EDS - TECHNICAL INSTRUCTIONS END TO END (BARRIER) OPTICAL BEAM LINEAR SMOKE DETECTOR RK100-B RK100-BS with Laser Pointer BLP-100 TECHNICAL MANUAL TECHNICAL INSTRUCTIONS FOR INSTALLATION, SETUP AND MAINTENANCE...
EDS - TECHNICAL INSTRUCTIONS NOTE - the version -S detectors (RK100-BS) are not equipped with the Turbulence detection circuit. Therefore no items related to this function are included. Keep in mind this indication while reading and using these instructions. CHAPTER INDEX...
Page 3
The procedure below is intended for trained personell with previous experience in installing EDS Beam Smoke Detectors RK100-B and RK100-BS. If you don’t have the needed experience please refer to the standard installation procedure of this manual. On our site www.eds.eu is available a video with instructions for installing the RK detectors.
In extraeuropean countries you must respect the relevant internatiobnal and national standards. 3 - INSTALLATION 3.1 - For the installation of the RK100-B(S) we suggest to use, besides the normal tools (drill, expansion plugs, etc), also the following elements: •...
EDS - TECHNICAL INSTRUCTIONS 4 - CABLE CONNECTIONS 4.1 - the low detector’s power consumption (20 mA with normally open alarm relay contact (NO) and 30 mA with normally closed alarm relay contact (NC), allows to use small size sections cables. We suggest to use a shielded cable with 8 conductors + shield ( 2x0,75 mmq for power conductors + 6x0,22 mmq for the signal conductors) for a distance up to 1 Km.
6 - OPERATION 6.1 - the RK100-B detector is equipped with 2 circuits for detection of the smoke produced by a fire, but the -S versions only have the obscuration circuit. • Obscuration - circuit sensitive to Obscuration. This circuit bases its operation on the attenuation of the infrared beam intensity, along the optical path between the transmitter and the receiver, caused by smoke presence.
EDS - TECHNICAL INSTRUCTIONS 7.5 - Acting on V1-V2-V3 (fig.9) bolts of optical orientation of the transmitter TX (see manual), so that the Laser beam impinges on the lens of the receiver RX on the opposite wall. When this happens the receiver lens has an intense red light spot.
Page 8
EDS - TECHNICAL INSTRUCTIONS 8.9 - if available, connect a 5V fullscale Multimeter between the SIG terminal and the negative power supply one and read the analog output signal. Instead of the Multimeter it is possible to use the STS01 meter (optional - fig. 11). If the output...
Page 9
EDS - TECHNICAL INSTRUCTIONS • if the signal in the range 0,5-1 V the Red led performs 1 flash, remains off for 2 seconds and then it repeats the sequence • if signal is among 1-1,5 V the Blue led flashes once, remains off for 2 seconds and then it repeats the sequence •...
EDS - TECHNICAL INSTRUCTIONS 9 - SETUP OF THE TURBULENCE - (HEAT) CIRCUIT (not relevant for -S version) 9.1 - The RK100B detector is equipped with a special additional circuit for the detection of air Turbulence (heat). This circuit is independent from the classic Obscuration one and in particular situations it can be used to increase the performan- ce of the detector.
After around 30 seconds, the fault output should be activated. 12 - ALARM MEMORY AND CONFIGURATION DATA 12.1 - the receiver of the RK100-B(S) is equipped with alarm Memory that can be activated / deactivated with the JP5 jumper (fig.9): •...
EDS - TECHNICAL INSTRUCTIONS 14.2 - verification of the circuit sensitive to Turbulence (if present). Place and remove an opaque screen in front of the RX several times with the following sequence (dark / light) and selecting the corresponding sensitivity with SW1 selector: •...
Page 19
JP4 must be in position 1-2 to have the contact closed because the fault relay is normally activated. The RK100-B(S) detector is normally factory preset with closed NC contacts. For the alarm relay the indication of JP2 is valid if JP7 is in OFF position JP5 - jumper to activate the alarm memory function or to deactivate such function (to get the auto Reset of the detector) •...
Page 20
EDS - TECHNICAL INSTRUCTIONS TRANSMITTER INSIDE PARTS SW3 - selector for the regulation of the transmitter power (TX) - power increases from 1 to 4. Maximum power in the position 4 and mimimum in position 1. DS1653 fig.10 POWER RECEIVER INSIDE PARTWITH STS-01 METER...
Page 21
FAULT relay contact contatto relè TURBOLENZA TERMINAL BLOCK OF TURBULENCE relay contact THE RECEIVER fig.13 contatto relè d'ALLARME ALARM relay contact alimentazione 11-30 Vcc supply voltage 11-30 Vcc NOTE On our website www.eds.eu is available on download section the Eds_installation guide.pdf...
Page 22
The turbulence relay, if not necessary, can be left unused. The fault output is the one from the NC contact of the fault relay of RK100-B. The values of the resistances of Alarm and End of Line will be indicated by the control panel manufacturer.
Page 23
EDS - TECHNICAL INSTRUCTIONS ACCESSORIES FOR OPTICAL BEAM SMOKE DETECTORS RK90R/S - RK100R/S - RK100/200B/S SUP - 90 Adjustable bracket for RK90R detector. It allows the installation of the detector in angular positions. It is very useful for installations in museum halls, picture galleries, churches, etc.
Page 24
4 - Name, registered trade name or registered trademark and contact address of the manufacturer as required pursuant to article 11(5) : EDS srl , Via Cà Nova Zampieri 6, San Giovanni Lupatoto (Verona) , 37057, Italy 5 - Where applicable, name and contract address of the authorised representative whose mandate covers the tasks specified in article 12(2) : Not applicable.
Page 25
EDS - TECHNICAL INSTRUCTIONS 9 - Declared Performance. All requirements including all essential characteristics and the corresponding performances for the intended use or uses indicated in 3 have been determined as described in the hEN mentioned in the following. Essential Characteristics...
Page 26
1. OBJECT to modify, extend or enlarge this warranty. The performance of any EDS S.r.l. - Via Cà Nova Zampieri 6, 37057 S. G. Lupatoto - Verona, warranty service under this Agreement is not an admission or Italy (hereinafter “EDS”), guarantees its products to be free from agreement that the design or manufacture of a product is defective.
Page 27
• tests using standard metods according to the standards EN54-9 • test through the use of smoke or smoke generators (EDS model SKE-04) or similar • simple and practical tests determining an artificial lowering of the signal by means of gradual obscuration of the ray For barrier detectors (separate TX and RX), the artificial lowering of the signal can be obtained putting in front of the receiver RX or transmitter TX appropriate optical attenuator filters.
Page 28
EDS - TECHNICAL INSTRUCTIONS The information contained in this document have been carefully checked and are reliable. By the way EDS company is not responsable in any way for possible inaccurancies or errors and it reserves the right to perform changes in any part of this document and/or product, to improve the quality, reliability or the design.