Resumption of Service

After replacing the failed relay unit or repairing failed external circuits, take the following
procedures to restore the relay to the service.
• Switch on the DC power supply and confirm that the "IN SERVICE" green LED is lit and the
"ALARM" red LED is not lit.
• Supply the AC inputs and reconnect the trip outputs.
6.7.5
Storage
The spare relay should be stored in a dry and clean room. Based on IEC Standard 60255-6 the
storage temperature should be − 25 ° C to +70 ° C, but the temperature of 0 ° C to +40 ° C is
recommended for long-term storage.