Overall torque limit
Besides the above two sources, an overall torque limit is also available. The overall torque
limit takes effect when a quick stop (OFF3) happens. In this case, the servo drive brakes
with a maximum torque.
You can configure the overall torque limit by setting the following parameters:
Parame-
p1520
p1521
Internal torque limit
Select an internal torque limit by setting the following parameters:
Parameter
p29050[0]
p29050[1]
p29051[0]
p29051[1]
The following diagram shows how the internal torque limit functions:
Torque limit reached (TLR)
When the generated torque has nearly (internal hysteresis) reached the value of the positive
torque limit or negative torque limit, the signal TLR is output.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2020, A5E37208830-008
Value range
ter
-1000000.00 to
20000000.00
-20000000.00 to
1000000.00
Value range
-150 to 300
-150 to 300
-300 to 150
-300 to 150
Default
Unit
0
Nm
0
Nm
Default
Unit
300
%
Internal torque limit 1 (posi-
tive)
300
%
Internal torque limit 2 (posi-
tive)
-300
%
Internal torque limit 1 (neg-
ative)
-300
%
Internal torque limit 2 (neg-
ative)
Control functions
7.3 Speed control (S)
Description
Overall torque limit (positive)
Overall torque limit (negative)
Description
Digital input (TLIM)
0
1
0
1
201