Control via the operator panel
5.7 Operation via the operator panel (LOCAL mode)
5.7.2

ON key / OFF key

ON key: always active in LOCAL when the operator input inhibit is deactivated.
OFF key: in the factory setting, acts as OFF1 = ramp-down at the deceleration ramp (p1121);
when n = 0: voltage disconnection (only if a main contactor is installed)
The OFF key is effective in the LOCAL mode and when the "OFF in REMOTE" function is
active.
Settings: Menu – Commissioning / Service – AOP Settings – Control Settings
Red OFF key acts as: (factory setting: OFF1)
● OFF1: Ramp-down on the deceleration ramp (p1121)
● OFF2: Immediate pulse block, motor coasts to a standstill
● OFF3: Ramp-down on the emergency stop ramp (p1135)
5.7.3

Switching between clockwise and counter-clockwise rotation

Settings: MENU – Commissioning/Service – AOP settings – Control settings
Switching between CCW/CW (factory setting: no)
● Yes: Switching between CW/CCW rotation by means of the CW/CCW key possible in
● No: The CW/CCW key has no effect in LOCAL mode
For safety reasons, the CW/CCW key is disabled in the factory setting (pumps and fans must
normally only be operated in one direction).
In the operation status in LOCAL mode, the current direction of rotation is indicated by an
arrow next to the operating mode.
Note
You have to make additional settings when switching between CW/CCW rotation.
36
LOCAL mode
The AOP30 operator panel
Operating Instructions, 03/2012, A5E00331451A