6.2 Electrical Wiring Connection
(1) Perform the electrical wiring work for the CH-Boxes. Select the wire size according to the table below.
(2) Pay attention to the marks on the terminal block when connecting wires for CH-Box and I.U./O.U.
Refer to "Example of Electrical Wiring" for the wiring connection on the next page.
Table 6.1 Electrical Data and Recommended Wiring, Breaker Size
Power
Model
Supply
CH-AP04MSSX
JCH-AP04MSSX
1/N~, 220-240V, 50Hz
CH-AP08MSSX
1/N~, 220V, 60Hz
1/N~, 230V, 50Hz
JCH-AP08MSSX
1~, 208-230V, 60Hz*
CH-AP12MSSX
1~, 220V, 60Hz*
JCH-AP12MSSX
*For Mexico model
only.
CH-AP16MSSX
JCH-AP16MSSX
NOTES:
1) Follow local codes and regulations when selecting field wires.
2) The wire sizes marked with *1 in the above table are selected at the maximum current of the unit according to the
European Standard, EN60 335-1. Use the wires which are not lighter than the ordinary tough rubber sheathed flexible
cord (code designation H05RN-F) or ordinary polychloroprene sheathed flexible cord (code designation H05RN-F).
3) The wire sizes marked with *2 in the above table are selected at the maximum current of the unit according to the
wire, MLFC (Flame Retardant Polyflex Wire) manufactured by Hitachi Cable Ltd., Japan.
4) Use a shielded cable for the transmitting circuit and connect it to ground.
5) In the case that power cables are connected in series, add each unit maximum current and select wires below.
Selection According to EN60 335-1
Current i (A)
i < 6
6 < i < 10
10 < i < 16
16 < i < 25
25 < i < 32
32 < i < 40
40 < i < 63
63 < i
P5417025-rev.1
Earth Leakage
1
Main Switch
2
Breaker (ELB)
Nominal
Nominal
Nominal
Sensitive
Current
Current
Current
[A]
[mA]
15
30
Selection According to MLFC (at Cable Temperature of 90
2
Wire Size (mm
)
Current i (A)
0.75
1
15 < i < 19
1.5
19 < i < 24
2.5
24 < i < 34
4
34 < i < 47
6
47 < i < 63
10
63 < i < 78
*3
78 < i < 113
113 < i < 148
148 < i < 179
Minimum Wire Thickness [mm
3
Earth
Wire
Power Source
4
Fuse
Size
Cable Size
2
[A]
[A]
[mm
] EN60 335-1
15
15
2.0
0.75
Wire Size (mm
i < 15
0.5
0.75
1.25
2
3.5
5.5
8
14
22
30
2
]
Transmitting
5
Cable Size
1
2
1
MLFC
EN60 335-1
MLFC
0.5
0.75
0.5
2
)
*3: In the case that
current exceeds 63A,
do not connect cables
in series.
Maximum
Current
2
[A]
0.2
0.4
0.6
0.8
o
C)
21