3 UCN Status Displays
3.7 HPMM Detail Status Displays
Bottom data fields defined
The data at the bottom of the display is defined in the following table.
Term
UCN
NODE
TYPE
P/S
STATUS
PKGOPT
UCN CHANNEL
UCN AUTO SWAP
FILE POS
Four-second update
With the exception of UCN, NODE, and TYPE, the data at the bottom of the display is updated every
four seconds.
Target comparison
The targets at the left side of the display are dependent on the node's redundancy status as illustrated by
comparison of Figure 120 and Figure 121. Except for the HPMM I/O Information display, the
information selected by the set of secondary HPMM targets is identical to those selected by the
corresponding target for a primary HPMM.
234
Table 44 HPMM Detail Status Display
The UCN number
The node number on the UCN
The node type (NIM or HPM)
The node's current redundancy status (PRIMARY, SECNDRY,
or NONREDUN)
The current composite status of the node. This is the same as
the composite status displayed on the UCN Status display. See
the Process Operations Manual for responses.
The configured hardware packaging of the HPMM.
REDUN = Nonredundant and redundant 7-Slot HPMM card files
REDUN_2F = Nonredundant and redundant 15-Slot HPMM
card files
Current UCN cable active (CHANNEL A or CHANNEL B).
The current UCN cable auto swap status (ENABLE or
DISABLE).
The HPMM node's assigned position in the HPM.
RIGHT = Right 7-Slot card file
LEFT = Left 7-Slot card file
FILE_1 = Primary (lower) 15-Slot card file
FILE_2 = Secondary (upper) 15-Slot card file.
HPM High-Performance Process Manager Service
Honeywell
Description
R688
December 2020
Need help?
Do you have a question about the HPM and is the answer not in the manual?