Siemens SIMATIC NET Installation Manual

Hide thumbs Also See for SIMATIC NET:

Advertisement

Installation Manual
SIMATIC NET
Rugged Ethernet Switches
RUGGEDCOM RS900F
Edition
04/2021
https://www.siemens.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC NET

  • Page 1 Installation Manual SIMATIC NET Rugged Ethernet Switches RUGGEDCOM RS900F Edition 04/2021 https://www.siemens.com...
  • Page 2 Preface Introduction Installing the Device SIMATIC NET Device Management Rugged Ethernet Switches RUGGEDCOM RS900F Communication Ports Technical Specifications Installation Manual Certification 04/2021 C79000-G8976-1350-07...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Table Of Contents

    Accessing Documentation ....................... v Registered Trademarks ......................v Warranty ..........................v Training ..........................vi Customer Support ........................vi Contacting Siemens ....................... vii Introduction ........................... 1 Feature Highlights ....................1 Description ......................2 Required Tools and Materials ................. 3 Decommissioning and Disposal ................3 Cabling Recommendations ..................
  • Page 5 Table of Contents Power Supply Specifications ................27 Failsafe Alarm Relay Specifications ..............28 Supported Networking Standards ................ 28 Copper Ethernet Port Specifications ..............28 Fiber Optic Ethernet Port Specifications ............... 29 Operating Environment ..................30 Mechanical Specifications ..................30 Dimension Drawings ...................
  • Page 6: Preface

    Warranty Siemens warrants this product for a period of five (5) years from the date of purchase, conditional upon the return to factory for maintenance during the warranty term. This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void.
  • Page 7: Training

    Siemens Sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, contact Siemens Customer Support through any of the following methods: Online Visit http://www.siemens.com/automation/support-request...
  • Page 8: Contacting Siemens

    Preface Contacting Siemens • Contact a local Siemens representative from Sales, Technical Support, Training, etc. • Ask questions or share knowledge with fellow Siemens customers and the support community Contacting Siemens Address Siemens AG Industry Sector 300 Applewood Crescent Concord, Ontario...
  • Page 9 Preface Contacting Siemens viii RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 10: Introduction

    Introduction The RUGGEDCOM RS900F is a 9-port utility-grade, fully managed Ethernet switch specifically designed to operate reliably in electrically harsh and climatically demanding environments. The RUGGEDCOM RS900F provides a high level of immunity to electromagnetic interference and heavy electrical surges typical of environments found on plant floors and curb-side traffic control cabinets.
  • Page 11: Description

    Introduction 1.2 Description • 20 AWG Galvanized Steel • DIN or panel mounting options provide secure mechanical reliability • [Optional] Conformal coated printed circuit boards Power Supply • Fully integrated power supply • Universal high-voltage range: • 125-250 VDC or 100-240 VAC (Hazardous Environments) •...
  • Page 12: Required Tools And Materials

    Introduction 1.3 Required Tools and Materials Power Supply Terminal Block Figure 1.1 RUGGEDCOM RS900F POWER LED Illuminates green during boot up and when power is supplied to the device. ALARM LED Illuminates red when an alarm condition exists. Console Port The serial console port is for interfacing directly with the device and accessing initial management functions.
  • Page 13: Cabling Recommendations

    Siemens also does not recommend using copper Ethernet ports to interface with devices in the field across distances that could produce high levels of ground potential rise (i.e. greater than 2500 V), during line-to-ground fault conditions.
  • Page 14 NOTICE Worn, damaged or missing seals must be replaced immediately. Replacement seals are available for purchase from Siemens. For more information, contact a Siemens Sales representative. There are three ways to determine if a security seal has been tampered with: •...
  • Page 15 Introduction 1.6 Tamper-Evident Security Seals RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 16: Installing The Device

    This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. Changes or modifications not expressly approved by Siemens AG could invalidate specifications, test results, and agency approvals, and void the user's authority to operate the equipment.
  • Page 17: General Procedure

    Visually inspect each item in the package for any physical damage. Verify all items are included. Note If any item is missing or damaged, contact Siemens for assistance. Installing the Device in Hazardous Locations The RUGGEDCOM RS900F is designed to comply with the safety standards for Class I, Division 2, Zone 2 hazardous locations where concentrations of flammable gases, vapors or liquids may be present, as opposed to normal operating environments.
  • Page 18: Mounting The Device

    Installing the Device 2.4 Mounting the Device • The equipment shall be installed in an enclosure that is considered to be not accessible in normal operation without the use of a tool providing a degree of protection of not less than IP54 according to CSA/UL/IEC/EN 60079-0 and CSA/ UL/IEC/EN 60079-15.
  • Page 19: Mounting The Device On A Din Rail

    Installing the Device 2.4.1 Mounting the Device on a DIN Rail Note Heat generated by the device is channeled outwards from the enclosure. As such, it is recommended that 2.5 cm (1 in) of space be maintained on all open sides of the device to allow for some convectional airflow.
  • Page 20 Installing the Device 2.4.1 Mounting the Device on a DIN Rail Mounting the Device To mount the device to a DIN rail, do the following: Hook the top teeth of the adapter onto the DIN rail. Note The adapter features a sliding release with a slot at the bottom for a flathead screwdriver.
  • Page 21: Mounting The Device To A Panel

    Installing the Device 2.4.2 Mounting the Device to a Panel Removing the Device To remove the device from a DIN rail, do the following: Insert a flathead screwdriver into the slot of the sliding release and move it down. DIN Rail DIN Rail Adapter Figure 2.3 Removing the Device from a DIN Rail...
  • Page 22: Connecting The Failsafe Alarm Relay

    Installing the Device 2.5 Connecting the Failsafe Alarm Relay Place the device against the panel and align the adapters with the mounting holes. Screw (M3.5 or #6-32) Panel Mount Adapter Figure 2.4 Panel Mounting Secure the adapters to the panel with M3.5 or #6-32 screws. Connecting the Failsafe Alarm Relay The failsafe relay can be configured to latch based on alarm conditions.
  • Page 23: Connecting Power

    Installing the Device 2.6 Connecting Power Connect a failsafe device to the terminal block. Normally Closed Common Normally Open Figure 2.5 Failsafe Alarm Relay Wiring Connecting Power The RUGGEDCOM RS900F supports power input from a single high AC/DC or low DC power supply. Note •...
  • Page 24: Connecting High Ac/Dc Power

    Installing the Device 2.6.1 Connecting High AC/DC Power 2.6.1 Connecting High AC/DC Power To connect a high AC/DC power supply to the device, do the following: NOTICE Electrical hazard – risk of damage to equipment Do not connect AC power cables to terminals for DC power. Damage to the power supply may occur.
  • Page 25 Installing the Device 2.6.1 Connecting High AC/DC Power Connect the positive wire from the power source to the positive/live (+/L) terminal on the terminal block. Positive/Live (+/L) Terminal Negative/Neutral (-/N) Terminal Surge Ground Terminal Braided Ground Cable Figure 2.6 Terminal Block Wiring RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 26: Connecting Low Dc Power

    Installing the Device 2.6.2 Connecting Low DC Power ± ± ± ± Positive Terminal Negative Terminal Surge Ground Terminal Braided Ground Cable Figure 2.7 Terminal Block Wiring – Dual DC Power Supply Inputs Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
  • Page 27 Installing the Device 2.6.2 Connecting Low DC Power Connect the positive wire from the power source to the positive terminal on the terminal block. ± ± Positive Terminal Negative Terminal Surge Ground Terminal Braided Ground Cable Figure 2.8 Terminal Block Wiring – Single DC Power Supply Inputs Connect the negative wire from the power source to the negative terminal on the terminal block.
  • Page 28 Installing the Device 2.6.2 Connecting Low DC Power [Optional] If a redundant connection is required, repeat Step 2 Step 3 connect the secondary power inputs. ± ± ± ± Positive Terminal Negative Terminal Surge Ground Terminal Braided Ground Cable Figure 2.9 Terminal Block Wiring – Dual DC Power Supply Inputs Using a braided wire or other appropriate grounding wire, connect the surge ground terminal to the chassis ground connection.
  • Page 29 Installing the Device 2.6.2 Connecting Low DC Power RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 30: Device Management

    Device Management This section describes how to connect to and manage the device. Connecting to the Device The following describes the various methods for accessing the RUGGEDCOM RS900F console and Web interfaces on the device. For more detailed instructions, refer to the RUGGEDCOM ROS Configuration Manual for the RUGGEDCOM RS900F.
  • Page 31: Configuring The Device

    Device Management 3.2 Configuring the Device The serial console port implements RS232 DCE (Data Communication Equipment) on a DB9 connector. The following is the pin-out for the port:   Name Description Reserved (Do Not Connect) Transmit Data Receive Data Reserved (Do Not Connect) Signal Ground Reserved (Do Not Connect) Reserved (Do Not Connect)
  • Page 32: Communication Ports

    Communication Ports The RUGGEDCOM RS900F can be equipped with various types of communication ports to enhance its abilities and performance. Ports 1 to 6 Ports 7 and 8 Port 9 Figure 4.1 Port Assignment Port Type 1 to 6 Copper Ethernet Ports (10/100Base-TX) 7 and 8 Copper (10/100Base-TX) or Fiber Optic (100Base-FX) Ethernet Ports Fast Ethernet Port (10/100Base-TX or 100Base-FX)
  • Page 33 Communication Ports 4.1 Copper Ethernet Ports WARNING Electric shock hazard – risk of serious personal injury and/or equipment interference When shielded cables are used, make sure the shielded cables do not form a ground loop via the shield wire and the RJ45 receptacles at either end. Ground loops can cause excessive noise and interference, but more importantly, create a potential shock hazard that can result in serious injury.
  • Page 34: Fiber Optic Ethernet Ports

    Communication Ports 4.2 Fiber Optic Ethernet Ports Name Description Transmit Data- Reserved (Do Not Connect) Reserved (Do Not Connect) Specifications For specifications on the available copper Ethernet ports, refer to "Copper Ethernet Port Specifications (Page 28)". Fiber Optic Ethernet Ports Fiber optic Ethernet ports are available with either MTRJ (Mechanical Transfer Registered Jack), LC (Lucent Connector), SC (Standard or Subscriber Connector) or ST (Straight Tip) connectors.
  • Page 35 Communication Ports 4.2 Fiber Optic Ethernet Ports State Description No link detected Specifications For specifications on the available fiber optic Ethernet ports, refer to "Fiber Optic Ethernet Port Specifications (Page 29)". RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 36: Technical Specifications

    Technical Specifications This section provides important technical specifications related to the device. Power Supply Specifications Note When determining cable lengths, make sure the minimum input voltage for the power supply is provided at the power source. Hazardous Environments Power Input Range Internal Isolation Maximum Power...
  • Page 37: Failsafe Alarm Relay Specifications

    Technical Specifications 5.2 Failsafe Alarm Relay Specifications Failsafe Alarm Relay Specifications Hazardous Environments Maximum Switching Voltage Rated Isolation Switching Current 30 VDC 1500 V for 1 minute 80 VDC 0.3 A 30 VAC Non-Hazardous Environment Maximum Switching Voltage Rated Isolation Switching Current 30 VDC 2 A, 60 W...
  • Page 38: Fiber Optic Ethernet Port Specifications

    3 dBm. To convert from peak to average, subtract 3 dBm. • Maximum segment length is greatly dependent on factors such as fiber quality, and the number of patches and splices. Consult a Siemens sales associate when determining maximum segment distances. Tx (dBm)
  • Page 39: Operating Environment

    Technical Specifications 5.6 Operating Environment Operating Environment The RUGGEDCOM RS900F is rated to operate under the following environmental conditions. Ambient Operating -40 to 85 °C (-40 to 185 °F) Temperature Ambient Storage Temperature -40 to 85 °C (-40 to 185 °F) Ambient Relative Humidity 5% to 95% Maximum Altitude...
  • Page 40 Technical Specifications 5.8 Dimension Drawings 65.3 116.59 7.87 Figure 5.1 Overall Dimensions RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 41 Technical Specifications 5.8 Dimension Drawings 130.2 13.64 101.6 11.2 78.74 120.65 Figure 5.2 Panel and DIN Rail Mount Dimensions RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 42: Certification

    Certification The RUGGEDCOM RS900F device has been thoroughly tested to guarantee its conformance with recognized standards and has received approval from recognized regulatory agencies. Approvals This section details the standards to which the RUGGEDCOM RS900F complies. 6.1.1 This device meets the requirements of the following Canadian Standards Association (CSA) standards under certificate 16.70065161: •...
  • Page 43: Csa/Sira

    Explosive Atmospheres – Part 15: Equipment Protection by Type of Protection "n" 6.1.3 European Union (EU) This device is declared by Siemens AG to comply with essential requirements and other relevant provisions of the following EU directives: • EN 62368-1 Information Technology Equipment –...
  • Page 44: Fcc

    Methods of Measurement The device is marked with a CE marking and can be used throughout the European community. A copy of the CE Declaration of Conformity is available from Siemens AG. For contact information, refer to "Contacting Siemens (Page vii)".
  • Page 45: Ised

    Title 21 Code of Federal Regulations (CFR) – Chapter I – Sub-chapter J – Radiological Health 6.1.6 ISED This device is declared by Siemens AG to meet the requirements of the following ISED (Innovation Science and Economic Development Canada) standard: • CAN ICES-3 (A)/NMB-3 (A) 6.1.7...
  • Page 46: Other Approvals

    Certification 6.1.10 Other Approvals 6.1.10 Other Approvals This device meets the requirements of the following additional standards: • IEEE 1613 IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric Power Substations • IEC 61000-6-2 Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments •...
  • Page 47 Certification 6.2 EMC and Environmental Type Tests Test Description Test Levels Severity Levels DC Power 10 V Ports AC Power 10 V Ports Earth 10 V Ground Ports Magnetic Field Enclosure 40 A/m Continuous   61000-4-8 Ports 1000 A/m for 1 s Voltage Dips and Interrupts AC Power 100% for 5 Periods...
  • Page 48 Certification 6.2 EMC and Environmental Type Tests EMC Immunity Type Tests per IEEE 1613 Note The RUGGEDCOM RS900F meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires error-free and interrupted communications.
  • Page 49 Certification 6.2 EMC and Environmental Type Tests RUGGEDCOM RS900F Installation Manual, 04/2021, C79000-G8976-1350-07...
  • Page 50 Further Information Siemens RUGGEDCOM https://www.siemens.com/ruggedcom Industry Online Support (service and support) https://support.industry.siemens.com Industry Mall https://mall.industry.siemens.com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY...

This manual is also suitable for:

Ruggedcom rs900fSimatic net ruggedcom rs900f