I NT ER LO C K S BE T W EE N PA NE LS
Step 7/10
On the protection relay LHMI (upstream circuit breaker) go to -> Main Menu/Monitoring/
I/O status/Current protection/PHIPTOC1/Inputs
– BLOCK = False

Figure 85: Deactivating blocking mode

Step 8/10
On the protection relay LHMI (tested feeder) go to -> Main Menu/Test/IED test
– Test mode = Normal mode
The ready LED is steady ON.

Figure 86: Entering test mode

Step 9/10
Repeat steps 3 to 8 for all feeders.
Step 10/10
On the protection relay LHMI (upstream circuit breaker) go to -> Main Menu/Test/IED test
– Test mode = Test off