2.5
Main circuit terminals
2.5.1
Details on the main circuit terminals
Terminal symbol
Terminal name
*1
AC power input
R/L1, S/L2, T/L3
U, V, W
Inverter output
P/+, PR
Brake resistor connection for
P/+, N/-
Brake unit connection
P/+, P1
DC reactor connection for
Earth (ground)
*1
Terminal T/L3 is not available for the single-phase power input model.
Terminal function description
Connect these terminals to the commercial power supply.
Connect these terminals to a three-phase squirrel cage motor or a PM
motor.
Connect an optional brake resistor (FR-ABR, MRS, or MYS model)
across terminals P/+ and PR. (A brake resistor cannot be connected to
the FR-E820-0008(0.1K), FR-E820-0015(0.2K), FR-E820S-
0008(0.1K), and FR-E820S-0015(0.2K).)
Connect the brake unit (FR-BU2, FR-BU, or BU), power regeneration
common converter (FR-CV), or multifunction regeneration converter
(FR-XC in power regeneration mode) to these terminals.
Remove the jumper across terminals P/+ and P1, and connect a DC
reactor.
When a DC reactor is not connected, the jumper across terminals P/+
and P1 should not be removed.
For earthing (grounding) the inverter chassis. Be sure to earth (ground)
the inverter.
Refer to
page
—
—
81
84
88
51
10
45