When using the multi-pump control mode, you must set Pr.10.35 for each pump to the same value.
10.36

Multi-pump ID

Settings
When using the multi-pump control mode, the settings of each pump for Pr.10.36 cannot be the same.
10.37
Multi-pump's Fixed Time Circulation Period
Settings
This parameter is only valid for master pump settings.
Fixed time circulation mode (alternative operation): Assume that when pump #1's operating time is longer
than the setting for Pr.10.37, pump #1 stops, and then pump #2 activates, and so on.
Fixed quantity control (multi-pump operating at constant pressure): Assume that when the master pump's
operating time is longer than the setting for Pr.10.37, the master pump and the slave pump switch
alternatively.
10.38
Frequency to Start Switching Pumps
Settings
10.39
Time Detected When Pump Reaches the Starting Frequency
Settings
10.40
Frequency to Stop Switching Pumps
Settings
10.41
Time Detected When Pump Reaches the Stopping Frequency
Settings
This parameter is only valid for master pump settings.
This parameter is only valid for fixed quantity control (multi-pump operating at constant pressure) mode.
When the master pump's operating frequency ≥ Pr.10.38, and the time exceeds Pr.10.39, slave pump #1
activates. If the quantity of water is still insufficient, slave pump #2 and #3 activates under the same
conditions.
If the master pump's operating frequency ≤ Pr.10.40, and the time exceeds Pr.01.41, slave pump #1 stops.
If the master pump can fulfill the conditions, slave pump #2 and #3 stop in sequence, and leave the master
pump in operation only.
Whether the master pump stops depends on the stopping detection function.
10.42
Pump's Frequency at Time-out (Disconnection)
Settings
This parameter is only valid for slave pump settings.
For details on the conditions of communication disconnection and treatment, refer to Pr.09.02
Transmission Fault Action and Pr.09.03 Time-out Detection.
If disconnection (time-out) occurs in the fixed quantity control (multi-pump operating at constant pressure)
mode, the frequency for the slave pump is Pr.10.42. When you press the STOP key, the disconnected
slave pump is in single-pump mode. (The RUN command and operating frequency is set by the parameter
settings for the slave pump.)
The master pump can re-detect the disconnection of the salve pump.
1: Fixed time circulation (alternative operation)
2: Fixed quantity control (multi-pump operating at constant pressure)
0–4
0: Multi-pump control mode is disabled
1: Master
2–4: Slave
1–65535 minutes
0.00 Hz–F
MAX
0.0–3600.0 sec.
0.00 Hz–F
MAX
0.0–3600.0 sec.
0.00 Hz–F
MAX
Chapter 4 Parameters
VFD-EL-W
Default: 0
Default: 60
Default: 60.00
Default: 1.0
Default: 48.00
Default: 1.0
Default: 0.00
4-93

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VFD-EL-W Series and is the answer not in the manual?

Questions and answers

George
February 6, 2025

When the relay is not energized

User image 67a46b3eab0b7
1 comments:
Mr. Anderson
February 10, 2025

If the relay on a Delta VFD-EL-W Series is not energized, check the following:

1. Parameter Settings: Ensure that the multi-function output relay (RA1, RB1, RC1) is correctly configured in parameter 03.00. Verify that the function assigned matches the intended operation.

2. RUN Command: Confirm that the drive is in the correct operational state. Some relay functions only activate when the drive is running or specific conditions are met.

3. Voltage and Connections: Use a multimeter to measure the voltage at the relay terminals and check for proper wiring connections.

4. Fault Conditions: Inspect for any active faults or alarms that might prevent the relay from energizing.

5. Environmental Factors: Ensure that temperature, humidity, and other environmental conditions are within the specified limits.

6. Inspection and Maintenance: If necessary, turn off the AC input power, wait at least five minutes, and check for any physical damage or contamination affecting relay operation.

If the issue persists, further diagnostic testing may be required.

This answer is automatically generated

Table of Contents