Error Codes For Bus Diagnostics - Phoenix Contact Axioline F AXC Series User Manual

Diagnostic registers, and error messges
Table of Contents

Advertisement

UM EN AXL F SYS DIAG
Table 2-2

Error codes for bus diagnostics

Code
Additional code
(hex)
0BD1
0BF1
0BF2
0BF3
0C01
Device number
0C02
0C11
0C12
0C13
0C14
0C15
22
PHOENIX CONTACT
2.2
Error codes for bus diagnostics
Meaning
The bus could not be activated due to bus malfunctions. Check the bus configuration.
The configured module is not accessible.
A device present in the configuration frame has been re-
moved from the physical bus structure after the configu-
ration frame has been connected.
A module has been detected that was not configured.
An additional device was added at the end of the physi-
cal bus structure after the configuration frame was con-
nected.
The module is not located in the configured slot.
An active device was inserted at the different location of
the physical bus structure after the configuration frame
was connected.
The module is accessible but was not put into operation
due to missing parameters.
An active device was replaced by an unknown device in
the physical bus structure after the configuration frame
was connected (wrong instance ID).
The process data length does not correspond to the
configured value.
The process data width of an active device was changed
after the configuration frame was connected.
The module type does not correspond to the configured
value.
The module ID does not correspond to the configured
value.
Remedy
Check the configuration.
Adapt the configuration
frame if the modification was
done on purpose.
8663_en_03

Advertisement

Table of Contents
loading
Need help?

Need help?