26.7 Parameters without index, with direct display
26.7.1 Using the example of parameter 208: Program stop
or
148/213
Building Technologies
HVAC Products
P
V
h min s
P
V
h min s
P
V
h
min s
Basic documentation LMV37.4...
26 Parameter level
PArA meter level 200: for basic units.
/reset
Press
to select «Program stop».
Display: Parameter 208: flashes, value 0 does
not.
%
/reset
Press
to go to editing mode.
/reset
Display:
Program stop time set
Here: Value 0
%
→ corresponding to program stop deacti-
vated.
Press
or
program stop time.
0 = deactivated
1 = PrePurgP (Ph24)
2 = IgnitPos (Ph36)
3 = Interv1 (Ph44)
%
4 = Interv2 (Ph52)
Example: 2 IgnitPos (Ph36)
Press
to go to menu
/reset
level 200:
to select the required
CC1P7546en
01.12.2009