Download Print this page

ABB CSU-2LV Installation And Maintenance Manual page 50

Arc guard system

Advertisement

50
ABB
ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALL ATION AND MAINTENANCE GUIDE
Active errors
6.6.3.3
Currently active errors, bit is set if error is active.
ACTIVE_ERRORS
0x65
Bit
15–10
9
-
Internal
error
power
supply
Activation times for active errors register. If an error is
inactive, the time is for the last time the error occurred. If
error never has occurred the register is set to 0xFFFF.
Parameter name
ERROR_ACTIVATE_YEAR_MONTH_1
ERROR_ACTIVATE_YEAR_MONTH_2
ERROR_ACTIVATE_YEAR_MONTH_3
ERROR_ACTIVATE_YEAR_MONTH_4
ERROR_ACTIVATE_YEAR_MONTH_5
ERROR_ACTIVATE_YEAR_MONTH_6
ERROR_ACTIVATE_YEAR_MONTH_7
ERROR_ACTIVATE_YEAR_MONTH_8
ERROR_ACTIVATE_YEAR_MONTH_9
ERROR_ACTIVATE_YEAR_MONTH_10
Bit
15
14
13
Parameter name
ERROR_ACTIVATE_DATE_HOUR_1
ERROR_ACTIVATE_DATE_HOUR_2
ERROR_ACTIVATE_DATE_HOUR_3
ERROR_ACTIVATE_DATE_HOUR_4
ERROR_ACTIVATE_DATE_HOUR_5
ERROR_ACTIVATE_DATE_HOUR_6
ERROR_ACTIVATE_DATE_HOUR_7
ERROR_ACTIVATE_DATE_HOUR_8
ERROR_ACTIVATE_DATE_HOUR_9
ERROR_ACTIVATE_DATE_HOUR_10
Bit
15
14
13
8
7
6
Internal
Internal
Internal
error
error
error
optical
daisy
input 1
output
chain
Register access
0x92 (R)
0x95 (R)
0x98 (R)
0x9B (R)
0x9E (R)
0xA1 (R)
0xA4 (R)
0xA7 (R)
0xAA (R)
0xAD (R)
12
11
10
9
Years since 2000
Register access
0x93 (R)
0x96 (R)
0x99 (R)
0x9C (R)
0x9F (R)
0xA2 (R)
0xA5 (R)
0xA8 (R)
0xAB (R)
0xAE (R)
12
11
10
9
Date (1 - 31)
5
4
3
Input 1
Input 1 no
Rogowski
low light
light
coil N
Remark
Rogowski coil L1
Rogowski coil L2
Rogowski coil L3
Rogowski coil N
Input 1 no light
Input 1 low light
Internal error input 1
Internal error daisy chain
Internal error optical output
Internal error power supply
8
7
6
5
Remark
Rogowski coil L1
Rogowski coil L2
Rogowski coil L3
Rogowski coil N
Input 1 no light
Input 1 low light
Internal error input 1
Internal error daisy chain
Internal error optical output
Internal error power supply
8
7
6
5
2
1
Rogowski
Rogowski
Rogowski
coil L3
coil L2
coil L1
4
3
2
1
Month (1 - 12)
4
3
2
1
Hour (0 - 23)
0
0
0

Advertisement

loading

This manual is also suitable for:

Csu-2mv