28.9 Parameter with index, with direct display

28.9.1 Using the example of parameter 501: No-flame positions fuel actuator

or
or
188/248
Building Technologies Division
Infrastructure & Citiies Sector
P
V
h min s
P
V
h min s
P
V
h min s
P
V
h min s
P
h min s
V
P
V
h min s
Basic documentation LMV36...
28 Parameter level
PArAmeter level 500: for fuel-air ratio
control.
%
/reset
Press
to go to menu level 500:.
/reset
Display: Parameter 501. flashes, index 00:
%
and value 0.0 do not.
/reset
Press
to go to the index.
/reset
Display: Parameter 501. does not flash, index
%
00: flashes, value 0.0 does not.
Press
or
index.
.00 = home position
.01 = prepurge position
.02 = postpurge position
%
Display: Index 01: for prepurge position
flashes, value 0.0 does not.
/reset
Press
to go to editing mode.
/reset
Display: Value 0.0
%
Press
or
prepurge position.
Example: 1.0
%
to select the required
to select the required
CC1P7544en
25.09.2013