Power quality filter
Table of Contents

Advertisement

If the hardware lock and/or the Communication lock has/have been engaged, the
filter cannot be started nor stopped. In order to see which lock(s) has/have been
engaged push
appear to indicate which lock(s) has/have to be disengaged. If authorized,
disengage the relevant lock.
The hardware lock can be disengaged by pushing the blue button present
at the bottom rear of the PQF-Manager. More information on the filter
menu locking facilities is given in
The Communication lock can be engaged in the menu [/Welcome/User
interface/Communication] by ticking the "check box". More information
on
the
"2GCS212013A0050-RS-485 Installation and Start-up guide".
When power is applied to the filter and it is started, the following startup sequence is
conducted:
Figure 83: Filter start-up sequence when power is applied and the start command is given
In
Figure 83
it may be seen that:
The DC capacitors charge as soon as the auxiliary circuit power is switched on.
The start-up sequence consists of the DC capacitors voltage check, the closure of
the filter main contactor, the start of the fan and the starting of the IGBTs
Network identification may be done after the start-up sequence has finished. This
network identification will always be done when harmonic components were
when the 'start/stop' menu is highlighted. A message will
Communication
lock
Manual Power Quality Filter PQFS  Operating instructions 169
Section
7.6.
is
available
in
the
document
.