Bosch Worcester 14/19CBI Installation And Servicing Instructions page 38

Wall mounted boilers for central heating and indirect supply of domestic hot water
Hide thumbs Also See for Worcester 14/19CBI:
Table of Contents

Advertisement

No
Is the gas supply
connected and at the
correct pressure?
Yes
Remove boiler casing.
Reset and restart
No
the boiler.
Can a flame be seen
through the spyglass?
Note: there is a 20
second delay from fan
on to spark.
Yes
TURN OFF GAS SUPPLY.
Remove the combustion
No
chamber cover. Is the
sense (right) electrode
and lead in good
condition and is gap
correct?
See Section 15.4.3
Yes
Replace control board.
Note: It is not possible
to reliably check the
cross light performance
of the burner.
In the unlikely event of
such a fault, investigate
condition of flue,
burner and injector.
Also check polarity of
mains voltage supply.
Rectify gas supply
problem.
TURN OFF GAS SUPPLY.
No
Remove inner casing
cover.
Reset and restart boiler.
Does a spark occur
across the electrodes?
Yes
No
During spark period
is there 216V D.C.
across the pins at
connector X2?
Yes
Replace gas valve or
check cable to it.
Repair or replace
flame sense
or cable to it.
NOTE: Do not attempt to light the boiler
with the combustion chamber cover
removed.
38
No
Are the electrodes
and gap and
connections
in good order?
Yes
Replace control board.
Repair or replace
spark electrode
or HT leads.