Platform Base; Surge Protection And Grounding System - Huawei FusionPower6000 Product Description

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Product Description
Figure 4-23 PAD
The PAD is a capacitive screen which supports multi-touch.
PAD screen size is 8–12 inches. The PAD uses Android 4.0 or later, and has a
memory of 2 GB or more.
If a non-standard PAD is selected, confirm with Huawei engineers.

4.3 Platform Base

The platform base of the PowerPOD is welded by I-steel and angle steel profiles
to meet the requirements for installing PowerPOD equipment and for
transporting, hoisting, and installing the entire PowerPOD.
Figure 4-24 Platform base
(1) Ground point
(4) Ribbed slab for fixing
binding tapes

4.4 Surge Protection and Grounding System

Surge Protection for Power Ports
Issue 02 (2021-06-30)
NO TE
For outdoor 10 kV cable trench digging and home access, the indoor 10 kV
medium-voltage cabinet must be configured with at least one level-1
common-mode surge protector. 17/45 kV (8/20 μs) is recommended.
The low-voltage AC output downstream device must meet class D surge
protection requirements of 5 kA (8/20 μs).
Copyright © Huawei Technologies Co., Ltd.
(2) Removable lifting eye
(5) L-shaped fastener
4 Product Overview
(3) Corner fitting
54