CHAPTER INDEX The procedure below is intended for trained personell with previous 1 - Qualified Personell experience in installing EDS Beam Smoke Detectors RK100R. 2 - Relevant Standards If you don’t have the needed experience please refer to the standard installation procedure of this manual.
EDS - TECHNICAL INSTRUCTIONS REFLECTIVE TYPE OPTICAL BEAM SMOKE DETECTOR RK100R - RK100RS GENERAL The RK100R detector is a newly-conceived microprocessor optical beam smoke detector, that bases its working concept on the interaction between the smoke present in a room and an infrared beam emitted by a transmitter and reflected by an optical reflector (fig.1).
• JP1 position 2-3 (ON)..alignment procedure ON able to project a concentrated and sufficiently intense light beam. (we recommend the EDS alignment lamp LAL02) • JP1 posizion 1-2 (OFF)..alignment procedure OFF • direct the light beam of the lamp to the lenses of the detector •...
Page 5
EDS - TECHNICAL INSTRUCTIONS what’s following • 1 flash of the blue Led: 1 Volt 8.6 - the P1 trimmer (regulation of the signal level) is regulated in • 1 flash of the red Led: 0.5 Volts factory to the 50-60% and it corresponds to a signal of 5V to the •...
EDS - TECHNICAL INSTRUCTIONS situation. The setting must normally be a medium sensitivity level, 10.5 - Stopped this phase of adjustment, the detector becomes but in case of dusty and perturbed environments it will be useful to operational. The blue Led of Alignment stops (detail cap.10.2) and set a lower sensitivity level.
Type: Reflective Type Optical Beam Linear Smoke Detector • jumper JP5 in position 1-2 - memory not activated (OFF) • Manufacture: EDS srl - V. Cà Nova Zampieri 6 - 37057 S.G. • jumper JP5 in position 2-3 - activated (ON) Lupatoto - Verona - Italy When the memory is activated, if the detector goes to alarm, the •...
Page 9
EDS - TECHNICAL INSTRUCTIONS DISTANCE SELECTION WITH JP7 Distance REFLECTOR Position fig.7 ° N ° N < a i r , 4 - g i l fig.8 > g i l g i l r u t i t a...
Page 10
EDS - TECHNICAL INSTRUCTIONS DS1649 LED di Allineamento LED di Allarme Relè Guasto fault Fehlerrelais relay Turbo Relè turbo Turborelais relay TURBO SENS POWER Relè Allarme alarm Alarmrelais relay fig.9 INTERNAL PARTS P1 - Trimmer for the regulation of the signal level. Normally regulated to 50-60% that corresponds to a signal of 5V at the maximum distance.
Page 11
EDS - TECHNICAL INSTRUCTIONS DS1650 LED di Allineamento LED di Allarme Relè Guasto fault Fehlerrelais relay Turbo Relè turbo Turborelais relay TURBO SENS POWER Relè Allarme alarm Alarmrelais relay fig.10 INTERNAL PARTS WITH STS-01 METER segnale analogico 0-5V analog signal output 0-5V contatto relè...
Page 12
EDS - TECHNICAL INSTRUCTIONS Example of RK100R connection with a zones Control Unit CENTRALE DI CONTROLLO alimentazione connessione zona1 segnale analogico 0-5V schermo contatto relè GUASTO resistenza di Allarme contatto relè TURBOLENZA contatto relè d'ALLARME resistenza di fine linea alimentazione 11-30 Vcc fig.12...
Page 13
40x60mm (dimensions) The information contained in this document have been carefully checked and are reliable. By the way EDS company is not responsable in any way for possible inaccurancies or errors and it reserves the right to perform changes in any part of this document and/or product, to improve the quality, reliability or the design.
Page 14
Agreement is not an admission or agreement that the design or manufacture of a product is defective. EDS - V. Ca' Nova Zampieri 6 - 37057 S. G. Lupatoto - VERONA - Tel. +39045547529 - Fax +390458750065 E.Mail: eds@eds.eu Web: www.eds.eu...