Woodward DTSC-200 Installation Manual

Woodward DTSC-200 Installation Manual

Ats controller
Hide thumbs Also See for DTSC-200:
Table of Contents

Advertisement

37385B
DTSC-200
ATS Controller
Installation
Software Version 1.0xxx
Manual 37385B

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DTSC-200 and is the answer not in the manual?

Questions and answers

Summary of Contents for Woodward DTSC-200

  • Page 1 37385B DTSC-200 ATS Controller Installation Software Version 1.0xxx Manual 37385B...
  • Page 2 Provides other helpful information that does not fall under the warning or caution categories. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
  • Page 3: Table Of Contents

    Manual 37385B DTSC-200 - ATS Controller Revision History Rev. Date Editor Changes 2013-07-03 Correction: • Pin assignment CAN-H/-L corrected on page 32. Manual: • Phone number on rear page updated 08-11-25 Minor corrections NEW 07-12-12 Release Content 1. G ..................6...
  • Page 4 Manual 37385B DTSC-200 - ATS Controller Illustrations and Tables Illustrations Figure 3-1: Housing - panel-board cutout ........................... 8 Figure 3-2: Housing - dimensions ............................... 9 Figure 3-3: Housing - drill plan ..............................11 Figure 4-1: Wiring diagram ..............................12 Figure 5-1: Power supply ................................14 Figure 5-2: Power supply - crank waveform at maximum load ....................
  • Page 5 Manual 37385B DTSC-200 - ATS Controller Tables Table 1-1: Manual - overview ..............................6 Table 3-1: Housing - panel cutout ............................... 8 Table 5-1: Conversion chart - wire size ............................ 13 Table 5-2: Power supply - terminal assignment ........................14 Table 5-3: Earth ground - terminal assignment .........................
  • Page 6: Chapter 1. General Information

    Manual 37385B DTSC-200 - ATS Controller Chapter 1. General Information Type English German DTSC-200 Series DTSC-200 - Installation this manual  37385 DTSC-200 - Configuration 37386 DTSC-200 - Operation 37387 DTSC-200 - Application 37388 DTSC-200 - Interfaces 37389 Additional Manuals...
  • Page 7: Chapter 2. Electrostatic Discharge Awareness

    CAUTION To prevent damage to electronic components caused by improper handling, read and observe the pre- cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Print- ed Circuit Boards, and Modules. © Woodward...
  • Page 8: Chapter 3. Housing

    Manual 37385B DTSC-200 - ATS Controller Chapter 3. Housing Panel Cutout ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ h' h H Figure 3-1: Housing - panel-board cutout Measure Description Tolerance Height Total 171 mm (6.73 in) Panel cutout 138 mm (5.43 in) + 1.0 mm (0.04 in) Housing dimension 136 mm (5.35 in)
  • Page 9: Dimensions

    Manual 37385B DTSC-200 - ATS Controller Dimensions ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Figure 3-2: Housing - dimensions © Woodward Page 9/41...
  • Page 10: Installation

    Manual 37385B DTSC-200 - ATS Controller Installation ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ For installation into a panel door with the fastening clamps, please proceed as follows: Panel cutout Cut out the panel according to the dimensions in Figure 3-3. Note: It is not necessary to drill the holes if the fastening clamps are used.
  • Page 11: Screw Kit Installation

    186,0 191,0 Cutout dimension: 2006-09-05 | DTSC-200 cutout+drillplan DTSC200ww-3606-ab.SKF 186 mm (+1.1 mm) x 138 mm (+1.0 mm) according to DIN 43700/IEC 61554 7.32 in (+0.045 in) x 5.43 in (+0.04 in) Unit will be mounted with 8 screws (P/N: LR02236) M4 x 6 mm, torque 0.6Nm.
  • Page 12: Chapter 4. Wiring Diagram

    LogicsManager Discrete output [R 1] freely 100 Vac configuable via LogicsManager Source 2 voltage L1 400 Vac Common (terminals 32 - 34) Subject to technical modifications. 2007-12-05 | DTSC-200 Terminal Diagram DTSCww-4907-ap.SKF Figure 4-1: Wiring diagram Page 12/41 © Woodward...
  • Page 13: Chapter 5. Connections

    Manual 37385B DTSC-200 - ATS Controller Chapter 5. Connections WARNING All technical data and ratings indicated in this chapter are not definite! Only the values indicated in Chapter 6: Technical Data on page 35 are valid! The following chart may be used to convert square millimeters [mm²] to AWG and vice versa: mm²...
  • Page 14: Power Supply

    ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Earth ground Figure 5-3: Earth ground Terminal Description Earth ground connection 2.5 mm² Table 5-3: Earth ground - terminal assignment NOTE Woodward recommends to connect this terminal to ground to comply with the EMC directives. Page 14/41 © Woodward...
  • Page 15: Voltage Measuring (Flexrange)

    DO NOT use both sets of voltage measuring inputs. The control unit will not measure voltage correctly if the 100 V and 400 V inputs are utilized simultaneously. NOTE Woodward recommends protecting the voltage measuring inputs with slow-acting fuses rated for 2 to 6 A. Voltage Measuring: Source 1...
  • Page 16: Figure 5-5: Voltage Measuring -Source 1 Pt Windings, 3Ph 4W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 1, parameter setting '3ph 4w' (3phase, 4wire) Figure 5-5: Voltage measuring -source 1 PT windings, 3ph 4w Voltage 3Ph 4W Figure 5-6: Voltage measuring -source 1 measuring inputs, 3ph 4w 3ph 4w...
  • Page 17: Figure 5-7: Voltage Measuring - Source 1 Pt Windings, 3Ph 3W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 1, parameter setting '3ph 3w' (3phase, 3wire) Figure 5-7: Voltage measuring - source 1 PT windings, 3ph 3w Voltage 3Ph 3W Figure 5-8: Voltage measuring -source 1 measuring inputs, 3ph 3w...
  • Page 18: Figure 5-9: Voltage Measuring - Source 1 Pt Windings, 1Ph 3W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 1, parameter setting '1ph 3w' (1phase, 3wire) Figure 5-9: Voltage measuring - source 1 PT windings, 1ph 3w Voltage 1Ph 3W Figure 5-10: Voltage measuring -source 1 measuring inputs, 1ph 3w...
  • Page 19: Figure 5-11: Voltage Measuring - Source 1 Pt Windings, 1Ph 2W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 1, parameter setting '1ph 2w' (1phase, 2wire) Figure 5-11: Voltage measuring - source 1 PT windings, 1ph 2w Voltage 1Ph 2W Figure 5-12: Voltage measuring -source 1 measuring inputs, 1ph 2w...
  • Page 20: Voltage Measuring: Source 2

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 2 400 Vac 400 Vac L1 / Va 100 Vac 100 Vac 400 Vac 400 Vac L2 / Vb 100 Vac 100 Vac 400 Vac 400 Vac L3 / Vc 100 Vac...
  • Page 21: Figure 5-14: Voltage Measuring - Source 2 Pt Windings, 3Ph 4W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 2, parameter setting '3ph 4w' (3phase, 4wire) Figure 5-14: Voltage measuring - source 2 PT windings, 3ph 4w Voltage 3Ph 4W Figure 5-15: Voltage measuring -source 2 measuring inputs, 3ph 4w...
  • Page 22: Figure 5-16: Voltage Measuring - Source 2 Pt Windings, 3Ph 3W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 2, parameter setting '3ph 3w' (3phase, 3wire) Figure 5-16: Voltage measuring - source 2 PT windings, 3ph 3w Voltage 3Ph 3W Figure 5-17: Voltage measuring -source 2 measuring inputs, 3ph 3w...
  • Page 23: Figure 5-18: Voltage Measuring - Source 2 Pt Windings, 1Ph 3W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 2, parameter setting '1ph 3w' (1phase, 3wire) Figure 5-18: Voltage measuring - source 2 PT windings, 1ph 3w Voltage 1Ph 3W Figure 5-19: Voltage measuring -source 2 measuring inputs, 1ph 3w...
  • Page 24: Figure 5-20: Voltage Measuring - Source 2 Pt Windings, 1Ph 2W

    Manual 37385B DTSC-200 - ATS Controller Voltage Measuring: Source 2, parameter setting '1ph 2w' (1phase, 2wire) Figure 5-20: Voltage measuring - source 2 PT windings, 1ph 2w Voltage 1Ph 2W Figure 5-21: Voltage measuring -source 2 measuring inputs, 1ph 2w...
  • Page 25: Current Measuring

    Manual 37385B DTSC-200 - ATS Controller Current Measuring ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ CAUTION Before disconnecting the current transformer/CT secondary connections or the connections of the current transformer/CT at the device, ensure that the current transformer/CT is short-circuited. Load NOTE Please connect the wires of the current transformer "L (x)" as near as possible to the unit.
  • Page 26: Figure 5-23: Current Measuring - Load, L1 L2 L3

    Manual 37385B DTSC-200 - ATS Controller Current Measuring: Load, parameter setting 'L1 L2 Gen L1 Gen L2 Gen L3 Ground Figure 5-23: Current measuring - load, L1 L2 L3 Wiring terminals Notes L1 L2 L3 DTSC-200 Phase Table 5-15: Current measuring - terminal assignment - load, L1 L2 L3...
  • Page 27: Discrete Inputs

    Manual 37385B DTSC-200 - ATS Controller Discrete Inputs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Discrete Inputs: Bipolar Signals The discrete inputs are electrically isolated allowing for a bipolar connection. The discrete inputs are able to han- dle positive or negative signals. NOTE All discrete inputs must use the same polarity, either positive or negative signals, due to the common ground.
  • Page 28: Figure 5-26: Discrete Inputs - Alarm/Control Input - Negative Signal

    Manual 37385B DTSC-200 - ATS Controller Power suppply + (8 to 40 Vdc) Discrete input 1 Power supply - Discrete input 2 Power supply - Discrete input 3 Power supply - Discrete input 4 Power supply - Discrete input 5...
  • Page 29: Discrete Inputs: Operation Logic

    Manual 37385B DTSC-200 - ATS Controller Discrete Inputs: Operation Logic Discrete inputs may be configured to normally open (N.O.) or normally closed (N.C.) states. In the state N.O., no potential is present during normal operation; if a control operation is performed, the input is energized. In the state N.C., a potential is continuously present during normal operation;...
  • Page 30: Discrete Outputs (Control Outputs And Logicsmanager)

    Manual 37385B DTSC-200 - ATS Controller Discrete Outputs (Control Outputs And LogicsManager) ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ max. 250 Vac/dc Relay output external device external device Relay output external device Figure 5-28: Discrete outputs Terminal Description Term. Com. Form A, common contact Type ...
  • Page 31: Interfaces

    Manual 37385B DTSC-200 - ATS Controller Interfaces ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ RS-485 Modbus RTU Slave 5 6 7 8 Figure 5-29: Interface Terminal Description RS-485-A RS-485-B RS-485-A' RS-485-B' RS-485, Modbus RTU Slave (TxD-) (TxD+) (RxD-) (RxD+) Table 5-19: RS-485 Modbus interface - terminal assignment...
  • Page 32: Can Bus (Flexcan)

    • Baud rate to high for wiring length • The CAN bus cable is co-routed with power cables Woodward recommends the use of twisted-pair cables for the CAN bus (i.e.: Lappkabel Unitronic LIYCY (TP) 2×2×0.25, UNITRONIC-Bus LD 2×2×0.22). Page 32/41...
  • Page 33: Table 5-21: Maximum Can Bus Length

    Manual 37385B DTSC-200 - ATS Controller Maximum CAN bus Length The maximum length of the communication bus wiring is dependent on the configured Baud rate. Refer to Table 5-21 for the maximum bus length (Source: CANopen; Holger Zeltwanger (Hrsg.); 2001 VDE VERLAG GMBH, Berlin und Offenbach;...
  • Page 34: Dpc - Direct Configuration Cable

    Manual 37385B DTSC-200 - ATS Controller DPC - Direct Configuration Cable The easYgen provides a configuration interface for connecting a computer via the DPC (direct configuration ca- ble). The configuration interface is the RJ45 socket on the side of the easYgen housing.
  • Page 35: Chapter 6. Technical Data

    Manual 37385B DTSC-200 - ATS Controller Chapter 6. Technical Data Nameplate ------------------------------------------------------------------------------------------------------ Serial number (numerical) Date of production (YYMM) Serial number (Barcode) Item number Item revision number Details Technical data Type Description (short) Type Description (long) UL sign Measuring values, voltages ------------------------------------------------------------------------------ /∆...
  • Page 36 Manual 37385B DTSC-200 - ATS Controller Discrete inputs ---------------------------------------------------------------------------------------- isolated Input range (V ) ........Rated voltage 12/24 Vdc (8 to 40 Vdc) Cont, digital input Input resistance....................approx. 20 kΩ Discrete outputs Group A [R 1-4] ----------------------------------------------------------------- isolated Contact material ......................AgCdO...
  • Page 37 Manual 37385B DTSC-200 - ATS Controller Housing ---------------------------------------------------------------------------------------------------------- Type ........................easYpack Dimensions (W × H × D) ........219 × 171 × 61 mm (8.6 × 6.7 × 2.4 in) Front cutout (W × H) ............... 186 [+1.1] × 138 [+1.0] mm Material..................
  • Page 38: Chapter 7. Environmental Data

    Manual 37385B DTSC-200 - ATS Controller Chapter 7. Environmental Data Dynamics -------------------------------------------------------------------------------------------------------- Frequency Range – Sine Sweep ..............5Hz to 150Hz Acceleration ......................4G Frequency Range - Random ................10Hz to 500Hz Power Density ................... 0,015G²/Hz RMS Value ....................1,04 Grms Standards ..........................
  • Page 39: Chapter 8. Accuracy

    Manual 37385B DTSC-200 - ATS Controller Chapter 8. Accuracy Measuring value Display Accuracy Notes Frequency Source 1 15.0 to 85.0 Hz 0.1 % Source 2 40.0 to 85.0 Hz 0.1 % Voltage Source 1 0 to 650 kV Transformer ratio selectable...
  • Page 40: Appendix A. Recommended Power Supply Units

    Manual 37385B DTSC-200 - ATS Controller Appendix A. Recommended Power Supply Units Woodward recommends the use of the following external power supply units: • Mean Well: DR-30-24 • Phoenix Contact: MINI-PS-100-240AC/24DC/1 An external buffered power supply solution may be achieved using the following devices:...
  • Page 41 Phone +49 (0) 711 789 54-510 • Fax +49 (0) 711 789 54-101 stgt-info@woodward.com Homepage http://www.woodward.com Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address/phone/fax/e-mail information for all locations is available on our website (www.woodward.com).

Table of Contents

Save PDF