I N T R O D U C T I O N Scope and liability This document describes the functions, the technical data of NA11 devices; instructions for mount- ing, setting and commissioning are included. This manual has been checked out, however, deviations from the description cannot be completely ruled out, so that no liability in a legal sense for correctness and completeness of the information or from any damage that might result from its use is formally disclaimed.
Test label with following informations: data, serial number and test operator signature. Environment The NA11 device must be employed according to the environment conditions shown (see technical data). In case of different environment conditions, appropriate provisions must be provided (conditioning system, humidity control, etc...).
Page 7
The declared values for the overshoot time are applicable with the lower setting value of the operation time. ThySetter Setting and monitoring software Trip Operation (with operate time) Output relay minimum pulse width Upgrade Firmware upgrade eXtensible Markup Language INTRODUCTION NA11 - Manual - 02 - 2009...
Page 8
ON delay timer with reset ( delay) OUTPUT RESET RESET INPUT ON delay timer without reset ( delay) OUTPUT INPUT DROP OFF delay timer (dropout) without reset ( delay) DROP DROP OUTPUT Symbols.ai NA11 - Manual - 02 - 2009 INTRODUCTION...
Page 9
DROP INPUT Minimum pulse width operation for output relays ( OUTPUT INPUT Latched operating mode for output relays and LEDs Latched OUTPUT INPUT Pulse operating mode for output relays OUTPUT Symbols1 .ai INTRODUCTION NA11 - Manual - 02 - 2009...
G E N E R A L Preface The relay type NA11 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent protection can be used on feeders of any length,...
RS232 front serial port (local communication for Thysetter). • Real time clock with super capacitor backup. The most signifi cant constructive features of the NA11 protection relay are: • Galvanically insulated input and output circuits (communication and binary circuits included).
Permissible relative humidity 10...95 % Atmospheric pressure 70...110 kPa Safety Reference standards EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use Pollution degree Reference voltage 250 V Overvoltage category TECHNICAL DATA NA11 - Manual - 02 - 2009...
3 mA Block input (logic selectivity) Quantity Type (powered by internal isolated supply) polarized wet input Max consumption, energized 5 mA Note 1 The different versions must be select on order NA11 - Manual - 02 - 2009 TECHNICAL DATA...
100 Base TX, RJ45 • Baud rate 100 Mbps • Protocol ModBus®TCP/IP Note 1 The different versions must be select on order Note 2 The different versions must be select on order TECHNICAL DATA NA11 - Manual - 02 - 2009...
Note 1 The nominal current settings doesn’t concern the protection elements; they must agree with hardware setting (dip-switch 1 A or 5 A) . Note 2 1 - 5 A selection is meaningful for standard CTs versions; the computed residual current is employed for NA11 protection relays equipped with...
I> Curve type (I> DEFINITE Curve IEC/BS A, B, C ANSI/IEEE MI, VI, EI RECTIFIER, I t or EM > Activation time (t 0.00...100.0 s CLP> 0.00...9.99 s (step 0.01 s) TECHNICAL DATA NA11 - Manual - 02 - 2009...
Page 18
Asymptotic reference value: 1.1 I> Minimum operate time: 0.1 s Equation is valid for 1.1 ≤ I/I> ≤ 20 With I> pickup ≥ 2.5 I , the upper limit is 35 I NA11 - Manual - 02 - 2009 TECHNICAL DATA...
Asymptotic reference value: 1.1 I > Minimum operate time: 0.1 s Equation is valid for 1.1 ≤ I > ≤ 20 With I > pickup ≥ 0.5 I , the upper limit is 10 I TECHNICAL DATA NA11 - Manual - 02 - 2009...
(step 0.01 I 10.0...35.0 I (step 0.1 I Note 1 The computed residual current (vector sum of the phase currents) is employed for NA11 protection relays equipped with LPCT sensor inputs NA11 - Manual - 02 - 2009 TECHNICAL DATA...
Page 21
Asymptotic reference value: 1.1 I > Minimum operate time: 0.1 s Equation is valid for 1.1 ≤ I > ≤ 20 With I > pickup ≥ 0.5 I , the upper limit is 10 I TECHNICAL DATA NA11 - Manual - 02 - 2009...
≤ 0.05 s Dropout time (I >) accuracy ± 4% ± 1% I Dropout time (I >) accuracy ± 4% ± 1% I Operate time accuracy 5% or ± 10 ms NA11 - Manual - 02 - 2009 TECHNICAL DATA...
F I X ) • Rolling on demand period (t 1...60 min (step 1 min) ROL ) • Number of cycles for rolling on demand (N. 1...24 (step 1) ROL ) TECHNICAL DATA NA11 - Manual - 02 - 2009...
Current converter Note 1 The measured residual current is available only for NA11 protection relays equipped with standard CTs sensor inputs Note 2 The measured residual current is available only for NA11 protection relays equipped with standard CTs sensor inputs...
Temperature PT8 Note 1 The computed residual current (vector sum of the phase currents) is provided for NA11 protection relays equipped with LPCT sensor inputs Note 2 The temperature measuring is acquired by means of RTD probes Pt100 (eight Pt100 inputs with one MPT module); if the module is not available the concerning measure is meaningless.
F U N C T I O N C H A R A C T E R I S T I C S F U N C T I O N C H A R A C T E R I S T I C S HARDWARE DESCRIPTION The following fi gure illustrates the basic structure of the NA11 relay LEDs LEDs...
The removable plug allows separation of the MMI module for free access to the CPU board when DIP-switch setting is required. Note 1 The phase and residual nominal currents must be adjusted by means dip-switch. FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Xml fi les used for communication. The automatic code generation criteria ensures the quality of the result in terms of the reusability, verifi ability and maintainability of the software life cycle. FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
From the sampled quantities, several measures are computed for protection, monitoring and meter- ing purposes. • Direct • Calculated • Harmonics • On demand Direct • Power frequency. ACQUISITION ACQUISITION ≈ ≈ ≈ ≈ (Hz) (Hz) ≈ ≈ F.a i F.a i NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 31
R OL R OL L 2 ROL L 2 ROL L x ROL L x ROL L x k L x k ∙60 ∙60 L 3 ROL L 3 ROL Rol-Demand.ai Rol-Demand.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 32
L 3 MIN L x MIN L x MIN L x n L x n ∙60 ∙60 Reset Reset Min-Demand.ai Min-Demand.ai Use of over-described measures is shown in the following tables. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
D i re c t se q uence cy cl i c order D i re c t se q uence cy cl i c order Inverse sequence cy cl i c order Inverse sequence cy cl i c order fasori1.ai fasori1.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Reset counters Reset CB Monitor (clear CB monitoring data) 52a (CB auxiliary contact) 52b (CB auxiliary contact) Open CB Close CB Remote trip Reset on demand measures 79 Enable 79 Block FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 36
Note 1 To enable the profi le switching the “Input-selected” parameter must be set inside the “Profi le selection” submenu. If multiple setting groups are not required, Group A is the default selection NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 37
Note 4 The activation of one binary input produces indiscriminately a block of all protective elements programmed for being blocked from Block1 FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 38
Binary input allocation for CB state acquisition Binary input allocation for CB state acquisition CB-pos.ai CB-pos.ai Note 1 The reset of the total counters is practicable by means ThySetter command with Session Level 1 (available with password) NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 39
Reset demand measures The input activation makes a reset of all demand measures. 79 Enable The input activation enables the auto reclosing function. 79 Block The input activation disables the auto reclosing function. FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
- No-latched , in order that it stays ON for normal conditions and the other way round it goes OFF if any fault is detected and/or the auxiliary supply turns OFF. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 41
Cumulative CB tripping I^2t diagnostic relays (SumI^2t-K) Circuit breaker opening time diagnostic relays (tbreak-K) Open CB command relays (CBopen-K) Close CB command relays (CBclose-K) Remote tripping relays (RemTrip-K) Not received pulses at BLIN signalling relays (PulseBLIN-K) FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Note 1 The START and the TRIP LED are user assignable to any function; other than starting and tripping information can be assigned to them too, just the same for L1...L5 Note 2 All LEDs are unassigned in the default setting. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 43
Close CB command LEDs (CBclose-L) g g g g g Remote tripping LEDs (RemTrip-L) g g g g g Not received pulses at BLIN signalling LEDs (PulseBLIN-L) FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Note 2 The RS485 port is not implemented on the Pro-N devices endowed with Ethernet FX port Note 3 Information about the ModBus map may be fi nd inside the “Remote programming manual” NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
The residual CT primary current I must be set as: I = 100 A Note 1 The computed residual current is available for NA11 protection relays equipped with LPCT sensor inputs FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 46
Measures may be displayed according the following operating modes: - With RELATIVE setting all measures are related to the nominal value, - With PRIMARY setting all measures are related to the primary value. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
0 . 2 5 s 0 . 2 5 s 0 . 2 5 s Pt1...8 update Pt1...8 update t-refresh-F26.ai t-refresh-F26.ai Note 1 The 26 menu is available when the MPT module is enabled FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 48
- 26 \ PTx Probe \ ThALx Trip where x = 1...8. Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Phase overcurrent-50/51 \ I> Element \ Setpoints menu. Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 50
Set \ Profi le A(or B) \ Phase overcurrent-50/51 \ I> Element (I>> Element, I>>> Element) \ Setpoints menus. Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 51
& & Block1 I>>>BF I>>>BF Trip I>>> & Start I>>> I>>>BLK2IN BLK2INI>>> & & Block2 I>>>BLK2OUT BLK2OUT Start I>>> & General logic diagram of the phase overcurrent elements - 50/51 all-F50-51.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 52
Note 1 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR- ING section Note 2 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND MONITORING section NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 53
CB OPEN CB CLOSED CB OPEN 0.1 s CLP> Output t CLP> HIGH THRESHOLD/ LOW THRESHOLD/ HIGH THRESHOLD/ BLOCK UNBLOCK BLOCK Phase overcurrent (50/51) - First element logic diagram (I>) Fun_50-51S1.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 54
>> Blk2 OUT ≥1 BLOUT1 >>> Blk2 OUT Pilot wire output ST-IE BLK2 Block2 output 50-51S1_BL-diagram.ai Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the first element (I>) NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 55
CB OPEN CB CLOSED CB OPEN 0.1 s CLP>> Output t > > HIGH THRESHOLD/ LOW THRESHOLD/ HIGH THRESHOLD/ BLOCK UNBLOCK BLOCK Phase overcurrent (50/51) - Second element logic diagram (I>>) Fun_50-51S2.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 56
>> Blk2 OUT ≥1 BLOUT1 >>> Blk2 OUT Pilot wire output ST-IE BLK2 Block2 output 50-51S2_BL-diagram.ai Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the second element (I>>) NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 57
CB OPEN CB CLOSED CB OPEN 0.1 s CLP>>> Output t CLP>>> HIGH THRESHOLD/ LOW THRESHOLD/ HIGH THRESHOLD/ BLOCK UNBLOCK BLOCK Phase overcurrent (50/51) - Third element logic diagram (I>>>) Fun_50-51S3.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 58
>> Blk2 OUT ≥1 BLOUT1 >>> Blk2 OUT Pilot wire output ST-IE BLK2 Block2 output 50-51S3_BL-diagram.ai Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the third element (I>>>) NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
NA11 protection relays equipped with standard CT sensor inputs The computed residual current I (vector sum of the phase currents) is employed for NA11 protection relays equipped with LPCT sensor inputs Note 2 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point...
Page 60
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the Breaker Failure - BF menu. Note 2 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITOR- ING section NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 61
& & Block1 IE>>>BF IE>>>BF & Trip IE>>> Start IE>>> IE>>>BLK2IN BLK2INIE>>> & & Block2 IE>>>BLK2OUT BLK2OUT Start IE>>> & General logic diagram of the residual overcurrent elements - 50N/51N all-F50N-51N.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 62
\ Selective block OUT menu. Note 1 The exhaustive treatment of the selective block (Block 2) function may be found in the “Selective Block” paragraph inside CONTROL AND MONITORING section NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 63
CB OPEN CB CLOSED CB OPEN 0.1 s ECLP> Output t ECLP> HIGH THRESHOLD/ LOW THRESHOLD/ HIGH THRESHOLD/ BLOCK UNBLOCK BLOCK Residual overcurrent (50N/51N) - First element logic diagram (IE>) Fun_50N-51NS1.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 64
>> Blk2 OUT ≥1 BLOUT1 >>> Blk2 OUT Pilot wire output ST-IE BLK2 Block2 output 50N-51NS1_BL-diagram.ai Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the first element (IE>) NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 65
CB CLOSED CB OPEN 0.1 s ECLP>> Output t > ECLP > HIGH THRESHOLD/ LOW THRESHOLD/ HIGH THRESHOLD/ BLOCK UNBLOCK BLOCK Residual overcurrent (50N/51N) - Second element logic diagram (IE>>) Fun_50N-51NS2.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 66
>> Blk2 OUT ≥1 BLOUT1 >>> Blk2 OUT Pilot wire output ST-IE BLK2 Block2 output 50N-51NS2_BL-diagram.ai Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the second element (IE>>) NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 67
CB CLOSED CB OPEN 0.1 s ECLP>>> Output t >> ECLP > HIGH THRESHOLD/ LOW THRESHOLD/ HIGH THRESHOLD/ BLOCK UNBLOCK BLOCK Residual overcurrent (50N/51N) - Third element logic diagram (IE>>>) Fun_50N-51NS3.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 68
>> Blk2 OUT ≥1 BLOUT1 >>> Blk2 OUT Pilot wire output ST-IE BLK2 Block2 output 50N-51NS3_BL-diagram.ai Residual overcurrent (50N/51N) - Logic diagram of the blocking signals concerning the third element (IE>>>) NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Note 1 Both auxiliary contact state 52a and 52b must be acquired (two binary inputs are required). Note 2 The exhaustive treatment of the logic block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITORING section FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 70
BLK1 BF & Block1 Logic INx t INx t n.c. INx t Block1 input (ON≡Block) INx t Block1 n.o. Binary input INx Logic diagram concerning the breaker failure element -BF Fun-BF_Pro-n.ai NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Note 1 The reclosing waiting time is calculated from the fi rst event that is detected between the reset of the trip element and the open state acquisition of the circuit breaker FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 72
Timer di neutralizzazione Timer di neutralizzazione Richiusura rapida seguita da guasto e successiva richiusura lenta operata con successo Richiusura rapida seguita da guasto e successiva richiusura lenta operata con successo 79RL-diafram.ai 79RL-diafram.ai NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 73
CB command and a delayed reclosure attempt. FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 74
79-IE>>> & & & & & & Schema a blocchi generale della funzione di richiusura automatica - 79 Schema a blocchi generale della funzione di richiusura automatica - 79 all-F79.ai all-F79.ai NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Note 1 In the following treatment, the logical block is defi ned as “Logical block” or “Block1” Note 2 The Block 1 signal forces a timer reset FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 76
INx t INx t BLK1 S< 74CT element n.o. BLK1 BF BF element Binary input INx Block1 info Block1 (internal state) Block1_L.ai Logic diagram concerning the logic block element -Block1 NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
After an adjustable time t (common for phase protection elements) or t (common for B-Iph B-IE Note 1 The “Logic selectivity” and “Block2“ terms are employed without distinction FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 78
FROM EARTH FAULT PROTECTIONS Logic INx t INx t Block2 IE ≥1 IE Block2 n.c. INx t INx t n.o. Binary input INx Logic diagram concerning the selective block intput - Block2 input Block2-in-diagram.ai NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 79
F-IPh/IE phase+earth functions. The timers starts when one or more selective block function goes ON. When a timer expires, the selective block output is disregarded (again if the start holds steady). FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 80
The periodic pulses that are sent by output circuit may be enabled or disabled by means the Pulse- BLOUT1 parameter available inside the Set \ Pilot wire diagnostic menu. The same setting must be for output (see Input selective block). NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Remote trip Remote trip INx t O F F Logic INx t O N Remote trip n.c. RemTrip-K INx t INx t n.o. RemTrip-L Binary input INx Remote trip logic diagram Fun-Remote-trip.ai FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
0.25 I - 1% E Locked frequency (Displayed value) 60 Hz (0 Hz) f (Hz) Frequency tracking IF.ai All protective elements are always operative; accuracy is guaranteed inside locked frequency band. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
(No-latched inside Set\Relays sub- menu) and the Logic parameters (Energized/De-energized) must be programmed in the same way of the related binary input connected with-it. FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Set\Profi le A(or B)\ Phase overcurrent - 50/51\ I> Element \ Defi nite time menu. CB position can be acquired by means one or two binary inputs; allocation of 52a and 52b func- tions is available inside the Set\Inputs\Binary input IN1...INx menu. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
CT monitoring logic diagram - 74CT Fun-74CT.ai Note 1 The exhaustive treatment of the logic block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITORING section FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
CB opening time is still in progress), to avoid untimely operations the previ- ous condition are checked every 80 ms and the output is issued after a 2 s delay; outputs are reset NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Page 87
TRIP contact of the protection: DE-energized, No latched Note 2 Since two binary inputs are just used (TCS1 and TCS2), an external I/O module is required for the logic block function FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 88
The power dissipated by the R resistor is: = R · I = R · [U / (R + R Depending on availability coil and/or CB auxiliary contacts other circuit are possible. NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
All the named parameters are available inside the Set\Circuit Breaker supervision\CB Diagnostic menu. Tutti i suddetti parametri, nonché l’associazione delle uscite ai relè fi nali ed ai LED, sono presenti nel menù Set\Monitoraggio interruttore\Diagnostica interruttore. FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Page 90
SumIL1^2t SumIL2^2t SumIL3^2t CB Diagnostic - Cumulative tripping energy I2t Mode-tOpen State tbreak Ktrig-break break tbreak-K & tbreak-L ≥ From CB position Opening transition CB Diagnostic - CB operating time Fun-CB-diagnostic.ai NA11 - Manual - 02 - 2009 FUNCTION CHARACTERISTICS...
Note 1 The temperature measure is acquired by means of Pt100 probes (eight inputs on MPT module) Note 2 The output relay K7...K10 and binary input IN3...IN42 states is meaningful when the I/O circuits are present (MRI and MID16 modules) FUNCTION CHARACTERISTICS NA11 - Manual - 02 - 2009...
Note 1 The computed residual current is available for NA11 protection relays equipped with LPCT sensor inputs Note 2 The third harmonic component of the residual current is available for NA11 protection relays equipped with CT inputs NA11 - Manual - 02 - 2009...
Note 4 Event 0 is the newest event, while the Event 299 is the oldest event Note 5 Counter is updated at any new record; it may be cleared by means ThySetter NA11 - Manual - 02 - 2009 MEASURES, LOGIC STATES AND COUNTERS...
Page 95
204 records can be stored if f = 60 Hz, since: Note 1 Data are stored into volatile memory RAM, they are lost when power goes down MEASURES, LOGIC STATES AND COUNTERS NA11 - Manual - 02 - 2009...
N.4 fori ø 3,5 N.4 fori ø 3,5 Flush-mount.ai Flush-mount.ai Flush mounting Flush mounting Separation of fixed and removable parts is NOT required Separation of fixed and removable parts is NOT required NOTE NOTE INSTALLATION NA11 - Manual - 02 - 2009...
Page 99
N.4 fori ø 4,5 N.4 fori ø 4,5 Separate operator panel Separate operator panel Separate-mount.ai Separate-mount.ai A standard direct shielded cable with RJ45 connectors must be used for connections. Separate operator panel Separate-mount1.ai INSTALLATION NA11 - Manual - 02 - 2009...
Page 100
Rack mounting Rack mounting Rack-mount.ai Rack-mount.ai To allow opening of the keyboard door a one unit space must be provided when several rack are overlapping mounted. Rack mounting Rack mounting Rack-mount1.ai Rack-mount1.ai NA11 - Manual - 02 - 2009 INSTALLATION...
CAUTION CAUTION Devices must be installed by qualified personnel only. No liability is accepted from Thytronic due to improper use. Devices must be installed by qualified personnel only. No liability is accepted from Thytronic due to improper use. For the A1...A22 connections, screw terminals with following characteristics are available: •...
Page 102
2.5 mm Ground screw Earthing rear.ai Note 1 The three groups of Dip-switches must be adjusted with same setting For more information about technical data of the LPCT current transformers please contact Thytronic NA11 - Manual - 02 - 2009 INSTALLATION...
Page 103
The same considerations also apply when the sensor is positioned near bends in the cabling. It is recommended that the transformer be placed away from bends in the conductors). Fig. 2a Fig. 2b Fig. 2c Current balanced transformer Toroide.ai INSTALLATION NA11 - Manual - 02 - 2009...
Page 104
Output relay K5 and K6 have one make contact (SPST-NO, type A for K5), one break contact (SPST- NC, type B for K6) and a common reference (A13 terminal). All contacts are shown in de-energized state for standard reference. NA11 - Manual - 02 - 2009 INSTALLATION...
Page 105
The link must be enabled by means ThySetter sw and RS232 connection: Set the IP address (Host IP address e IP net mask) in order that the NA11 and PC parameters • are matched; the parameters are inside the Communication \ Ethernet submenu.
Page 106
It is recommended to terminate the line at the extremities of the same; this must be performed on the RS485 line control unit and on the NA11 device placed at the furthest point connecting the specially provided resistor; termination can be made by means a jumper between the F2-F3 terminals.
Page 108
One MRI module, two MID16 modules, one MPT module, one MCI module and one MMI module (separate operator panel) can be connect at the same time to the Thybus port (maximum expansion). NA11 - Manual - 02 - 2009 INSTALLATION...
Page 109
A ring network example is shown on the following pages. Block out signals concerning the NA11 devices (S3.1, S3.2 e S3.3) are split on two isolated outputs by means of MRB devices (B2.1, B2.2 and B2.3) to allow proper selectivity logic operation..
Disconnect.ai • Remove the upper tile and open the little door to access the fastening screws. Removing tie to access the fastening screws Removing tie to access the fastening screws Remove-tile.ai Remove-tile.ai NA11 - Manual - 02 - 2009 INSTALLATION...
Page 113
Unmounting of the case from the switchboard is not needed. set-in.ai set-in.ai Unmounting Unmounting • Split the MMI module and disconnect cable Split MMI module from fixed module Split MMI module from fixed module Split-MMI.ai Split-MMI.ai INSTALLATION NA11 - Manual - 02 - 2009...
Page 114
- eliminate any potential differences between the human body and the device by touching the metallic case, - avoid touching the printed circuit and connections (tracks, component terminals), - avoid handing the device to others, - set the programming DIPs by using antistatic tools. NA11 - Manual - 02 - 2009 INSTALLATION...
Page 115
Dip-switch localization concerning the nominal current setting inside the CPU board set-In.ai set-In.ai • Reassemble all parts with the previous operations in reverse order. • Reconnect the RS485 and RJ45 cables (Ethernet and/or Thybus). INSTALLATION NA11 - Manual - 02 - 2009...
The auxiliary voltage in the panel falls within the operative range of Pro_N relays. • The rated current (1 A or 5 A) of the line CT’s corresponds to the setting of Pro_N relays. • All wirings are correct. • All screws are tightly screwed. NA11 - Manual - 02 - 2009 INSTALLATION...
The ThySetter sw is a “browser” of data (setting, measure, etc..); it implements an engine that is afford to rebuild the menu set up and the relationships to data concerning all Thytronic protective relays by means of XML fi les.
“PILOT WIRE DIAGNOSTIC >>” “SELECTIVE BLOCK BLOCK2 >>” “FAULT RECORDING >>” “EVENTS RECORDING >>” Note 1 Setting changes are enabled when the La mEnabling setting by MMI parameter is set NA11 - Manual - 02 - 2009 SETTING AND COMMISSIONING...
(Enter) button for a few seconds; new message appears: “Confi rm settings?” • Answer to the message ENTER: YES to confi rm changes or RESET: NO to abort. The end of the LED blinking points out the end of procedure. SETTING AND COMMISSIONING NA11 - Manual - 02 - 2009...
By means of the (Open) and (Close) keys the circuit breake command may be issued. The committed output relays must be enabled; the concerning setting is available inside the CIR- CUIT NA11 - Manual - 02 - 2009 SETTING AND COMMISSIONING...
State SumI^2t State tbreak SumIL1 0 In SumIL2 0 In SumIL3 0 In SumIL1^2t 0 In^2s Binary SumIL2^2t 0 In^2s DELAYED INPUTS PROCEED READ MENU’ Binary SumIL3^2t 0 In^2s NA10_menu1.ai SETTING AND COMMISSIONING NA11 - Manual - 02 - 2009...
Page 122
Settings EVENTS RECORDING IL1r: 0 In Date IL2r: 0 In Eventx: Time IL3r: 0 In Settings IEr: 0 IEn Date Event19: Binary IN: Time Settings Relay OUT: Date Time NA10_menu2.ai NA11 - Manual - 02 - 2009 SETTING AND COMMISSIONING...
Page 125
NTP Synch. Test state: Stop test? >> Start test? >> Test K1 >> Test K2 >> TEST Test K3 >> Test K4 >> Test K5 >> Test K6 >> NA60_menuset5.ai SETTING AND COMMISSIONING NA11 - Manual - 02 - 2009...
Nota 3 With setting more than 2.5 In for the 50/51 elements and 0.5 IEn for the 50N/51N elements, the upper limit of the measuring range is limited to 50 In and 10 IEn respectively. APPENDIX NA11 - Manual - 02 - 2009...
0.5 s t> 0.2 s t> 0.1 s t> 0.02 s 0.01 I /I>inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> = 700 F_51-IECA-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
0.5 s t> 0.1 s t> 0.2 s t> 0.02 s 0.01 I /I>inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> = 14.5 F_51-IECB-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
= 0.1 s t> = 0.2 s t> = 0.5 s I /I >inv 0.01 7 8 9 10 Note: match of operating and setting time takes place when I/I> F_51-IECC-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
0.5 s E>inv 0.2 s E>inv 0.1 s E>inv 0.02 s E>inv 0.01 >inv 7 8 9 10 Note: match of operating and setting time takes place when I > = 700 F_51N-IECA-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
= 0.1 s E>inv 0.2 s E>inv = 0.02 s E>inv 0.01 >inv 7 8 9 10 Note: match of operating and setting time takes place when I > = 14.5 F_51N-IECB-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
= 0.02 s E> = 0.1 s E> = 0.2 s E> = 0.5 s 0.01 >inv 7 8 9 10 Note: match of operating and setting time takes place when I > F_51-IECC-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
Nota 3 With setting more than 2.5 In for the 50/51 elements and 0.5 IEn for the 50N/51N elements, the upper limit of the measuring range is limited to 50 In and 10 IEn respectively. NA11 - Manual - 02 - 2009 APPENDIX...
= 0.5 s t> = 0.2 s t> = 0.02 s 0.01 I /I >inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> = 1.664 F_51-ANSIMI-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
= 0.1 s t> = 0.2 s t> = 0.5 s t> 0.01 I /I >inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> = 2.306 F_51-ANSIVI-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
= 0.2 s t> = 0.5 s t> t> = 1 s 0.01 I /I >inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> = 2.789 F_51-ANSIEI-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
= 0.5 s > = 0.2 s > = 0.02 s 0.01 >inv 7 8 9 10 Note: match of operating and setting time takes place when I > = 1.664 F_51N-ANSIMI-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
= 0.1 s > = 0.2 s > = 0.5 s > 0.01 >inv 7 8 9 10 Note: match of operating and setting time takes place when I > = 2.306 F_51N-ANSIVI-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
= 0.2 s > = 0.5 s > > = 1 s 0.01 >inv 7 8 9 10 Note: match of operating and setting time takes place when I > = 2.789 F_51N-ANSIEI-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
Nota 3 With setting more than 2.5 In for the 50/51 elements and 0.5 IEn for the 50N/51N elements, the upper limit of the measuring range is limited to 50 In and 10 IEn respectively. APPENDIX NA11 - Manual - 02 - 2009...
= 0.1 s t> = 0.02 s t> = 0.1 s 0.01 I /I >inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> F_51-RI-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
= 0.2 s t> = 0.02 s t>> = 0.02 s t> = 0.1 s t>> = 0.1 s 0.01 Note: match of operating and setting time takes place when I/I> F_51-I2t-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
[s] 10000 0.28 t =t> · -0.236 [(I/I> -0.339] · 1000 t> = 0.02 s t> = 0.1 s 0.01 Note: match of operating and setting time takes place when I/I> F_51-EM-Char.ai NA11 - Manual - 02 - 2009 APPENDIX...
Residual overcurrent 50N/51N - Electromechanical inverse curves (EM) t [s] 10000 1000 > 0.02 s > 0.1 s 0.01 Note: match of operating and setting time takes place when I > F_51N-EM-Char.ai APPENDIX NA11 - Manual - 02 - 2009...
For all diagrams the output contacts are shown in de-energized state for standard reference. NA11 74CT 50/51 50BF 50N/51N CB position Three phase CTs and residual current from core balanced CT NA11-SCH.ai NA11 - Manual - 02 - 2009 APPENDIX...
Page 149
NA11 74CT 50/51 50BF 50N/51N CB position Two phase CTs and residual current from core balanced CT NA11-SCH2.ai APPENDIX NA11 - Manual - 02 - 2009...
Page 150
NA11 74CT 50/51 50BF 50N/51N CB position Three phase CTs and residual current from common return of phase CTs (Holmgreen) NA11-SCH4.ai NA11 - Manual - 02 - 2009 APPENDIX...
Page 151
L1 L2 L3 NA11 74CT 50/51 50BF 50N/51N CB position Transformer protection example - low voltage side NA11-SCH5.ai APPENDIX NA11 - Manual - 02 - 2009...
Page 176
I>> Output selective block I>>BLK2OUT OFF | ON I>> Second harmonic restraint I>>2ndh-REST OFF | ON I>> Breaker failure I>>BF OFF | ON I> Disabling by I>> start I>disbyI>> OFF | ON NA11 - Manual - 02 - 2009 APPENDIX...
Electrical relays Part 6: General requirements for measuring relays and protection equipment IEC 60255 Electrical relays Year of CE marking: 2005 Signature ..........Name FIORE Ing. GIOACCHINO Title Managing director Date 12-2005 NA11 - Manual - 02 - 2009 APPENDIX...