Testing Binary Inputs - ABB Relion REX640 User Manual

Bio-tester
Hide thumbs Also See for Relion REX640:
Table of Contents

Advertisement

Section 4
BIO-Tester Relion® REX640
4.5.4
26
paths within the menu structure, is provided in a collectively grouped and visualized
format on the Testing and Commissioning pages found on the top bar menu.
Some of the Testing and Commissioning pages require the relay to be
set in test mode.
GUID-1ADCE271-EB04-4FFB-B703-268B42286FD0 V1 EN
Figure 12:
Home page for Testing and Commissioning pages

Testing binary inputs

The BI input voltage circuit is protected against binary input short circuits. For
example, if binary inputs are damaged and shorted, the BI input voltage circuit detects
the faulty condition, activates Error mode and the red Error LED lights up.
Table 6:
Binary input error indication
LED
When binary inputs are tested one by one, the faulty binary input is the one that
activates the Error LED. All the other binary inputs that were already activated via
BIO-Tester return to the deactivate state (OFF state) after the activation of the Error
LED.
Color
Off
Red
2NGA000105 B
Decsription
-
Activated
BIO-Tester Relion® REX640
User Manual