Technical specifications
6.1 Technical specifications
Article number
Input ranges (rated values), resistance ther-
mometer
•
Ni 100
Input resistance (Ni 100)
–
•
Ni 1000
Input resistance (Ni 1000)
–
•
Pt 100
Input resistance (Pt 100)
–
•
Pt 1000
Input resistance (Pt 1000)
–
Input ranges (rated values), resistors
•
0 to 150 ohms
Input resistance (0 to 150 ohms)
–
•
0 to 300 ohms
Input resistance (0 to 300 ohms)
–
Thermocouple (TC)
Temperature compensation
parameterizable
–
internal temperature compensation
–
external temperature compensation
–
with compensations socket
dynamic reference temperature value
–
fixed reference temperature
–
Cable length
•
shielded, max.
Analog value generation for the inputs
Measurement principle
Integration and conversion time/resolution per
channel
•
Resolution with overrange (bit including
sign), max.
•
Integration time, parameterizable
•
Integration time (ms)
•
Basic conversion time, including integration
time (ms)
additional conversion time for wire-
–
break monitoring
additional conversion time for re-
–
sistance measurement
42
6ES7144-5KD50-0BA0
Yes; Standard/climate
10 MΩ
Yes; Standard/climate
10 MΩ
Yes; Standard/climate
10 MΩ
Yes; Standard/climate
10 MΩ
Yes
10 MΩ
Yes
10 MΩ
Yes
Yes
Yes
Yes
Yes
30 m
integrating
16 bit
Yes; channel by channel
16.7 / 20 / 60
18 / 21 / 61 ms
4 ms
2 ms
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
Equipment Manual, 08/2020, A5E48753535-AA