Main Circuit Terminals; Details On The Main Circuit Terminals - Mitsubishi Electric 800 Series Instruction Manual

Connection
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.5

Main circuit terminals

2.5.1

Details on the main circuit terminals

Terminal symbol
Terminal name
*1
AC power input
R/L1, S/L2, T/L3
U, V, W
Inverter output
P/+, PR
Brake resistor connection for
P/+, N/-
Brake unit connection
P/+, P1
DC reactor connection for
Earth (ground)
*1
Terminal T/L3 is not available for the single-phase power input model.
Terminal function description
Connect these terminals to the commercial power supply.
Connect these terminals to a three-phase squirrel cage motor or a PM
motor.
Connect an optional brake resistor (FR-ABR, MRS, or MYS model)
across terminals P/+ and PR. (A brake resistor cannot be connected to
the FR-E820-0008(0.1K), FR-E820-0015(0.2K), FR-E820S-
0008(0.1K), and FR-E820S-0015(0.2K).)
Connect the brake unit (FR-BU2, FR-BU, or BU), power regeneration
common converter (FR-CV), or multifunction regeneration converter
(FR-XC in power regeneration mode) to these terminals.
Remove the jumper across terminals P/+ and P1, and connect a DC
reactor.
When a DC reactor is not connected, the jumper across terminals P/+
and P1 should not be removed.
For earthing (grounding) the inverter chassis. Be sure to earth (ground)
the inverter.
Refer to
page
81
84
88
51
10
45
2. Installation and Wiring
2.5 Main circuit terminals