Display
Error type
L-20
Flame error
L-21
Flame error
L-22
Flame error
L-25
Sensor error
L-26
Sensor error
L-27 to 31 Internal error
L-32
Sensor error
L-33 to 38 Internal error
L-42
Flue temperature
error
L-43
Overheating
9.2 Temporary errors
The table below describes the temporary errors that can
occur. These will disappear automatically after the cause
has been resolved.
Display
Error type
E-00 to 04
Internal error
E-05
Overheating
E-06 to 13
Internal error
E-14
Flame error
E-15 to 20
Internal error
E-21 and 22
Heat exchanger
sensor error
E-23 and 24
Flue sensor error Flue sensor not detected
E-27 and 28
Heat exchanger
sensor error
E-30 and 31
Flue sensor error Flue sensor short-circuit
E-34
Reset button
error
E-36
Overheating
E-38 and 39
Heat exchanger
sensor error
E-47 and 48
Heat exchanger
sensor error
E-49 to 64
Internal error
E-65
Voltage too low
E-66
Voltage too high
E-67
Pressure switch
error
E-68
Flue temperature
error
E-69
Configuration
error
20
Description
Case #
Flame detected after
15
closing the gas valve
Flame detected after
16
closing the gas valve
Flame failure during
5
burning
Heat exchange sensor
4
failure
Flue sensor failure
4
Internal error
13
Heat exchange sensor
4
failure
Internal error
13
Too many flue temperature
3
errors
Heat exchange sensor is
3
overheated too often
Description
Case #
Internal error
13
Heat exchange sensor is
3
overheated
Internal error
13
16
Flame detected when there
shouldn't be one
Internal error
13
Heat exchanger sensor not
4
detected
4
Heat exchanger sensor
4
short-circuit
4
Too many reset actions in a
9
short timespan
Heat exchange sensor is
3
overheated
Heat exchanger sensor not
4
detected
Heat exchange sensor
4
short-circuit
Internal error
13
Supply voltage is too low
for over 1 minute
Supply voltage is too high
for over 1 minute
Too many pressure switch
11
errors
Flue sensor is overheated
3
Heater configuration error 19
9.3 Warnings
The table below describes the temporary warnings that
can occur. The heater may still be working, or stops until
the cause has been resolved.
Display
Error type
A-02
Configuration
error
A-07
Overheating
A-08
Overheating
9.4 Instructions
After identifying the problem, use the Case number to find
the possible cause in this paragraph.
Case 1: Flame lasts only 5 seconds after ignition.
•
The flame is not detected:
– Check the ignition/ionisation cable and the
electrode. The cable should have a resistance
of 1 kΩ.
•
The air heater is not earthed properly.
•
The circuit board is defective.
Case 2: No flame after ignition.
•
There is not enough gas pressure.
•
The gas mixture is too poor:
– Adjust the gas valve (see §8.1).
•
The gas valve does not open:
– During ignition, check for a 230 V voltage on
the valve.
•
Check if the ignition electrode sparks. If not:
– Check the cable and electrode and replace
them when damaged.
– Check the burner control unit and replace it
when it does not give a spark output.
Case 3: Heat exchange sensor or flue sensor is overheated.
•
Check if the connectors J12 and J6 are plugged in
correctly and if the connection J12[1-4] (optional
overheating protection) is closed.
•
Check if the system fan supplies enough air.
•
Check the settings of the gas valve. The heater may
be overfired. If so:
– Adjust the burner pressure.
Case 4: Heat exchange sensor or flue sensor not detected,
or short circuit.
NOTICE
L-25 refers to the heat exchange sensor. L-26
refers to the flue sensor, if applicable.
Description
Case #
Heater configuration error
19
Heat exchange sensor is
3
almost overheated
Flue sensor is almost
3
overheated