INPUT / OUTPUT WIRING
When the Exit terminal is shorted to 0V, the Exit LED will illuminate and the ACU will operate Relay 1.
The reader/exit button Green LED will flash during this period. More than one exit button can be wired in
parallel. Relay 1 will remain transfered while the short to 0V remains.

Exit button

Where fitted, a 'push to make' button is required.
(See Specification table for ratings)
The Exit LED will be ON when the switch is closed. -
Button Pushed.

Door Contact

A NO switch may be fitted so that it is held closed while
the door is shut.
The Contact LED will be ON when the switch is closed.
- Door Closed.
When connected, Net2 will check the door position during
access activity and will raise an Alarm in the event of a
'Door Forced' or 'Door left open' condition.

Tamper switch

The ACU supplied in a plastic housing has a 'NO' tamper
switch fitted and pre-wired into the circuit board.
The Tamper LED will be ON when the switch is closed.
Net2 will monitor the switch position and will raise an
Alarm in the event of a 'Tamper' condition.
Connect to a UL listed burglar alarm unit for supervision.
PSU monitoring
The PSU LED will be ON when the NO Relay contacts are
closed. - Power OK.
The Net2 software will monitor the relay contacts
and will raise an Alarm in the event of a 'Power Fail'
condition.
Door Bell - Relay 2
Pressing the bell button on the keypad will result in
Relay 2 being energized for 1 second. A bell sounder
can be controlled by wiring one of the bell feeds
across COM / NO on the relay.
See Specification table for Output Ratings