Installation checklist
Contents of this chapter
This chapter contains a list for checking the mechanical and electrical installation of the
brake chopper.
Checklist
Check the mechanical and electrical installation of the brake chopper before start-up. Go
through the checklist together with another person.
WARNING! Only qualified electricians are allowed to carry out the work described
below. Obey the complete safety instructions for the drive. If you ignore the safety
instructions, physical injury or death can occur.
Open the main switch-disconnector of the drive and lock it to open position.
Ensure by measuring that the drive is not powered.
Check that ...
The brake chopper module has been attached properly on an even, vertical and non-flammable
mounting plate.
There is an adequately sized protective earth (ground) conductor between the brake chopper and the
cabinet PE busbar.
All protective earth (ground) conductors have been connected to the appropriate terminals and the
terminals have been tightened (pull the conductors to check). The galvanic connection between the
brake chopper module frame and the cabinet is proper. (Fastening points are unpainted.)
The supply voltage matches the nominal input voltage of the brake chopper module. Check the type
designation label.
Installation checklist 39
6