28 Electrical installation
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
Go through these steps before you begin any installation or maintenance work.
1. Clearly identify the work location and equipment.
2. Disconnect all possible voltage sources. Make sure that re-connection is not possible.
Lock out and tag out.
• Open the main disconnecting device of the drive.
• Open the charging switch if present.
• Open the disconnector of the supply transformer. (The main disconnecting device in
the drive cabinet does not disconnect the voltage from the AC input power busbars
of the drive cabinet.)
• If the drive is equipped with a DC/DC converter unit (optional) or a DC feeder unit
(optional): Open the DC switch-disconnector ([Q11], option +F286 or +F290) of the
unit. Open the disconnecting device of the energy storage connected to the unit
(outside the drive cabinet).
• Open the auxiliary voltage switch-disconnector (if present), and all other possible
disconnecting devices that isolate the drive from dangerous voltage sources.
• In the liquid cooling unit (if present), open the switch-disconnector of the cooling
pumps.
• If you have a permanent magnet motor connected to the drive, disconnect the motor
from the drive with a safety switch or by other means.
• Disconnect all dangerous external voltages from the control circuits.
• After you disconnect power from the drive, always wait 5 minutes to let the intermediate
circuit capacitors discharge before you continue.
3. Protect any other energized parts in the work location against contact.
4. Take special precautions when close to bare conductors.