ABB Zenith 50P-2035 Operation And Maintenance Manual page 16

Modbus network card for mx150/mx250 (mx version 6.0+ only)
Table of Contents

Advertisement

Appendix B
H
o
d l
n i
g
R
e
. g
B
t i
C
o
l i
D
e
c s
i r
HR 40094 - 40098 MUST ALL be written with a Write Multiple Holding Register Command
40094
System Time – Hour
40095
System Time – Minute
40096
System Time – Day
40097
System Time – Month
40098
System Time – Year
40100
Daylight Savings Time
HR 40101 - 40109 MUST ALL be written with a Write Multiple Holding Register Command
HR's listed as "Not Writeable" under certain conditions must be written as zeros
HR40101-40110 are for CDP Programmable Exercisers Only
40112
System Busy Control
0 113 Command to Bypass In-Phase Monitor 1 = Bypass In-Phase Monitor
1 114 Confirm Bypass In-Phase Monitor
2 115 Unused
3 116 Unused
4 117 Unused
5 118 Unused
6 119 Unused
7 120 Unused
40113
Net Control 2
0 121 Bypass Pending Exerciser
1 122 Cancel Exerciser Bypass
2 123 Unused
3 124 Unused
4 125 Unused
6 127 Unused
7 128 Unused
14
MX150/MX250 Series Modbus Network Card (71R-2200)
I
Read/Write Register List
(cont'd)
t p
o i
n
R
a
n
g
e
N
t o
0 - 23
0 - 59
1 - 31
Max val. depends on month, year
1 - 12
0 - 255, 0 = Year 2000
1 = ATS follows DST
1 = Confirm
1 = Bypass
1 = Cancel Bypass