Connection Of The Dc Reactor (Fr-Hel) - Mitsubishi Electric 800 Series Instruction Manual

Connection
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

*6
Always connect terminal RDYB on the FR-CV to a terminal where the X10 signal or MRS signal is assigned on the inverter. Always connect
terminal SE on the FR-CV to terminal SD on the inverter. Not connecting these terminals may damage the FR-CV.
NOTE
• The safety communication model (FR-E800-SCE) is not intended for the use with the power regeneration common converter
(FR-CV).
• The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1, S2/L2, and T2/L3 must
be matched.
• Use the sink logic when the FR-CV is connected. It cannot be connected when the source logic is selected.
• Do not connect a DC reactor (FR-HEL) to the inverter when the FR-CV is connected.
2.9.6

Connection of the DC reactor (FR-HEL)

• Keep the surrounding air temperature within the permissible range (-10 to +50°C). Keep enough clearance around the
reactor because it heats up. (Take 10 cm or more clearance on top and bottom and 5 cm or more on left and right
regardless of the installation direction.)
• When using the DC reactor (FR-HEL), connect it to terminals P/+ and P1.
In this case, the jumper connected across terminals P/+ and P1 must be removed. Otherwise, the reactor will not be
effective.
• Select a DC reactor according to the applied motor capacity. (Refer to
• Since the DC reactor (FR-HEL) is electrically connected to the enclosure through mounting screws, the DC reactor is
earthed (grounded) by being securely mounted to the enclosure. However, if the DC reactor is not earthed (grounded)
securely enough, an earthing (grounding) cable may be used.
NOTE
• The wiring distance must be within 5 m.
• As a reference, the cable gauge for the connection must be equal to or larger than that of the power cables (R/L1, S/L2, T/L3)
and the earthing (grounding) cable. (Refer to
88
2. Installation and Wiring
2.9 Connection of stand-alone option units
10 cm or more
5 cm or
5 cm or
more
more
P1
Remove
the jumper
page
47.)
5 cm or
5 cm or
more
more
P/+
FR-HEL
page
110.)

Advertisement

Table of Contents
loading

Table of Contents