Provides other helpful information that does not fall under the warning or caution categories. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
Manual 37386D DTSC-200 - ATS Controller Revision History Rev. Date Editor Changes NEW 07-12-12 Release 08-11-25 Implementation of the changes starting with SW version 1.0006 09-09-17 Implementation of the changes starting with SW version 1.0008 • S1 & S2 Start fail delay time: configuration range expanded from 100 s to 6500 s.
Manual 37386D DTSC-200 - ATS Controller Chapter 2. Configuration Configuration Via The Front Panel ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ How to operate the unit via the front panel is explained in the operation manual 37387. Please familiarize yourself with the unit, the buttons and their meaning/operation and the display monitoring using this manual. The display of parameters via the front panel will differ from the display of the parameters via the LeoPC1 program described in this manual.
• You may start the PC program as follows: - by "Start/Program/Woodward/LeoPC" (starting at version 3.1.xxx), or - by a double click on a file ending ".cfg" in the subdirectory "/LeoPC". • After the PC program was started, establish the communication by pressing the "F2" button. This will establish a data link between the unit and the laptop/PC.
General Information ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The DTSC-200 has been developed to control ATS (Automatic Transfer Switch) units. The main purpose of the ATS controller is to control and monitor the transfer switch as well as issuing an engine start signal to a connected genset control. The controller is continuously monitoring the presence of a source. If the preferred source fails, it attempts to transfer to a second source (emergency power supply, etc.).
Manual 37386D DTSC-200 - ATS Controller Monitoring Functions Source Monitoring • Overvoltage / undervoltage • Overfrequency / underfrequency • Voltage imbalance • Rotation field monitoring NOTE If one of these monitoring functions is triggered, the ATS controller attempts to change to the non- preferred source.
Manual 37386D DTSC-200 - ATS Controller Function Of The Inputs And Outputs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Discrete Inputs The discrete inputs may be grouped into two categories: programmable • The programmable discrete input has been programmed with a factory default function using the LogicsManager.
Page 14
Manual 37386D DTSC-200 - ATS Controller Relay Outputs The discrete outputs can be grouped into two categories: programmable • The relay output is freely programmable using the LogicsManager (which is described in the following text). pre-defined • The relay output has been pre-defined (programmed) with this function using the...
Manual 37386D DTSC-200 - ATS Controller Chapter 3. Parameters The description of the parameters is confined to the illustration via the PC-program. The parameters are thereby described as follows. Language and parameter text EN: English parameter text DE: German parameter text Caption Brief description of the parameter.
Password ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The DTSC-200 utilizes a password protected multi-level configuration access hierarchy. This permits varying degrees of access to the parameters being granted by assigning unique passwords to designated personnel. A distinction is made between the access levels as follows:...
Manual 37386D DTSC-200 - ATS Controller Event History ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The event history is a FIFO (First In/First Out) memory for logging alarm events and operation states of the unit. The capacity of the event history is 300 entries. As new event messages are entered into the history, the oldest messages are deleted once 300 events have occurred.
Manual 37386D DTSC-200 - ATS Controller Measuring ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ NOTE This controller is available in two different hardware version with either 1A [../1] or 5A [../5] current transformer inputs. Both versions are discussed in this manual. The set points for specific parameters will differ depending upon the hardware version.
Page 19
Manual 37386D DTSC-200 - ATS Controller Measurement principle: Source 1 3Ph 4W / 3Ph 3W / 1Ph 2W / 1Ph 3W S1 voltage measuring S1 Spannungsmessung Please refer to the comments on measuring principles in the installation ...
Page 20
Manual 37386D DTSC-200 - ATS Controller Measurement principle: Source 2 3Ph 4W / 3Ph 3W / 1Ph 2W / 1Ph 3W S2 voltage measuring S2 Spannungsmessung Please refer to the comments on measuring principles in the installation ...
Page 21
Manual 37386D DTSC-200 - ATS Controller Measurement principle: S1 Load current L1 L2 L3 / Phase L1 / Phase L2 / Phase L3 S1 Load current measuring S1 Last Strommessung Please refer to the comments on measuring principles in the installation ...
Manual 37386D DTSC-200 - ATS Controller Measuring: Transformers Voltage Transformer Voltage transformer, source 1, primary 50 to 650,000 V S1 voltage transf. primary S1 Spannungswandler primär Some applications may require the use of potential transformers to facilitate ...
Page 23
Manual 37386D DTSC-200 - ATS Controller Current Transformer NOTE This controller is available in two different hardware version with either 1A [../1] or 5A [../5] current transformer inputs. Both versions are discussed in this manual. The set points for specific parameters will differ depending upon the hardware version, indicated on the data plate.
Manual 37386D DTSC-200 - ATS Controller Application ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Application: Application Mode Application mode Util-Gen / Gen-Gen / Util-Util Application mode Betriebsmodus This parameter selects the basic function of the unit. If the unit is used to transfer ...
Manual 37386D DTSC-200 - ATS Controller Application: Transfer Timers Transfer commit YES / NO Transfer commit Transfer zustimmen This function is only effective if a transfer from the preferred source to the non- preferred source is requested. 4146 YES ....A transfer to the non-preferred source is committed as soon as the non-preferred source stable timer has started to count.
Page 26
Manual 37386D DTSC-200 - ATS Controller Source 1 source stable time 1 to 6500 s S1 Source Stable time S1 Stabilisierzeit This parameter configures the delay before source 1 is considered as OK. This timer starts after the last monitored value has returned within the restore limits 3333 following a source 1 outage.
Page 27
Manual 37386D DTSC-200 - ATS Controller Source 1 outage delay 0.1 to 10.0 s S1 outage delay S1 Ausfallverzögerung This timer defines the maximum time before source 1 (voltage, frequency and phase rotation) is considered as "not OK" to initiate a transfer to source 2. This 2804 timer starts if one of the monitored source 1 values exceeds the fail limits.
Manual 37386D DTSC-200 - ATS Controller [V], [f] rated value source stable timer source stable timer restore value source OK source not OK outage outage delay delay timer timer fail value source is stable stable timer start source has failed...
Manual 37386D DTSC-200 - ATS Controller Application: Transfer Logics (LogicsManager) NOTE All functions which are described in the following text may be assigned by the LogicsManager to any relay which is available via the LogicsManager and not assigned to another function. The assignment of the defined relays to defined functions occurs by selection of the application mode.
Page 30
Manual 37386D DTSC-200 - ATS Controller Inhibit Transfer to Source 1 If this logical output becomes TRUE, the transfer back to source 1 will be blocked temporarily and the "Inhib. XFR to S1" message is displayed. Application example: Supposed, there is a failure of source 1 (preferred source) in a hospital. Then, source 2 will be started and a transfer to source 2 will be performed.
Manual 37386D DTSC-200 - ATS Controller Interruptible Power Rate Provisions If this logical output becomes TRUE, the non-preferred source will be started, a transfer to the non-preferred source will be performed, and the "Pwr.rate.prov." message is displayed as soon as the non-preferred source supplies the load.
Page 32
Manual 37386D DTSC-200 - ATS Controller Gen-Gen Enable This function is only enabled if the application mode (parameter 4148) is configured to "Gen-Gen". If this logical output becomes TRUE (by energizing a DI for example), the gen-gen mode will be enabled.
Manual 37386D DTSC-200 - ATS Controller Application: Elevator Pre-Signal The elevator pre-signal flag (20.01) may be assigned to any output relay using the LogicsManager. The elevator pre-signal is important for buildings which are equipped with elevators. This signal will be enabled before any transfer in order to signal a transfer to an elevator control.
Manual 37386D DTSC-200 - ATS Controller The following examples show the behavior of the elevator pre-signal for different applications. Example 1 (elevator pre-signal disabled): Transfer to non-preferred source is requested & non-preferred source non-preferred source has been started stable timer...
Manual 37386D DTSC-200 - ATS Controller Application: Motor Load Disconnect The motor load disconnect flag (20.02) may be assigned to any output relay using the LogicsManager. The motor load disconnect function is intended for sequential load shedding before a transfer and sequential load addition after a transfer.
Manual 37386D DTSC-200 - ATS Controller Application: Source Priority Selection The two LogicsManager functions "Source Priority S1" and "Source Priority S2" are used to determine which source is to be considered as preferred. The LogicsManager enables to use a discrete input for example to select the preferred source externally using a source priority selector switch, which is usually on the operation panel.
Manual 37386D DTSC-200 - ATS Controller Application example 1 (source priority = S1): Transfer direction upon loss of S1 preferred source non-preferred source (emergency source) Load Figure 3-7: Source priority selection - S1 preferred Application example 2 (source priority = S2):...
Page 38
Manual 37386D DTSC-200 - ATS Controller Extended Parallel Time NOTE This function is only effective if the transfer switch type (parameter 3424) is configured to "Closed" and in-phase monitoring (parameter 4570) is enabled. If a closed transition is performed, the overlap time of the make-before-break process, in which both sources are LogicsManager parallel, is as configured in parameter 4577 (Max.
Page 39
Manual 37386D DTSC-200 - ATS Controller The following example shows a typical transfer sequence from source 1 to source 2 with extended parallel time: Initial situation: Load is supplied by source 1 A transfer is initiated (e.g. by a load test): As soon as source 2 is detected as stable and synchronicity is achieved, the transfer switch is closed to source 2.
Manual 37386D DTSC-200 - ATS Controller Load Shed NOTE Load shed is inactive as long as an "Extended parallel time" (parameter 12860) is enabled. The load shed function bypasses the in-phase monitoring function. This can cause an asynchronous transfer in case a standard transition switch is used.
Manual 37386D DTSC-200 - ATS Controller Table 3-2 defines the behavior in case of a load shed request when utilizing a delayed or closed transition switch depending on the system conditions. Load is connected to Pre-transfer In-phase Preferred source Behavior on load shed request...
Manual 37386D DTSC-200 - ATS Controller Breaker ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Breaker: Transfer Switch Type Transfer switch type Standard / Delayed / Closed Transfer switch type Transfer Schalter Typ This parameter configures the type of ATS switch, which is connected to the ...
Manual 37386D DTSC-200 - ATS Controller Delayed Transfer Switch If an delayed transition switch is used, "Delayed" transfer switch type must be selected. This switch type may take on three states: • Position 1: Connected to source 1 Transfer Switch...
Manual 37386D DTSC-200 - ATS Controller Closed Transfer Switch If an closed transition switch is used, "Closed" transfer switch type must be selected. This switch type may take on four states: • Position 1: Connected to source 1 Transfer Switch...
Page 45
Manual 37386D DTSC-200 - ATS Controller Use Limit Switch Open Replies This function is used to define the limit switch reply signals, which are evaluated for determining the current ATS switch position. The following four signals are available for determining the ATS switch position: •...
Page 46
Manual 37386D DTSC-200 - ATS Controller Transition Timers The "Neutral Time S2 -> S1" parameter is only enabled, if "Delayed" or "Closed" is configured as "Transfer switch type" (parameter 3424) and inphase monitoring is disabled (parameter 4570). Neutral Time S2 -> S1 0 to 6500 s Neutral Time S2->S1...
Manual 37386D DTSC-200 - ATS Controller Waiting time until next transition attempt 0.1 to 99.9 s Wait time until next XFR attempt This parameter configures the interval following an unsuccessful transition Wartezeit vor neuem Transfer attempt before a new transition attempt is being performed.
Page 48
Manual 37386D DTSC-200 - ATS Controller Triggering of the "Fail to close S1" failure This failure is triggered if the following conditions are met: • Source 1 is available • The ATS controller has issued the C1 signal (LogicsManager flag (20.07)) to close to source 1 As soon as the C1 signal (command: close to source 1) is issued, the "Limit switch reply timeout"...
Page 49
Manual 37386D DTSC-200 - ATS Controller Triggering of the "Fail to open S1" failure This failure is triggered if the following conditions are met: • Source 2 is available • The ATS controller has issued the C1O signal (LogicsManager flag (20.08)) to open source 1 As soon as the C1O signal (command: open source 1) is issued, the "Limit switch reply timeout"...
Manual 37386D DTSC-200 - ATS Controller Test Modes ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ There are two different types of system tests: • Load Test This is a test with load transfer. If a load test is requested, a failure of the preferred source will be simulated.
Manual 37386D DTSC-200 - ATS Controller Monitoring ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Monitoring: Alarm Acknowledgement Self acknowledgment of the centralized alarm (horn) 0 to 1,000 s Time until horn reset Zeit Hupenreset After each alarm occurs, the alarm LED flashes and the command variable 03.05 ...
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 1 Monitoring Voltage monitoring source 1 Ph - Ph / Phase - N Voltage monitoring S1 Spg.-Überwachung S1 The unit can either monitor the wye voltages (phase-neutral: 3ph-4w, 1ph-3w and ...
Page 53
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 1 Monitoring: Underfrequency Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value. This permits a very rapid and accurate frequency measurement. The frequency however will be measured properly even if voltage is applied to one phase only.
Page 54
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 1 Monitoring: Overfrequency Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value. This permits a very rapid and accurate frequency measurement. The frequency however will be measured properly even if voltage is applied to one phase only.
Page 55
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 1 Monitoring: Voltage Imbalance The voltage imbalance monitoring is practically used to detect defective fuses in certain phases. The voltage imbalance monitoring measures voltage differences between the phases of source 1. The voltage is measured three-phase.
Page 56
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 1 Monitoring: Phase Rotation CAUTION Please ensure during installation that all voltages applied to this unit are wired correctly to both sides of the circuit breaker. Failure to do so may result in damage to the control unit and/or generation...
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 2 Monitoring Voltage monitoring source 2 Ph - Ph / Phase - N Voltage monitoring S2 Spg.-Überwachung S2 The unit can either monitor the wye voltages (phase-neutral: 3ph-4w, 1ph-3w and ...
Page 58
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 2 Monitoring: Underfrequency Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value. This permits a very rapid and accurate frequency measurement. The frequency however will be measured properly even if voltage is applied to one phase only.
Page 59
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 2 Monitoring: Overfrequency Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value. This permits a very rapid and accurate frequency measurement. The frequency however will be measured properly even if voltage is applied to one phase only.
Page 60
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 2 Monitoring: Voltage Imbalance The voltage imbalance monitoring is practically used to detect defective fuses in certain phases. The voltage imbalance monitoring measures voltage differences between the phases of source 2. The voltage is measured three-phase.
Page 61
Manual 37386D DTSC-200 - ATS Controller Monitoring: Source 2 Monitoring: Phase Rotation CAUTION Please ensure during installation that all voltages applied to this unit are wired correctly to both sides of the circuit breaker. Failure to do so may result in damage to the control unit and/or generation...
Manual 37386D DTSC-200 - ATS Controller Monitoring: In-Phase Monitoring (Synch Check) The in-phase monitoring function is used to determine whether the phase angles of the preferred source and the non-preferred source are in phase, i.e. whether the relative phase difference of the two sources is within specified limits.
Page 63
Manual 37386D DTSC-200 - ATS Controller Monitoring: Inphase Monitoring: Parameters Inphase monitoring ON / OFF In-Phase monitor Synchrocheck This parameter configures, whether inphase monitoring is performed. OFF ....No inphase monitoring is performed prior to a transfer.
Page 64
Manual 37386D DTSC-200 - ATS Controller Maximum Overlap Time NOTE This function is only effective if the transfer switch type (parameter 3424) is configured to "Closed" and in-phase monitoring (parameter 4570) is enabled. NOTE If the LogicsManager function "Extended parallel time" (parameter 12860) is TRUE, the maximum overlap time is not effective.
This will result in system [A] and system [B] being at the same voltage potential. The phase angle deviation will now be displayed on the DTSC-200 Counters screen (refer to the Navigation section of the Operation manual 37387). Enter the displayed value into this parameter.
1. Because of the transformer the phase angles at the breaker differ DTSC-200 between the measuring voltages of system [A] and system [B]. A phase angle deviation exists which can be compensated with the DTSC-200. High voltage side Dyn5 Using the vector group 5 (Dyn5) it counts α...
Page 67
Manual 37386D DTSC-200 - ATS Controller Outcome on Inphase Timeout Inphase timeout after 0 to 6,500 s In-phase timeout after Synchr. Zeitüberschr. This parameter configures the maximum time for attempting to detect synchronicity. This timer starts to count as soon as inphase monitoring is enabled 4576 prior to a transfer.
Manual 37386D DTSC-200 - ATS Controller Monitoring: Overcurrent Current is monitored depending on the parameters 1860 "S2 Load current measuring" and 1863 "S1 Load current measuring". Only the current of the source, which is connected to the load, is measured, because the CT is located at the load connection.
Page 69
Manual 37386D DTSC-200 - ATS Controller Load overcurrent, TOC: Monitoring (Level 1/Level 2/Level 3) ON / OFF Monitoring Überwachung ON ....Overcurrent monitoring is carried out according to the following parameters. Monitoring is performed at three levels. All three values...
Manual 37386D DTSC-200 - ATS Controller Monitoring: Overload Power is monitored depending on the parameters 1861 "S2 voltage measuring", 1862 "S1 voltage measuring", 1860 "S2 Load current measuring" and 1863 "S1 Load current measuring". Only the power of the source, which is connected to the load, is measured, because the CT is located at the load connection.
Page 71
Manual 37386D DTSC-200 - ATS Controller Overload: Monitoring (Level 1/Level 2) ON / OFF Monitoring Überwachung ON ....Overload monitoring is carried out according to the following parameters. Monitoring is performed at two levels. Both values may...
Manual 37386D DTSC-200 - ATS Controller Monitoring: Engine, Start Failure Source 1 If this protective function is triggered, the alarm list indicates "Start Fail S1". Source 1 start fail: delay time 1 to 6500 s S1 start fail delay time S1 Startfehler Zeit If the "S1 start delay"...
Manual 37386D DTSC-200 - ATS Controller Monitoring: Battery, Overvoltage There are two battery overvoltage alarm levels available in the control. Both alarms are definite time alarms and are illustrated in the below figure. The figure diagrams a frequency trend and the associated pickup times and length of the alarms.
Page 74
Manual 37386D DTSC-200 - ATS Controller Battery overvoltage: Monitoring (Level 1/Level 2) ON / OFF Monitoring Überwachung ON ....Overvoltage monitoring of the battery voltage is carried out according to the following parameters. 3450 3456 OFF ....Monitoring is disabled for level 1 and/or level 2.
Manual 37386D DTSC-200 - ATS Controller Monitoring: Battery, Undervoltage There are two battery undervoltage alarm levels available in the control. Both alarms are definite time alarms and are illustrated in the below figure. The figure diagrams a frequency trend and the associated pickup times and length of the alarms.
Page 76
Manual 37386D DTSC-200 - ATS Controller Battery undervoltage: Monitoring (Level 1/Level 2) ON / OFF Monitoring Überwachung ON ....Undervoltage monitoring of the battery voltage is carried out according to the following parameters. 3500 3506 OFF ....Monitoring is disabled for level 1 and/or level 2.
Manual 37386D DTSC-200 - ATS Controller Monitoring: CANopen Interface The CANopen interface is monitored. If the interface does not receive a CANopen protocol message before the delay expires, an alarm will be initiated. If this protective function is triggered, the alarm list indicates "CAN Open Fault".
1225 Table 3-9: Discrete inputs - parameter IDs If a Woodward IKD 1 or other external expansion board (Phoenix BK 16DiDo/Co 16DiDo) is connected to the DTSC via the CAN bus, it is possible to use 16 additional discrete inputs.
1 to neutral position) [C1O] LogicsManager [R 9] 48/49 (pre-defined with command: open from source 2 to neutral position) [C2O] External relay output (via CANopen; not included in DTSC-200 delivery; can be an expansion card like IKD1) LogicsManager [Rex01] [Rex02] LogicsManager [Rex03]...
12170 Table 3-12: Discrete outputs - parameter IDs If a Woodward IKD 1 or other external expansion board (Phoenix BK 16DiDo/Co 16DiDo) is connected to the DTSC via the CAN bus, it is possible to use 16 additional discrete outputs.
Manual 37386D DTSC-200 - ATS Controller Counters ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Configure Counters: Operation Hours, kWh, and kvarh Counter: Set point value for counters 0 to 99,999,999 Counter value preset Zähler-Setzwert This value is utilized to set the hours in the following parameters: ...
Manual 37386D DTSC-200 - ATS Controller LogicsManager ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ LogicsManager: Internal Flags LogicsManager Internal flags within the logical outputs may be programmed and used for multiple functions. For conditions and explanation of programming please refer to page 101 in chapter "LogicsManager").
Manual 37386D DTSC-200 - ATS Controller LogicsManager: Timer LogicsManager: Daily Time Set Point LogicsManager Utilizing the it is possible to establish specific times of the day that functions (i.e. generator exerciser) can be enabled. The two daily time set points are activated each day at the configured time. Using the LogicsManager these set points may be configured individually or combined to create a time range.
Page 85
Manual 37386D DTSC-200 - ATS Controller Timer: Active time set point: second 0 to 59 s Active second Aktive Sekunde Enter the second of the active switch point here. Example: 0....0 second of the minute. 1660 59 ....
Manual 37386D DTSC-200 - ATS Controller Interfaces ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ NOTE Please refer to the Interface Manual 37389 for a detailed description of the interface parameters. Interfaces: Device address 1 to 127 Device number Gerätenummer So that this control unit may be positively identified on the CAN bus, the unit ...
Page 88
Manual 37386D DTSC-200 - ATS Controller Interfaces: CAN BUS: CANopen: Additional Server SDOs CAN bus: Client->Server COB-ID (rx) 1 to FFFFFFFF Client->Server COB-ID (rx) 2. Client->Server COB-ID (rx) In a multi-master application, each Master needs its own identifier (Node ID) from ...
Manual 37386D DTSC-200 - ATS Controller NOTE The COB IDs must be entered in decimal numbers in LeoPC 1 and in hexadecimal numbers in the unit. Here are some important conversions: Hexadecimal value Decimal value 181h 201h 281h 301h 381h...
Page 90
No func..No external unit is selected for connection. The CAN bus is disabled. Values are not sent or received. IKD ..The unit is pre-configured for the connection of a Woodward IKD 1 expansion board. IKD ..The unit is pre-configured for the connection of a second Woodward IKD 1 expansion board.
Page 91
Manual 37386D DTSC-200 - ATS Controller RPDO-COB-ID ext. device 1 1 to FFFFFFFF RPDO-COP-ID ext. device {x} RPDO-COP-ID ext. Gerät {x} Value to be written in the object 1800h sub index 1h of the external device. 9070...
Page 92
Manual 37386D DTSC-200 - ATS Controller CAN bus 1: Transmit PDO 1 - Transmission type 0 to 255 Transmission type Transmission type This parameter contains the communication parameters for the PDOs the unit is able to transmit. It defines whether the unit broadcasts all data automatically (value...
Page 93
Manual 37386D DTSC-200 - ATS Controller CAN bus 1: Transmit PDO 1 - 3. Mapped object 0 to 65535 3. Mapped Object 3. Mapped Objekt This parameter contains the information about the mapped application variables. These entries describe the PDO contents by their index. The sub-index is always 1.
Manual 37386D DTSC-200 - ATS Controller Interfaces: Serial Interface 1 (RS-232) Serial interface: Baud rate 2.4 / 4.8 / 9.6 / 14.4 / 19.2 / 38.4 / 65 / 115 kBaud Baudrate Baudrate A DPC (P/N 5417-557) must be used for connecting the control unit ...
Manual 37386D DTSC-200 - ATS Controller System ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ System: Configure Display Backlight Display backlight ON / OFF / Auto / Key actv. Configure display backlight Konfig. Display Beleuchtung This parameter determines the behavior of the display backlight. The following ...
Manual 37386D DTSC-200 - ATS Controller System: Configure Daylight Saving Time It is possible to configure the real-time clock for an automatic change to daylight saving time. Start and end date/time of the daylight saving time period have to be entered for this.
Manual 37386D DTSC-200 - ATS Controller System: Password System Refer to the Password section on page 16 for a detailed description of the password system. Password system: Code level via display Info Code level display Codeebene Display This value displays the code level, which is currently enabled for access via the ...
Page 98
Woodward technicians! NOTE If the DTSC-200 parameters are read out via CAN / DPC and stored as standard values, all parameters behind parameter 1701 (Set default values) will not be overwritten when writing back the standard value file via CAN / DPC.
Manual 37386D DTSC-200 - ATS Controller System: Real-Time Clock Set This screen shows the current date and time. The clock is implemented as real time clock. In case of a voltage supply failure an internal battery guarantees that the information is not lost. The data stand for: XX:YY:ZZ .....
Manual 37386D DTSC-200 - ATS Controller System: Versions The parameters in this section are informational only and cannot be modified. The control unit may be identified from the numbers located on the unit and in the software. The most important technical information is located on the unit data plate.
Manual 37386D DTSC-200 - ATS Controller Appendix A. LogicsManager LogicsManager is used to customize the sequence of events in the control such as the start command of unit the engine or the operation of control unit relay outputs. For example, the start routine may be programmed so that it requires the closing of a discrete input or a preset time of day.
Manual 37386D DTSC-200 - ATS Controller Structure and description of the LogicsManager Sign [S1] Command [C1] Sign [S2] Command [C2] Sign [S3] Command [C3] Figure 3-29: LogicsManager - function overview • Command (variable) - A list of over 100 parameters and functions is provided for the command inputs.
Manual 37386D DTSC-200 - ATS Controller Configuration of the chain of commands LogicsManager Using the values specified in the above table, the chain of commands of the (for example: operating the relays, setting the flags, specification of the automatic functions) is configured as follows:...
Manual 37386D DTSC-200 - ATS Controller Logical Outputs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The logical outputs or combinations may be grouped into three categories: • internal logical flags • Internal functions • relay outputs NOTE The numbers of the logical outputs in the third column may again be used as input variable for other outputs in the LogicsManager.
Manual 37386D DTSC-200 - ATS Controller Logical Outputs: Relay Outputs All relays may be controlled directly by the LogicsManager depending on the respective application mode. Name Function Number Relay 1 If this logical output becomes true, the relay output 1 will be activated 13.01...
Manual 37386D DTSC-200 - ATS Controller Logical Command Variables: [01.00] - Alarm Classes Alarm class commands, Logic command variables 01.01-01.10 Alarm classes may be configured as command variables for all logical outputs in the LogicsManager. Number Name / Function Note...
Manual 37386D DTSC-200 - ATS Controller Logical Command Variables: [04.00] - Operating Status Operating status commands, 4.01-04.15 These operating statuses may be used as command variable in a logical output to set parameters for customized operations. Name Function Note 04.01...
Manual 37386D DTSC-200 - ATS Controller Logical Command Variables: [08.00] - Alarms of the System System alarms status commands, 08.01-08.10 These system alarms may be used as command variable in a logical output n to set parameters for customized operations.
Manual 37386D DTSC-200 - ATS Controller Logical Command Variables: [11.00] - Time Functions Time function commands, 11.01-11.10 Time functions may be used as command variable in a logical output. Number Name / Function Note 11.01 Set point 1 (exceeded) see page 84 11.02...
Manual 37386D DTSC-200 - ATS Controller Logical Command Variables: [13.00] - Status Of The Internal Relay Outputs Discrete output commands, 13.01-13.08 The discrete outputs may be used as command variable in a logical output. Number Name / Function Note 13.01 Digital output DO1 [R01] 13.02...
Switch alarm: Fail to close (to switch position) S2 21.11 Switch alarm: Mechanical fail (not plausible limit switch feedbacks have been detected by the DTSC-200) 21.12 In-Phase monitor alarm: In-phase timeout (the system was not able to establish a "Sync" situation within the configured time) 21.13...
Manual 37386D DTSC-200 - ATS Controller Factory Setting ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The inputs, outputs, and internal flags, which may be programmed via the LogicsManager have the following factory default settings when delivered: simple (function) extended (configuration) result Factory Setting: Functions Inhibit ATS...
Page 115
Manual 37386D DTSC-200 - ATS Controller simple (function) extended (configuration) result Remote peak shave (parameter 12630 on page 30) If TRUE, the remote peak shave function will be performed. Prepared for: - Deactivated by default FALSE Interruptible power rates...
Page 116
Manual 37386D DTSC-200 - ATS Controller simple (function) extended (configuration) result Source 1 priority (parameter 12680 on page 36) If TRUE, source 1 is preferred. Prepared for: - Activated by default TRUE Source 2 priority (parameter 12810 on page 36) If TRUE, source 2 is preferred.
Page 117
Manual 37386D DTSC-200 - ATS Controller simple (function) extended (configuration) result Delayed mode active (parameter 12850 on page 45) If TRUE, the transfer switch type will be set to Delayed. Prepared for: - Deactivated by default FALSE...
Manual 37386D DTSC-200 - ATS Controller simple (function) extended (configuration) result Factory Setting: Relay Outputs Relay {x} [R0x]; {x} = 1 to 4 (parameters 12100, 12110, 12310, and 12320 on page 81) If TRUE, relay 1 will be energized. ...
Page 120
Manual 37386D DTSC-200 - ATS Controller simple (function) extended (configuration) result Relay 8 [R08] (parameter 12160 on page 81) If TRUE, relay 8 will be energized. True, if the command: Open from Source 1 is issued dependent...
Manual 37386D DTSC-200 - ATS Controller simple (function) extended (configuration) result Factory Setting: Internal Flags Internal flag {x}; {x} = 1 to 7 (refer to Table 3-14 on page 83 for the parameter IDs of the parameters for internal flags 1 through 7) If TRUE, the internal flag {x} will be ...
Manual 37386D DTSC-200 - ATS Controller Discrete Inputs [D1] Reply from ATS switch: Breaker in source 1 position [D2] Reply from ATS switch: Breaker in source 2 position [D3] Reply from ATS switch: Breaker in source 1 open position [D4]...
Manual 37386D DTSC-200 - ATS Controller Appendix B. GetEventLog The event logger is a 300-entry FIFO (First In/First Out) memory for logging alarm events and operation states of the unit. Refer to the Event History section on page 17 for more info about the event logger.
Manual 37386D DTSC-200 - ATS Controller Reading Out GetEventLog On the Eventlog tab of GetEventLog, click the Request Eventlog button to read out the content of the event logger memory. The content of the event logger is displayed as shown in Figure 3-33.
Manual 37386D DTSC-200 - ATS Controller Resetting the Event Logger The event logger can be reset using the parameter "Clear event log" via the front panel or LeoPC1 (deleted events or empty entries are represented with a series of dashes in the event logger). To do this, perform the following...
Manual 37386D DTSC-200 - ATS Controller Appendix C. List Of Parameters Unit number P/N _____________________________ Rev _______________________________ Version DTSC- ________________________________________________________________ Project ______________________________________________________________________ Serial number S/N _______________ Date ______________________________ Par. Parameter Setting range Default value Customer setting Data type MAIN MENU...
Page 127
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type APPLICATION Util-Gen Util-Gen Util-Gen 4148 Application mode Gen-Gen Util-Gen Gen-Gen Gen-Gen UNSIGNED Util-Util Util-Util Util-Util 4146 Transfer Commit YES / NO ...
Page 128
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type MONITORING 1756 Time until horn reset 0 to 1000 s 180 s UNSIGNED 12490 External acknowledge see descr. in LogicsManager chap. starting page 114; default: (0 & 0)+ 0...
Page 129
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type MONITORING Load Monitoring Overcurrent Monitoring level 1 2200 Monitoring ON / OFF 1 0 1 0 UNSIGNED 2204 Limit 50.0 to 300.0 % 110.0 %...
Page 130
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type DIGITAL INPUTS Digital Input 1 N.O. DI 1 operation N.C. UNSIGNED N.C. DI 1 delay 0.08 to 650.00 s 0.08 s UNSIGNED Digital Input 2 N.O.
Page 131
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type DIGITAL INPUTS External Digital Input 3 N.O. N.O. N.O. 16021 Operation N.O. UNSIGNED N.C. N.C. N.C. 16020 Delay 0.05 to 650.00 s 0.20 s...
Page 132
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type DIGITAL OUTPUTS 12100 Relay 1 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman 12110 Relay 2 see descr. in LogicsManager chap.
Page 133
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type COMMUNICATION INTERFACES 1702 Device number 1 to 127 UNSIGNED CAN Interfaces OFF OFF 3155 Protocol CAN Open CAN Open CAN O.
Page 134
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type COMMUNICATION INTERFACES Transmit PDO 3 9620 COB-ID 1 to FFFFFFFF UNSIGNED 9622 Transmission type 0 to 255 UNSIGNED 9624 Event-timer 20 to 65000 ms...
Page 135
Manual 37386D DTSC-200 - ATS Controller Par. Parameter Setting range Default value Customer setting Data type SYSTEM PARAMETER Display Backlight On On Off Off 4556 Configure display backlight UNSIGNED Auto Auto Auto Key actv.
Returning Equipment For Repair ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If a control (or any part of an electronic control) is to be returned to Woodward for repair, please contact Woodward in advance to obtain a Return Authorization Number. When shipping the unit(s), attach a tag with the following information: •...
Stuttgart [+49 (0) 711 789 54-0]. They will help expedite the processing of your order through our distributors or local service facility. To expedite the repair process, contact Woodward in advance to obtain a Return Authorization Number, and arrange for issue of a purchase order for the unit(s) to be repaired. No work can be started until a purchase order is received.
+49 (0) 711 789 54-100 e-mail: stgt-info@woodward.com For assistance outside Germany, call one of the following international Woodward facilities to obtain the address and phone number of the facility nearest your location where you will be able to get information and service. Facility...
DTSC-200 - ATS Controller Engineering Services ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Woodward Industrial Controls Engineering Services offers the following after-sales support for Woodward products. For these services, you can contact us by telephone, by e-mail, or through the Woodward website. • Technical support •...
Manual 37386D DTSC-200 - ATS Controller Technical Assistance ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If you need to telephone for technical assistance, you will need to provide the following information. Please write it down here before phoning: Contact Your company ____________________________________________________ Your name _______________________________________________________ Phone number ____________________________________________________...
Page 141
Phone +49 (0) 711 789 54-0 • Fax +49 (0) 711 789 54-100 stgt-info@woodward.com Homepage http://www.woodward.com/power Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address/phone/fax/e-mail information for all locations is available on our website (www.woodward.com).