel output shall never be used for the safety purpose(s). S2 is used if: an odd number of dynamic safety units is to be bypassed using an odd (including Tina 5A) number of dynamic safety devices. See connection example below (drawing no. HE3824C-01).
  • Page 7: Connection Examples

    Connection examples Drawing number HE3824C-01 Caution! All cable colours according to ABB/Jokab Safety standard cables. 2TLC172131M0201, rev. A www.abb.com/lowvoltage 2011-09-20...
  • Page 8 Drawing number HE3824F-01 Caution! All cable colours according to ABB/Jokab Safety standard cables. 2TLC172131M0201, rev. A www.abb.com/lowvoltage 2011-09-20...
  • Page 9 Drawing number HE3824D-01 Caution! All cable colours according to ABB/Jokab Safety standard cables. 2TLC172131M0201, rev. A www.abb.com/lowvoltage 2011-09-20...
  • Page 10 Drawing number HE3824E-01 Caution! All cable colours according to ABB/Jokab Safety standard cables. 2TLC172131M0201, rev. A www.abb.com/lowvoltage 2011-09-20...
  • Page 11: Installation And Maintenance

    Bypassing of Eden and Tina units If one or more Eden or Tina units are bypassed by a Tina 5A, a diode such as a 1N4007 must be inserted with forward current out from pin-4 of the last bypassed unit.
  • Page 12: Testing Of The Safety Functions

    LED indication Expected causes of faults Checking and measures to take No dynamic signal to S1 Check dynamic signal input Mute LED off (on Tina 5A) Mount a new 820 / 2 W resistor at terminals Mute resistor removed L1-L2...
  • Page 13: Operation

    H) is given in the table below. Info output signal switch Delay 0 ms 0 ms Warning! The information output signal is not a failsafe signal and should never be used for the safety purpose(s). 2TLC172131M0201, rev. A www.abb.com/lowvoltage 2011-09-20...
  • Page 14: Technical Data

    No bypass: 10 mA Bypass using a 5 W indication lamp: 240 mA Bypass connection Tina 5A can bypass max. 30 Eden/Tina-units or 6 Spot T/R Time delay t (in/out) t < 260 µs Voltage supply at normal operation (protection OK)
  • Page 15: Dimensions

    Dimensions NB: All measurements in millimetres. 2TLC172131M0201, rev. A www.abb.com/lowvoltage 2011-09-20...
  • Page 16: Ec Declaration Of Conformity

    EC Declaration of conformity EC Declaration of conformity (according to 2006/42/EC, Annex2A) ABB AB declare that the safety components of ABB AB make with type designations and safety JOKAB SAFETY functions as listed below, is in conformity with the Directives Varlabergsvägen 11...