Insulation Resistance Measurements; Main Terminal Box Options; Delivery Without Main Terminal Box; Insulation Distances Of Main Power Connections - ABB AMA Manual

High voltage process performance motors
Table of Contents

Advertisement

Manual for High Voltage Process Performance Motors

4.2.3 Insulation resistance measurements

4.2.4 Main terminal box options

4.2.4.1 Delivery without main terminal box

4.2.5 Insulation distances of main power connections

32 - Mechanical and Electrical Connections
If the secondary circuit of the current transformer is extended, make sure that it does not
become open-circuited in use
Before a machine is started up for the first time, after a long period of standstill or within the
scope of general maintenance work, the insulation resistance of the machine must be measured,
see Chapter 7.6.4 Insulation resistance test.
The inside of the main terminal box must be free from dirt, moisture and foreign debris. The box
itself, cable glands, and unused cable entrance holes must be closed in a dust- and watertight
manner.
The main terminal box is equipped with a drain plug at the lowest part of the box. The plug
should be in open position, i.e. half of the plug is inside and half of the plug is outside, during
transportation and storage. During operation of the machine, the plug should be kept in shut
position but opened from time to time. If the box is turned after delivery the drain plug function
must be checked, and possibly re-positioned at the lowest part of the box.
Some main terminal boxes can be turned in 90 degrees steps. Before turning, check that the
length of the cables between the stator winding and the terminal box is sufficient.
If the machine is delivered without a main terminal box, the stator connection cables have to be
covered with earthed protective structure before commissioning. The structure must have the
same or higher enclosure classification and hazardous area certifications as the machine.
To avoid cable failure, stator connection cables must be shortened to minimize free movement
of the cables. The supplier of the terminal arrangement is responsible for ensuring that adequate
stator connection cable supports are used. The stator connection cable arrangement has to be
spacious in order to avoid overheating of the cables. Stator connection cables must not touch
sharp corners. The minimum bending radius of stator connection cable is 6 times the cable outer
diameter.
The connections of the main power cables must be designed to withstand demanding operation
conditions where the insulators can be subjected to dirt, humidity and surge voltages. In order to
ensure lasting and trouble-free running, it is therefore important that the length of the insulation
and creepage distances are sufficient. The minimum insulation and creepage distances should be
equal or exceed demands set by:
Local requirements
Standards
Classification rules
Hazardous area classification.
The insulation and creepage distances apply both for insulation distances between two different
phases, and for insulation distances between one phase and earth. The air insulation distance is
3BFP 000 063 R0101 REV D