System Solutions; 11.2.1 Explanations Of The System Solutions; 11.2.2 Bypass Of The Heating System - Bosch Compress 3000 AWES 2-6 Installation Manual

Indoor unit for air to water heat pump
Table of Contents

Advertisement

Technical information
11.2

System solutions

The outdoor unit and the indoor unit may only be installed according to
the manufacturer's official system solutions.
Deviating system solutions are impermissible. Liability is voided in the
case of damage and problems resulting from impermissible installation.

11.2.1 Explanations of the system solutions

General
SEC 20
Installer module integrated in the indoor unit
HPC 400
User interface
CR10H
Room temperature-dependent control unit with air
humidity sensor (accessory)
T1
Outdoor sensor
MK2
Humidity sensor (accessory)
CW1
DHW cylinder (accessory)
VW1
Diverter valve (accessory)
PW2
DHW circulation pump (accessory)
TW1
Hot water temperature sensor
Table 7 General Information
Z1
Heating circuit without mixer
PC1
Circulation pump, heating circuit
T0
Flow temperature sensor
Table 8 Z1

11.2.2 Bypass of the heating system

1
2
3
Fig. 24 Indoor unit with heating circuit and bypass
[1]
Bypass ( fig. 26) ([1] Tab. 9)
[2]
Flow pipe diameter ( [2] Tab. 9)
[3]
Return pipe diameter ( [3] Tab. 9)
24
T
T
Some system configurations require accessories (buffer cylinder, 3-way
valve, mixing valve, DHW circulation pump). If a heating circuit pump
(PC1) is installed, this is controlled by the controller in the indoor unit.
Fig. 25 Indoor unit with heating circuit and DHW heating
[1]
Bypass ( fig. 26) ( [1] Tab. 9)
[2]
Flow pipe diameter ( [2] Tab. 9)
[3]
Return pipe diameter ( [3] Tab. 9)
Fig. 26 Bypass details (
[1] [AWES fig. 24 and 25)
[L]
Minimum bypass length
[D]
Piping diameter
The bypass must have an outer pipe diameter of 22 mm (Cu) and be
installed between the supply and return. The bypass must be installed
close to the indoor unit (AWES), and no more than 1.5 m away from it.
([1]  fig.
([2] and [3]
 fig. 24
24 and 25)
[AWES] and
external
HP of
25) external
bypass pipe
outdoor
flow/return
diameter ([D]
unit
 fig. 26)
pipe diameter
mm
mm
2-8
22
22
11-15
28
22
Compress 3000 AWES – 6720892204 (2020/06)
Bypass design
([A]  fig.
([B]  fig.
27)
27)
Minimum
Minimum
bypass
bypass
length ([L]
length ([L]
 fig. 26)
 fig. 26)
mm
mm
200
100
200
100