Page 2
No part of this document may be photocopied, reproduced, or translated into another language for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of STULZ Air Technology Systems, Inc. (STULZ).
Page 4
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual TABLE OF CONTENTS (Continued) Maintenance ........5-1 Appendix A - Forms Periodic General Maintenance ....5-1 Checklist for Completed Installation ......A-1 Troubleshooting ...........5-3 Periodic General Maintenance Checks Field Service ..........5-6 and Service Checklist ..........A-2 5.3.1...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual INTRODUCTION The CyberRow system captures high temperature (hot aisle) discharge air from adjacent rack-based 1.1 General IT equipment and reintroduces it as conditioned air through the front of the unit (cold aisle).
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 1.3 Product Warranty See the contract.
Page 7
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual An extended warranty may be purchased on the unit’s compressor. The compressor warranty as stated below will be sent with your unit if the option is purchased and should be retained for future reference. You may...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 1.4 Safety WARNING 1.4.1 General Never operate the unit with any cover, guard, screen panel, etc. removed unless the instruc- STULZ Air Technology Systems, Inc. uses NOTES tions specifi cally state otherwise, then do so along with CAUTION and WARNING symbols with extreme caution to avoid personal injury.
Page 9
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual CAUTION WARNING Do not use cleaning solvents near open fl ame All personnel working on or near equipment or excessive heat. Wear eye protection when should be familiar with hazards associated blowing solvent from parts.
1.5 General Design The STULZ CyberRow unit is housed in a steel frame type cabinet rated for indoor use. The exterior of the cabi- net is coated with a powder coat fi nish to protect against corrosion. Removable access panels are located on the front and rear of the cabinet for easy access to all components.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 1.5.1 Electrical Compartment 1.5.3.2 Electronic Hot Gas Bypass The electrical components are protected inside an Used for freeze protection and capacity control, an electric box located behind the rear access panel.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual During start up, the fans begin operating in stages 1.6 Optional Equipment with fi ve second time delays. The middle fan starts 1.6.1 Remote Mounted Supply fi rst, then the upper fan, then the lower fan. The Temperature/Humidity Sensor system controller monitors fan operation.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual INSTALLATION CAUTION 2.1 Receiving the Equipment Tipping Danger. Keep the shipping support brackets attached to the front and rear of the Your CyberRow precision A/C system has been tested cabinet after removing the CyberRow unit and inspected prior to shipment.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual installation drawing provided with your unit for the pilot cool, conditioned air through the front grille to the hole locations. adjacent server modules on the cold aisle side of the row. It is recommended to position the unit to obtain 2.3.1...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual The cabinet is equipped with an adjustable foot at each corner to raise the cabinet off the casters after Hot Aisle the unit is positioned in its operating location. The adjustable feet are also used for leveling and overall height correction.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Cable type water detector- 3. Level the base. Mark and drill mounting holes through at least two of the available slotted holes. Lay the cable water detector fl at across the sub-fl oor where water could collect.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.7 Water- Water/Glycol Cooled DX (CRS-W & CRS-G Models) The system utilizes an external source of fl uid to provide coolant to the condenser inside the A/C unit. No refrigeration connections are required for self-contained water or glycol cooled systems (see Figure 4).
Page 18
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual For pipe connection sizes, refer to the following table: NOTE Water/Glycol lines should be insulated to PIPE CONNECTION SIZES prevent condensation from forming on the pipes if ambient dew point temperatures are higher...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.8 Split Air Cooled Systems (CRS-A Models) Split air-cooled systems with a remote condenser will require fi eld installed refrigerant piping. All split systems are shipped with a dry nitrogen charge of 100 psig. Release the pressure via an available stem valve or schrad- er valve prior to uncapping the pipes.
Page 20
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual debris to get inside refrigerant lines. Dry nitrogen PIPE CONNECTION SIZES should be fl owing through the tubing while soldering at a rate of not less than 1-2 CFM (0.028-0.57 M 3/...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual lent feet. For longer rises, individual calculations EQUIVALENT LENGTH (FT.) OF STRAIGHT PIPE should be made. Sizes assume the use of single risers; double rises may be necessary. OD (In.) Globe Angle 90°...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.9 Utility Connections The unit is provided with terminals for all required fi eld-wiring. Refer to the electrical drawing supplied 2.9.1 Main Power with the unit for all power and control fi eld-wiring. It is...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.9.1.1 Single-Phase Units 208/230V CAUTION The supply voltage for units that are designed for Do not connect any additional loads to the 208V operation must have a tolerance within -5% and +10%. If the measured supply voltage is 230V, system control transformers.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.9.3 Outdoor Equipment The following sections detail fi eld power wiring required for a typical system. Additional conductors may be required depending on the options purchased with the equipment. Refer to the electrical drawing supplied with your unit for the appropriate fi...
Page 25
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.9.3.3 Remote Condenser (CRS-A Models) For systems equipped with a remote condenser, the installer must provide main power wiring to the main power distribution block located within the remote condenser electric box. A separate equipment ground lug is provided within the electrical box for termination of the earth ground wire.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.10 System Charging Procedures R410A operates at high pressures which must be considered when checking the operating 2.10.1 Water-Water/Glycol Cooled Systems temperatures/pressures while charging or troubleshooting the system. Tables are provided in No fi...
Page 27
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Table3 EVACUATE THE SYSTEM Weight of R410A Refrigerant CAUTION (Lbs./100 Ft of type L tubing) A proper vacuum must be drawn on the Line Discharge refrigerant system to remove moisture prior...
Page 28
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual moisture is in the system that still needs to be WARNING boiled off. Proceed to step #5. If the pressure rises rapidly up to atmospheric pressure (more than 50 If refrigerant gas is released in an enclosed area, microns per minute) it indicates a leak that wasn’t...
Page 29
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4. Block off a portion of the intake air to the 2.10.2.4 -30°F Ambient Applications condenser until a constant discharge pressure NOTE can be obtained. This will lower the possibility of For units designed for -30°F operation, a...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 2.10.3 Refrigerant Characteristics 2.11 Settings and Adjustments 2.10.3.1 Pressure/Temperature Settings 2.11.1 Water-Water/Glycol Circuit The following table is provided to assist with the Condensing temperature is maintained by liquid normal settings of the system for R410A refrigerant.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual compressor. As a standard, superheat is factory set 2.11.5 EC Fans at 12-15°F and should not need adjustment. The The speed of the EC fans are controlled via a 0 superheat temperature is monitored and controlled by to 10 VDC signal from the system controller.
4. After “Unit On” appears, the fans begin operating in 5 second, time delayed stages (adjustable). The middle fan is turned on 1st, then the upper fan, then the lower fan. The STULZ logo in the display is replaced with a blower symbol.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.0 E² CONTROLLER General 4.1.1 Features The advanced microprocessor based, E 2 Series 4.1.1.1 Field Confi gurable controller is a highly versatile and fl exible A/C system The program for the E 2 Series controller is fi eld controller.
Illuminates yellow when unit is on own unique address. Returns to the previous menu level Multiple A/C units consisting of up to eight (8) STULZ Cancels a changed entry precision air conditioners equipped with like controllers may be controlled and monitored via the...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.1.4 BMS Interface 4.1.3 Controller I/O Module series controller may incorporate a BMS network The controller is a microprocessor based I/O module card equipped with a communication port (Figure 12). mounted inside the A/C system electric box (see Figure This can be fi...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Navigating Controller Display Screens 4.2.1 Menu Selection When the desired menu is centered in the screen with Series controller provides fi ve user selectable bold capital letters and an arrow symbol pointing...
Page 37
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.2.3 Display Variables advance the cursor through the various modifi able fi elds of the display screen eventually returning to the fi rst fi eld. The user interface display panel provides screens with...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.2.6.1 Password Protected Screens 4.2.6.2 Wrong Password Upon fi rst attempting to select a secure menu in a given session, the "Enter Password" screen will be Reset? No displayed. This screen displays the current security level Enter Password: authorized.
Page 39
fl uid control valve (CRS-W & CRS-G units) and the fans are allowed to begin operating. 5. The STULZ logo in the display is replaced with a blower symbol. The fans begin operating in stages with fi...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.3.1 Setpoint Adjustment 6. From the Temperature setpoint screen, select the Humidity Setpoint screen by scrolling with the Up ( ) or 1. From the Main screen, access the Main Menu screen Down ( ) arrow key.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.3.2 Alarms 4.3.2.3 Custom Alarms A custom (user confi gured) alarm is activated upon As programmed into the system controller, an alarm detection of one or more programmed alarm conditions condition activates the summary alarm logic which as set by the operator in the Service>Options>Custom...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.4 Controller Operation The E ² Series controller is designed to control an air conditioning system in a space or process application to temperature and humidity levels as defi ned by the user. Conditioned air is supplied to the space as needed to maintain the temperature/humidity control setpoints.
Page 43
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual The E 2 controller continually analyzes the demand 4.4.2 Control Methods for cooling, humidifying and dehumidifying against System operation depends on the controller's programmed the control setpoints and determines the appropriate operating confi...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Actual Temp/RH (Dewpoint) Setpoint Cool Only- No Humidifi cation Needed Psychrometric Chart Figure 15- Dewpoint Control 4.4.3 Operating Confi gurations The operating confi guration for the controller depends on Minimum what type of air conditioner is being controlled (i.e. AR,...
Page 45
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual The control output signal is matched to the valve. If the If one of the fans fails to operate, the controller alerts valve typically opens at 2.5 VDC, the control I/O module...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.4.5 Remote On/Off 4.5 Menu Screens For Remote On/Off operation, terminal positions are 4.5.1 Main Menu provided to connect a remotely located, On/Off switching MAIN MENU control device. If the A/C unit is turned on and the...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.5.2 Information Menu Loop MAIN MENU The Info menu screens may be accessed from the Main screen by simply Factory scrolling with the Up ( ) and Down ( ) arrow keys. The same screens may INFO also be viewed if you enter the Info menu by pressing the "Prg"...
Page 48
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Information Menu Screen Lock Feature (Continued from previous page) You may lock any of the status display screens, bypassing the display screen time-out function. This is sometimes useful to maintain visibility to a specifi c screen when testing, making adjustments or troubleshooting the system.
Page 49
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Information Menu (Continued from previous page) EHGB Status 4.5.2.10 EHGB Status Pos: 50.0% Displays the current operating position of the electronic hot gas bypass valve. Temp: 30.0°F The current suction temperature appears below. The bar gauge next to the valve icon provides a visual representation of the output signal controlling the valve position.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Alarm Log Menu 4.5.3 Alarm Log The application software supports two (2) types of MAIN MENU alarms, “Non-Critical” and “Critical”. Any alarm may be Info programmed to activate the “Custom” (user confi gured) alarm relay contacts.
Page 51
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Alarm Log Menu 4.5.3.4 Alarm Screen Messages ALARM MESSAGE DESCRIPTION OF ALARM CONDITION High Temperature Air temperature is above user defi ned alarm setpoint. Low Temperature Air temperature is below user defi ned alarm setpoint.
Main cycle: Boot: 4.03 03/07/06 3.4 cycles/s 285ms Press ( ) Key Two Version screens are provided for information only. They show controller hardware and software details that are useful to STULZ Product Support if technical assistance is needed. 4-20...
Page 53
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Control Menu 4.5.4.1 Setpoint Screens Fan Control Fan links: None CONTROL Upper Fan Spd Ctrl: Version Var frm Avg Upper Fan Spd Ctrl: Var frm Avg Upper Fan Spd Ctrl: Var frm Avg...
Page 54
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Control Menu humidity drops to the High Humidity Alarm setpoint Humidity Alarm (70.0%) - the Offset (5.0%) Low alarm Enable:Yes Setpoint 30.% 70.0% - 5.0% = 65.0% STATUS________________ Hum: 45.6% Set:45.0% The High Humidity Alarm will cancel at 65%.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu 4.5.5 Service Menu Loop 4.5.5.1 Humidity The cut-in/cut-out offsets for the Dehumidifi cation modes MAIN MENU may be adjusted from the Service>Humid menu. Control SERVICE SERVICE Cool Factory HUMID...
Page 56
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu 4.5.5.3 Sensors 4.5.5.4 Blower SERVICE SERVICE Alarms Sensors SENSORS BLOWER Blower Options From the Service>Sensors menu you may access From the Service>Blower menu you may access screens multiple display screens to enter offsets for calibrating to view and adjust the blower speed parameters.
Page 57
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu fan speed is 90%, the fans will run at 60% during 4.5.5.5 Options Menu Loop dehumidifi cation. SERVICE Blower 25%- Zone 75%- Zone Minimum Maximum OPTIONS 100% (Off) Digital In From the Service>Options menu you may press the...
Page 58
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu after turning the unit on with a remote on command. EXAMPLE 3: Humidity Offset Multiplier "Airfl ow delay"- Time delay for allowing the blowers If 1.3 is entered, the offset for humidity is multiplied by to reach adequate speed before the air proving sensor 1.3.
Page 59
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu 4.5.5.5.4 Custom Setup From the Service>Options>Custom Setup screen you may press the Enter Custom Setup key to access a menu loop to set up custom alarm features. Any controller Setup the alarm text, alarm or signal failure will activate the summary alarm output.
Page 60
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu Alarms 1 to 8 Alarms 9 to 16 Description mask Default Description mask Default Upper Fan alarm Filter alarm Lower fan alarm Fire/Smoke alarm Middle fan alarm Water detection alarm...
Page 61
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu 4.5.5.5.7 Work Group Screens only. It shows the state of each digital input as either Closed (+24 V) or Open (Gnd). The Service>Group display screens shown below only appear if two or more units are wired together as a group.
Page 62
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Service Menu 4.5.5.9 Save Confi guration Set Passwords SERVICE BMS Comm Control: Service: SAVE CFG Factory The second Service>Save Cfg menu screen allows you to The default setpoints may be restored and passwords may set new passwords for entering the Control and Service be changed from the Service>Save Cfg menu.
In this mode, the Lead controller will rotate duty between in the fi eld with assistance from STULZ Product Support. the grouped A/C units to promote equal run time and A unit may also be designated as "Out of Service".
The rotation time period is typically 1 week, however it take the lead). In this case the message "No_Rot" may be set by the user via the Factory menu. Call STULZ appears after the duty assignment displayed in the main Product Support for assistance when accessing the screen.
Page 65
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual The Display Address Changed screen will appear indicating Display address the display address selected is not the same as the one saved changed previously and the new value will be saved to the permanent memory.
Page 66
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 7. The Priv/Shared column indicates the type of terminal. The workgroup is setup using private terminals. Do not change the value (“Pr”). Press the ( ) key to move to the last fi eld 8.
Page 67
Press the Enter ( ) key twice and you'll be prompted to enter the MAIN MENU password for the Factory level (contact STULZ Product Support for Service the password). FACTORY Once the Factory level password is entered, press Enter ( ) to call up the menu screens.
Page 68
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Group Rotation Factory>Group>Group Rotation (Screen 2) Force Rotation Number of Days Hour of Day Cur lead 1 Rot Unit 0 Next lead 0 Value 0 From this screen you may set the schedule to rotate operation of the A/C units to promote equal run times.
Page 69
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Capacity Assist Assist Time 300s Factory>Group> Capacity Assist (Screen 3) Cooling Cut in 1.0° Cut out 0.0° Each A/C unit in the group may be assigned local cut-in and cut-out setpoints for it's capacity assist operation. The values entered are offsets which are applied to the control setpoints established at the lead controller.
Page 70
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Group Averaging Factory>Group>Group Averaging (Screen 5) Use unit sensors when in Standby or Assist for Group Averaging Temp/Hum Sensors Static Pr Sensors Display description Description Variables Default Temp/Hum Sensors Enter Yes for the unit to respond to it's local...
Page 71
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Group Alarms 17 to 24 Group Alarms 25 to 32 Description mask Default Description mask Default High temperature Upper temp sensor Low temperature Middle temp sensor High humidity Lower temp sensor...
Page 72
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Group Status Factory>Group>Group Status (Screen 8) Running Active Standby Assist Online Out of Service This screen provides an overview of the current duty status for all the A/C units combined in the group.
Page 73
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.6.2.7 Service>Options>Group Menu Screens Accessed in the Service menu, the Service>Options>Group Setup screens only appear if two or more units are wired together as a work group. 4.6.2.7.1 Group Setup 4.6.2.7.4 Group Sensors...
Page 74
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.6.2.8 Information Menu Group Menu Screens The following display screens are available in the Information menu loop (Section 4.5.2.8) if two or more units are wired together as a group. They display key operating parameters for grouped A/C units.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.7 BMS Communication 4.7.1 Direct BMS Control The controller may be confi gured to accept proportional When BMS communication is utilized, the controller must analog signals that mimics a sensor. The controller will act...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.8 Troubleshooting the Control I/O Module Signal LED's The E 2 control I/O module includes 3 signal LED's (red, yellow and green) that provide information on the operation of the control module and status of the connection to the pLAN. These signal LED's are positioned adjacent to the yellow, "Power On"...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.9 BMS Parameters, Version 1.2 Supported Speed Media Connection Notes Protocols BACnet over IP 10 Mbps 10BaseT RJ45 direct unit connection Uses BMS addresses BACnet over 10 Mbps 10BaseT RJ45 direct unit connection...
Page 78
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.9.2 Unsigned Values for HTTP, SNMP / Modbus Holding Registers / Analog Values for BACnet Modbus BACnet Description Default Direction Address Address Address 1001 Cooling analog output 1002 Middle Fan Speed analog output...
Page 79
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.9.3 Boolean Values for HTTP, SNMP / Modbus Coils / Binary Values for BACnet Modbus BACnet Description Default Direction Address Address Address Global alarm output System on status Airfl ow has been proven Call for cooling Call for humidifi...
Page 80
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.9.5 Sensor Failure Packed Bit Variables Sensor Failures 1 Sensor Failures 2 Middle temperature Reserved Upper temperature Reserved Lower temperature Reserved Return temperature Reserved Return humidity Reserved Static air pressure Reserved...
Page 81
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 4.9.7 Digital Output Packed Bit Variables Digital Outputs 1 Digital Outputs 2 Global alarm Reserved Custom alarm 1 Reserved Master fan enable Reserved DX1 enable Reserved DX1 liquid line solenoid Reserved Humidifi...
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual MAINTENANCE 5.1.1 Filters The fi lter is usually the most neglected item in an air 5.1 Periodic General Maintenance conditioning system. To maintain effi cient operation, the fi lter should be checked every 3 to 6 months and Systematic, periodic general maintenance of the cleaned or replaced as required.
Page 83
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 5.1.1.2 Cartridge Filters Replaceable cartridge fi lters are held in place by an end cap in the bottom of the Rear Access rear access panel. Lay the access panel Panel down on a piece of cardboard and remove the four screws holding the end cap in place.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 5.2 Troubleshooting Turn off all power to the unit before conducting any troubleshooting procedures, unless the procedure specifi cally requires the system to operate. For troubleshooting purposes, the system may be operated with the doors open by using a pair of channel lock pliers to turn the shaft of the main power disconnect switch to the “On”...
Page 85
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual SYMPTOM PROBABLE CAUSE RECOMMENDATION Compressor Fails to Start c. Complete loss of refrigerant charge Locate and repair leak. Recharge system. (cont.) (low pressure safety switch tripped). d. Condenser pressure too high Check condenser for obstructions.
Page 86
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual SYMPTOM PROBABLE CAUSE RECOMMENDATION Condenser Pressure too a. Non-condensable gas or air in the Recover system, evacuate per Section High (CRS-A Units) system. 2.10.2.2, recharge. Replace drier/strainer. b. Condenser air intake is blocked.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Field Service 5.3.2 DX System It may be necessary to perform repairs on the Repairs must be performed by a journeyman, refrigeration system. If fi eld repairs are necessary, refrigeration mechanic, or air conditioning technician.
Page 88
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual pungent odor once the system has been opened. CAUTION If a burnout has occurred, the oil will be black and acidic. A mechanical failure will have no burned odor PVE oil is used in systems with R410A refrigerant.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual 8. Recharge the system through the access valve on the suction line fi lter-drier. 9. Turn on power at the main power disconnect Inlet Ring switch and start the system. 10. A permanently installed suction line fi lter-drier permits small-system cleanup to be completed in one service call.
UPS ground the customer is returned to STULZ within 30 days of the purchase date. responsible for the shipping charges. If you do not have Spare part sales over 30 days old will be considered established credit with STULZ you must give a freight fi...
CyberRow Series APPENDIX A - FORMS STULZ Air Technology Systems Inc. Frederick, Maryland USA 21704 Telephone: (301) 620-2033 Facsimile: (301) 620-1396 Checklist for Completed Installation Proper clearances for service access have All wiring connections are tight. been maintained in front of the equipment.
STULZ CyberRow DX Series Installation, Operation & Maintenance Manual Appendix B – Glossary Defi nition of Terms and Acronyms STULZ - STULZ Air Technology Systems, Inc. MAX FUSE - Maximum Fuse BTU/Hr - British Thermal Units Per Hour MCA -...
Need help?
Do you have a question about the CyberRow DX CRS-042-W and is the answer not in the manual?
Questions and answers