Troubleshooting
4-5-5 Compressor error (E461, E467)
Compressor starting error(E461), Compressor wire missing error(E467)
1. Check items
1) Is the power connected properly?
2) Is the connector of compressor connected correctly?
3) Is the resistance normal between each phase for compressor ?
2. Check procedure
Does the error occur?
Is the value of resistance
between each phase(*) for compressor
smaller than 2
Is the value of resistance
mega
Ω
and outdoor unit body?
Is the wire of compressor
connected correctly?
90
Yes
Ω?
(*) U↔V, V↔W, W↔U
Yes
between compressor
Yes
Yes
No
No
Exchange the compressor
No
Exchange the compressor
No
Check the wire of compressor
Normal operation