Belimo GM24A-MOD Technical Data Sheet

Belimo GM24A-MOD Technical Data Sheet

Advertisement

Communicative damper actuator
for adjusting dampers in technical
building installations
• Air damper size up to approx. 8 m²
• Torque motor 40 Nm
• Nominal voltage AC/DC 24 V
• Control modulating, communicative,
hybrid
• Conversion of sensor signals
• Communication via BACnet MS/TP,
Modbus RTU, Belimo-MP-Bus or
conventional control
Technical data
Functional data
www.belimo.com
Technical data sheet
Electrical data
Nominal voltage
Nominal voltage frequency
Nominal voltage range
Power consumption in operation
Power consumption in rest position
Power consumption for wire sizing
Connection supply / control
Torque motor
Torque variable
Communicative control
Operating range Y
Operating range Y variable
Position feedback U
Position feedback U note
Position feedback U variable
Position accuracy
Direction of motion motor
Direction of motion note
Direction of motion variable
Manual override
Angle of rotation
Angle of rotation note
Running time motor
Running time motor variable
Adaptation setting range
Adaptation setting range variable
Override control, controllable via bus
communication
Override control variable
Sound power level, motor
Mechanical interface
Position indication
Safety
Protection class IEC/EN
Protection class UL
Degree of protection IEC/EN
Degree of protection NEMA/UL
Enclosure
EMC
GM24A-MOD • en-gb • 2020-04-21 • subject to changes
AC/DC 24 V
50/60 Hz
AC 19.2...28.8 V / DC 21.6...28.8 V
4 W
1.6 W
7 VA
Cable 1 m, 6 x 0.75 mm²
40 Nm
25%, 50%, 75% reduced
BACnet MS/TP
Modbus RTU (ex works)
MP-Bus
2...10 V
0.5...10 V
2...10 V
Max. 1 mA
Start point 0.5...8 V
End point 2...10 V
±5%
selectable with switch 0/1
Y = 0%: At switch position 0 (ccw rotation) / 1
(cw rotation)
electronically reversible
with push-button, can be locked
Max. 95°
can be limited on both sides with adjustable
mechanical end stops
150 s / 90°
75...290 s
manual
No action
Adaptation when switched on
Adaptation after pushing the gear
disengagement button
MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position) = 50%
MAX = (MIN + 32%)...100%
MIN = 0%...(MAX – 32%)
ZS = MIN...MAX
45 dB(A)
Universal shaft clamp 12...26.7 mm
Mechanically, pluggable
III Safety Extra-Low Voltage (SELV)
UL Class 2 Supply
IP54
NEMA 2
UL Enclosure Type 2
CE according to 2014/30/EU
GM24A-MOD
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GM24A-MOD and is the answer not in the manual?

Questions and answers

Summary of Contents for Belimo GM24A-MOD

  • Page 1 III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2 Enclosure UL Enclosure Type 2 CE according to 2014/30/EU www.belimo.com GM24A-MOD • en-gb • 2020-04-21 • subject to changes...
  • Page 2: Technical Data

    Parametrisable actuators The factory settings cover the most common applications. Single parameters can be modified with the Belimo Service Tools MFT-P or ZTH EU. The communication parameters of the bus systems (address, baud rate etc.) are set with the ZTH EU. Pressing the “Address” button on the actuator while connecting the supply voltage, resets the communication parameters to the factory setting.
  • Page 3 Service Tool, with ZIP-USB function, for parametrisable and ZTH EU communicative Belimo actuators / VAV controller and HVAC performance devices Belimo PC-Tool, Software for adjustments and diagnostics MFT-P Adapter for Service-Tool ZTH MFT-C www.belimo.com GM24A-MOD • en-gb • 2020-04-21 • subject to changes...
  • Page 4: Electrical Installation

    Connection with switching contact, e.g. Δp monitor – D– Requirements for switching contact: The switching contact must be able to accurately switch a current of 16 mA @ 24 V. GM24A-MOD • en-gb • 2020-04-21 • subject to changes www.belimo.com...
  • Page 5: Operating Controls And Indicators

    Release button: Gear engages, synchronisation starts, followed by standard mode Service plug For connecting parameterisation and service tools Check power supply connection Off and Possible wiring error in power supply www.belimo.com GM24A-MOD • en-gb • 2020-04-21 • subject to changes...
  • Page 6: Dimensions (Mm)

    12...18 Further documentation • Tool connections • Description Protocol Implementation Conformance Statement PICS • Description Modbus register • Overview MP Cooperation Partners • MP Glossary • Introduction to MP-Bus Technology GM24A-MOD • en-gb • 2020-04-21 • subject to changes www.belimo.com...

Table of Contents