Philips OccuSwitch DALI LRM2070 User Manual page 55

Hide thumbs Also See for OccuSwitch DALI LRM2070:
Table of Contents

Advertisement

Parameter
Power-up state*
Background level*l
Mode setting*
Infrared group*
Fade time
Burn-in mode*
Motion detect timer**
Light sensor correction**
Feedback LED**
Table 15: Mode-independent parameters
* Can be changed with the IRT9090 extended IR programming tool
** Cannot be set by a user, please contact your Philips representative .
Range
Lights OFF,
Lights ON (default)
Min .
10%
20% (default)
30%
40%
50%
60%
70%
1 (default), 2, 3, 4, 5, 6, 7, 8, 9, 10
A (default), B, C, D, E, F, G
0 . 7 (default), 1, 1 .4, 2, 2 .8, 4, 5 . 7 , 8, 11 .3, 16, 22 .6, 32, 45 .3, 64 seconds
Enabled
Disabled (default)
Potentiometer setting, 70 seconds, 5, 10, 15, 20, 25, 30, 35 minutes
Default: potentiometer setting
Disabled, -40%, -30%, -20% (default), -10%, 5%, 10%, 15%, 20%, 25%, 30%, 35%,
40%, 45%, 50%
Enabled (default)
Disabled