Checking The Insulation Of The Dc Cabling - ABB ACS880-7107LC DC Hardware Manual

Hide thumbs Also See for ACS880-7107LC DC:
Table of Contents

Advertisement

5. Measure that the installation is de-energized. Use a quality voltage tester. If the
measurement requires removal or disassembly of shrouding or other cabinet structures,
obey the local laws and regulations applicable to live working (including – but not limited
to – electric shock and arc protection).
• Before and after measuring the installation, verify the operation of the voltage tester
on a known voltage source.
• Make sure that the voltage between the drive input power terminals (L1, L2, L3) and
the grounding (PE) busbar is zero.
• Make sure that the voltage between the drive output terminals (T1/U, T2/V, T3/W)
and the grounding (PE) busbar is zero.
Important! Repeat the measurement also with the DC voltage setting of the tester.
Measure between each phase and ground. There is a risk of dangerous DC voltage
charging due to leakage capacitances of the motor circuit. This voltage can remain
charged even long time after the drive power off. The measurement discharges the
voltage.
• Make sure that the voltage between the drive DC terminals (UDC+ and UDC-) and
the grounding (PE) terminal is zero. In cabinet-built drives, measure between the
drive DC busbars (+ and -) and the grounding (PE) busbar.
WARNING!
The busbars inside the cabinet of liquid-cooled drives are partially coated.
Measurements made through the coating are potentially unreliable, so only
measure at uncoated portions. Note that the coating does not constitute a safe
or touch-proof insulation.
6. Install temporary grounding as required by the local regulations.
7. Ask for a permit to work from the person in control of the electrical installation work.

Checking the insulation of the DC cabling

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur. If you are not a qualified electrical
professional, do not do installation or maintenance work.
WARNING!
Open the DC switch/disconnector [Q11] of each unit.
WARNING!
Do not do any voltage withstand or insulation resistance tests on any part of the
drive as testing can damage the drive. Every drive has been tested for insulation
between the main circuit and the chassis at the factory. Also, there are
voltage-limiting circuits inside the drive which cut down the testing voltage
automatically.
Check the DC cabling as follows:
Electrical installation 29