Installation and Operating Instruction for B.E.G. - Occupancy detectors PD4-M-1C-FC/-FM
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision
of qualified skilled electrical person-
nel in accordance with electrotechni-
cal regulations.
Disconnect supply before installing!
When in Master/ Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
120 60 50
A
daylight.
120 60 50
40
A
40
30
15
30
5
10
15
5
10
3. Putting into operation / Settings
Follow-up time for light control
16 10
The time can be set infinitely variably at between
5
16 10
15 seconds and 16 minutes.
5
2
Symbol
2
1
Symbol
TEST
(Every movement switches on the light for a period of 1
30
1
15
second, switching it off for a period of 2 seconds after that
TEST
30
15
regardless of the level of brightness.)
2000
2000
1200
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10
1200
600
and 2000 Lux. Using the rotary control, the luminance set
points can be set as desired.
600
200
40
Symbol :
200
40
Symbol
Option:
max
IR-PD
ON
OFF
Wall bracket for remote
max
control IR-PD
ON
OFF
IR-PD-Mini
®
2a. Installation of the LUXOMAT
PD4-M-1C-FC
The detector has
been designed and
developed specifi-
cally for installation in
suspended ceilings.
A circular opening of
diameter 68 - 70 mm
must first of all be pro-
duced in the ceiling.
Having connected up the cables in accordance
with regulations, the detector is inserted into
the opening as shown in the drawing opposite
and fixed into position with the assistance of the
spring clip.
:
impulse < 1sec.
TEST
:
Test mode
Night-time operation
:
Daytime / Night-time operation
Unlocking device
��
Luminance set point
���
����
���
Automatic reading in the current light value
as new luminance set point
Individual light value 2 - 2500 Lux
��
Follow-up time (relay and channel 1)
��� ��
���
15 sec. up to 30 min.
50
1500
Lux
Lux
Impulse function (relay and channel 1)
1sec. ON, 9 sec. OFF
Preset / user mode
Fully automatic/semi automatic mode => (see page 2, point 5)
Semi automatic: red LED (flashing),
Fully automatic: red LED on for ca. 3 sec.
50
1500
Lux
Lux
Resetting when open
All values which have been programmed using the remote
control IR-PD are deleted, and those values which have
been set by potentiometer are activated.
Lock device
PD4-M-1C
®
2b. Installation of the LUXOMAT
PD4-M-1C-FM
The detector can be installed
in conventional inlet-sockets
mounted on the ceiling.
The assembly plate enclosed
must be stripped off prior to
installation and secured to
the ceiling using 4 screws
and ensuring that it is not
laterally transposed.
Having connected up the
cables in accordance with
regulations, the detector can
be placed in position as
shown in the drawing op-
posite and, applying a little
pressure, can then be locked into position with
the assistance of the spring clips.
max
ON
OFF
®
2c. Self test cycle
The product enters an initial 60-sec-
ond self-test cycle, when the supply
is first connected. The occupancy
detector is ready for operation.
4. Settings carried out using remote control (optional)
Remote control LUXOMAT IR-PD
120 60 50
A
40
30
15
5
1. Check Battery:
10
open battery compartment by pressing the
120 60 50
16 10
A
plastic springs together and removing the
5
40
2
30
battery-holder.
1
15
5
10
TEST
30
15
1
2
2. IMPORTANT
16 10
2000
5
1200
Please pay attention, that the setting is Potentio-
2
600
1
meter 1 at "TEST" and Potentiometer 2 not at
200
TEST
30
15
40
"SUN". All values which have been programmed
120 60 50
A
40
using the remote control will be deleted in the
30
2000
15
5
1200
event of power failure in the position "TEST/
10
600
1
2
SUN". Please switch Potentiometer 2 over to
200
40
2000
"MOON" or any other value.
16 10
5
1200
2
600
1
200
TEST
30
15
40
Caution:
2000
1200
Settings with remote control supersede the
600
settings by courtesy of potentiometers.
200
40
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e.
opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated).
This operating mode can only be activated during the period of
5 seconds after pressing the "lock" button. This status will only
permit actuating the function "Light on/Light off".
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
50
1500
Lux
Lux
5. Open detector
Light on/ off
The light will remain switched on/ off for as long as movements
are detected in the areas of coverage. Once the last movement
has been detected, the light will remain on for the duration of the
follow-up time as per setting.
The appliance will then return independently to the mode
selected (Fully or Semi-automatic).
GB

Advertisement

loading
Need help?

Need help?

Do you have a question about the LUXOMAT PD4-M-1C Series and is the answer not in the manual?

Questions and answers

Summary of Contents for B.E.G. LUXOMAT PD4-M-1C Series

  • Page 1 LUXOMAT PD4-M-1C ® Installation and Operating Instruction for B.E.G. - Occupancy detectors PD4-M-1C-FC/-FM 1. Mounting preparations 2a. Installation of the LUXOMAT ® 2b. Installation of the LUXOMAT ® 2c. Self test cycle PD4-M-1C-FC PD4-M-1C-FM Work on the 230 V mains supply The detector has The detector can be installed may only be carried out by qualified...
  • Page 2 9. Wiring diagrams 12. Technical data PD4-Master-1C 5. Fully / Semi automatic mode (for IR-PD functions see page 1) Sensor and power supply in one case Terminal connection for standard operation Power supply: 230 V~ +6 %/-10 % Fully automatic operation Power consumption: <...

This manual is also suitable for:

Luxomat pd4-m-1c-fcLuxomat pd4-m-1c-fm