Siemens SICAM Q100 System Manual page 34

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

Communication
2.2 Modbus
2.2.7.6 Register 0113: Group Indications (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
Table 2-10
Register
0
0113/2
2
0113/2
4
0113/2
6
0113/2
8
0113/2
10
0113/2
12
0113/2
14
0113/2
2.2.7.7 Register 0114: Power Quality Event (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
Table 2-11
Register
0
0114/2
2
0114/2
4
0114/2
6
0114/2
to
14
0114/2
NOTE
If a voltage, frequency or voltage unbalance event happened and ended, the relevant bit of this register will
be set to "1" and will be kept until it is reset by using relevant bits in register 141.
34
Register 0113: Group Indications
Type of Information
Group indication 1
Group indication 2
Group indication 3
Group indication 4
Reserved
Reserved
Reserved
Reserved
Register 0114: Power Quality Event
Type of Information
PQ Volt event
PQ Freq event
PQ VoltUnbal event
Reserved
Remark
Up to 4 single-point indications can be linked logically and
combined to a group indication. A total of 4 group indications
can be parameterized:
0 = Off
1 = On
= 0
= 0
= 0
= 0
Remark
1 = Voltage event exists
0 = Voltage event does not exist
1 = Frequency event exists
0 = Frequency event does not exist
1 = Voltage unbalance event exists
0 = Voltage unbalance event does not exist
= 0
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020